Pfannenberg DTS 3041 Thermostat Instructions
- June 16, 2024
- Pfannenberg
Table of Contents
Pfannenberg DTS 3041 Thermostat
Product Information
Specifications
- Weight:
- DTS 3041: 28 kg (61.7 lbs)
- DTS 3061: 28 kg (61.7 lbs)
- DTS 3081: 30 kg (66.2 lbs)
- Material: 304 Stainless Steel / Rostfreier Stahl / Acero inoxidable
- IP Rating:
- Type 12 IP 54 (EN 60529) – DTS 3041
- Type 3R/4 IP 56 (EN 60529) – DTS 3061
- Type 4/4x IP 56 (EN 60529) – DTS 3081
Product Usage Instructions
Installation
- Place the unit in a well-ventilated area with sufficient clearance for airflow.
- Connect the air-in and air-out ducts as per the provided diagram.
- Ensure proper sealing of gaskets for efficient operation.
Operation
- Power on the unit and set the desired temperature using the control panel.
- Monitor the ambient air temperature to adjust settings if needed.
- Check for any unusual noises or malfunctions during operation.
Maintenance
- Regularly clean the air filters to maintain optimal airflow.
- Inspect and replace any worn-out sealing gaskets to prevent air leaks.
- Schedule professional maintenance checks as recommended by the manufacturer.
FAQ
Q: What should I do if the unit is making loud noises?
A: Check for any loose components or obstructions in the air ducts. If the issue persists, contact customer support for further assistance.
Q: How often should I replace the air filters?
A: It is recommended to replace the air filters every 3 to 6 months depending on usage and environmental conditions.
Q: Can I use this product outdoors?
A: The product is designed for indoor use. Using it outdoors may affect its performance and longevity.
Wiring
-
1 CAP Capacitors- Compressor fans
-
2 CAP Capaci1ors- Condenser fan
-
2HTR Crankcase-heater
-
Heater
-
Compressor
-
Condenser fan
-
Evaporator fan
-
High pressurestat
-
Fan cycle pressurestat
-
Cooling Thermostat
-
Enclosure Heater
-
Heater Thermostat
-
Transformer
-
Connection mains
-
Connection door contact + failure indication
-
3-4 Door Contact
If door contact is used, remove the bridge between wires 3 + 4 -
Transformer Switch (3 + 1 = 460V; 3 + 2 = 400V)
-
-
WNL Live conductor junction
-
WNN Neutral conductor junction
-
CON 10 Main relay
NOTICE
- Before installation/operation of this unit, read the installation/operation manual completely. Installation/operation should only be completed by properly trained personnel
- Minimum distance to obstructions – 200mm (Exterior) – 100mm (Internal)
- DO NOT APPLY external voltage to the door contact switch. Damage to the unit may result.
Unit Dimensions
Technical Data
Cooling Data | DTS 3041 | DTS 3061 | DTS 3081 |
---|---|---|---|
Cooling capacity (Q0) A35°C(95°F)/A35°C(95°F) | 765 W (2610 BTUh) | 698 W (2382 |
BTUh)
Cooling capacity (Q0) A50°C(122°F)/A40°C(104°F)| 366 W (1250 BTUh)| 334 W
(1140 BTUh)
Refrigerant type| R-134a 400 g (14.1 oz.)
Adjustable thermostat setting 1TAS (factory set)| 10°C – 40°C Factory Setting
35°C
(50°F – 104°F Factory Setting 95°F)
Ambient air temperature| 8°C – 45°C
46°F – 114°F
| 0°C – 55°C
32°F – 131°F
Air volume, external circulation| 150 m³/h (88 cfm)| 150 m³/h (88 cfm)
Air volume, internal circulation| 325 m³/h (191 cfm)| 325 m³/h (191 cfm)
Condensation discharge| ½“ FNPT connection
Electrical data|
Voltage| 460v-60Hz-1Φ (400v-50Hz-1Φ) – Voltage +/- 10%
Power consumption| 789 W| 760 W
Nominal Running Current| 0.76 A
Recommended Maximum Fuse Size – NO HEATER OPTION| 5 A (Time Delay Fuse Class
CC)
Recommended Maximum Fuse Size – WITH HEATER OPTION| Not Available
Certifications| CE, CULUS
Heating data – Non-Standard Option
Internal Thermostat| 10°C – 40°C (50°F – 104°F)
Heating capacity| N/A| 900 W
Specifications|
Weight| 28 kg (61.7 lbs)| 28 kg (61.7 lbs)| 30 kg (66.2 lbs)
Unit construction| G90 Galvanized Steel. Electrostatically powder coated.
Baked (200°C / 392°F)| 304 Stainless Steel
Sound Level|
Protection classification (against the enclosure, under correct operating
conditions)| Type 12
IP 54 (EN 60529)
| Type 3R/4
IP 56 (EN 60529)
| Type 4/4x
IP 56 (EN 60529)
Spare Parts
Please order your spare parts only with the Pfannenberg parts number.
Description | DTS 30×1 |
---|---|
Internal fan | 18811000001 |
External fan | 18811100011 |
Thermostat | 18883000001 |