ESPitON ES-EOE Series LED Emergency Converter Owner’s Manual

June 12, 2024
ESPitON

ESPitON ES-EOE Series LED Emergency Converter

ESPitON ES-EOE Series LED Emergency Converter

Features

  • Constant output power
  • Used with lithium battery
  • Suits for LED fitting with external LED driver
  • Accessary test switch and LED indicator
  • Auto Testing – Self Diagnostic Operation
  • With multi-protection function:
    • battery overcharge protection;
    • battery over-discharge protection;
    • output overload protection;
    • short-circuit protection

Technical Data

Input voltage 220-240 Vac 50/60Hz
Input Current 0.06A (Max) 230V AC
Input Power <2W @230Vac
Power Factor ≥0.5
Output voltage range 10-50VDC
Max.output current 170mA
Battery charging current 200mA(Max)
Battery charging time 24h(Max)
Working temperature 0-60℃
Maximum shell temperature 75℃
Storage temperature -20-60℃
Electric strength 3000Vac 5mA (input to output)
IP Rating IP20
Warranty 3 Years

Status LED & Test button

LED Indicator Green on keep on represents the battery is charging

Slow flashing means monthly inspection test
Quick flshing means annual inspection test
Red on| Blinking every three seconds indicates the battery is faulty
Blinking second times every three seconds

indicates the LED fixture is faulty

Blinking three times every three seconds indicates the emergency time test failed

Self-test

| Monthly inspection test| Test 18 minutes every month
Annual inspection test| Test 180 minutes every year

Test button

| Press the button one time| Reset the self-test time
Press the button keep 3 seconds| Automatically switch to self-test mode for five minutes

Model Selection table

Model No.

| Input voltage| Ouput voltage| Emergency power| Lithium battery| Emergency time| Output current
---|---|---|---|---|---|---
ES-EOE01-01S| 220-240Vac 50/60Hz| 10-50V DC| 1W| 2000mAh/3.7V| 3Hrs|

100-20mA

ES-EOE02-01S

| 220-240Vac 50/60Hz| 10-50V DC| 2W| 2500mAh/3.7V| 3Hrs| 200-40mA
ES-EOE03-01S| 220-240Vac 50/60Hz| 10-50V DC| 3W| 3000mAh/3.7V| 3Hrs|

300-60mA

Dimension (Unit:mm)

Dimension \(Unit:mm\)
Dimension \(Unit:mm\)

Wiring Diagram

Wiring Diagram
Wiring Diagram

Mechanical Structure

Operation Instructions

  1. Connect the wires according to the wiring diagram.
  2. Power on L and N, and close the switch S1. At this time, the load light will turn on, the indicator light of the emergency power supply will turn green, and the emergency power supply is charged normally. Turn off this switch S1, the load light will go out.
  3. Simulated emergency: close switch S1, turn on the load light, and then press the switch (TEST SWITCH),  then switch to emergency power supply mode, the green light of the emergency power indicator will go out. Then release  the switch (TEST SWITCH), at this time it should be switched to external drive power supply, the green light of the emergency power indicator will light up.
  4. Power failure and incoming call, the phenomenon should be the same as simulated emergency

Battery Application Notice

  1. The battery should be recharged and discharged semiannually in normal use conditions.
  2. Do not connect to the circuit when the battery is not use to prevent over-discharge of the battery due to self-consumption of the circuit board.
  3. Please keep the battery from the heat source when installing and using, and only be allowed to use incertain working temperature range.
  4. The battery should be stored in a cool and dry environment.
  5. After long time storage, the battery is cycled every 6 months as required.

www.haisensz.com