ESPitON ES-EOE Series LED Emergency Converter Owner’s Manual
- June 12, 2024
- ESPitON
Table of Contents
ESPitON ES-EOE Series LED Emergency Converter
Features
- Constant output power
- Used with lithium battery
- Suits for LED fitting with external LED driver
- Accessary test switch and LED indicator
- Auto Testing – Self Diagnostic Operation
- With multi-protection function:
- battery overcharge protection;
- battery over-discharge protection;
- output overload protection;
- short-circuit protection
Technical Data
Input voltage | 220-240 Vac 50/60Hz |
---|---|
Input Current | 0.06A (Max) 230V AC |
Input Power | <2W @230Vac |
Power Factor | ≥0.5 |
Output voltage range | 10-50VDC |
Max.output current | 170mA |
Battery charging current | 200mA(Max) |
Battery charging time | 24h(Max) |
Working temperature | 0-60℃ |
Maximum shell temperature | 75℃ |
Storage temperature | -20-60℃ |
Electric strength | 3000Vac 5mA (input to output) |
IP Rating | IP20 |
Warranty | 3 Years |
Status LED & Test button
LED Indicator | Green on | keep on represents the battery is charging |
---|
Slow flashing means monthly inspection test
Quick flshing means annual inspection test
Red on| Blinking every three seconds indicates the battery is faulty
Blinking second times every three seconds
indicates the LED fixture is faulty
Blinking three times every three seconds indicates the emergency time test failed
Self-test
| Monthly inspection test| Test 18 minutes every month
Annual inspection test| Test 180 minutes every year
Test button
| Press the button one time| Reset the self-test time
Press the button keep 3 seconds| Automatically switch to self-test mode for
five minutes
Model Selection table
Model No.
| Input voltage| Ouput voltage| Emergency power| Lithium
battery| Emergency time| Output current
---|---|---|---|---|---|---
ES-EOE01-01S| 220-240Vac 50/60Hz| 10-50V DC| 1W| 2000mAh/3.7V| 3Hrs|
100-20mA
ES-EOE02-01S
| 220-240Vac 50/60Hz| 10-50V DC| 2W| 2500mAh/3.7V| 3Hrs| 200-40mA
ES-EOE03-01S| 220-240Vac 50/60Hz| 10-50V DC| 3W| 3000mAh/3.7V| 3Hrs|
300-60mA
Dimension (Unit:mm)
Wiring Diagram
Mechanical Structure
Operation Instructions
- Connect the wires according to the wiring diagram.
- Power on L and N, and close the switch S1. At this time, the load light will turn on, the indicator light of the emergency power supply will turn green, and the emergency power supply is charged normally. Turn off this switch S1, the load light will go out.
- Simulated emergency: close switch S1, turn on the load light, and then press the switch (TEST SWITCH), then switch to emergency power supply mode, the green light of the emergency power indicator will go out. Then release the switch (TEST SWITCH), at this time it should be switched to external drive power supply, the green light of the emergency power indicator will light up.
- Power failure and incoming call, the phenomenon should be the same as simulated emergency
Battery Application Notice
- The battery should be recharged and discharged semiannually in normal use conditions.
- Do not connect to the circuit when the battery is not use to prevent over-discharge of the battery due to self-consumption of the circuit board.
- Please keep the battery from the heat source when installing and using, and only be allowed to use incertain working temperature range.
- The battery should be stored in a cool and dry environment.
- After long time storage, the battery is cycled every 6 months as required.
www.haisensz.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>