magic-pak MCE4-12-14 Electric Cooling Heating Packaged Unit Owner’s Manual
- June 12, 2024
- magic-pak
Table of Contents
- MCE4-12-14 Electric Cooling Heating Packaged Unit
- APPLICATIONS
- STANDARD FEATURES
- CONDENSATE MANAGEMENT
- OPTIONS & ACCESSORIES
- UNIT DIMENSIONS (IN.)
- MINIMUM CLEARANCES
- 1 thru #2| 10| 15| 20| 24| 28
- 1 thru #3| 12| 18| 25| 32| 38
- 1 thru #4| 18| 28| 36| 45| 54
- 1 thru #5| 23| 35| 46| 57| 69
- 1 thru #6| 27| 41| 54| 67| 80
- 1 thru #7| 32| 48| 63| 78| 93
- 1 thru #8| 37| 55| 73| 90| 107
- 1 thru #9| 41| 61| 80| 100| 118
- RATED COOLING & HEATING PERFORMANCE
- Documents / Resources
MCE4-12-14 Electric Cooling Heating Packaged Unit
Owner’s Manual
M-SERIES™ MCE4-12/14
ELECTRIC COOLING / ELECTRIC HEATING PACKAGED UNIT
FORM NO. MCE4-100 (10/2022)
MCE4-12-14 Electric Cooling Heating Packaged Unit
MODEL NUMBER GUIDE
- Check that equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation.
APPLICATIONS
- MagicJack units are designed for use in all multifamily applications, such as: apartments, condominiums, student housing and senior living
- Installation in conditioned and non-conditioned mechanical spaces
UNIT APPROVALS
ETL (INTERTEK)
- Design certified by ETL (Intertek) to latest edition of UL 1995
- Certified for the U.S. and Canada
- Certified for less than 1.4% cabinet air leakage using ASHRAE Standard 193
- Factory-installed electric heaters are ETL listed for the U.S. and Canada
- Rated with a 5kA Short Circuit Current Rating (SCCR) in accordance with RMS Symmetrical per UL 508A
- Refer to Unit Electrical and Physical Data table for additional details
AHRI/DOE
- Certified to AHRI Standard 210/240-2008; refer to the AHRI Directory for AHRI certificates
- Rated and tested in accordance with DOE test procedures (latest edition) and Federal Trade Commission (FTC) labeling regulations
CORROSION PROTECTION
- Epoxy coating is specifically designed for use on HVAC type coils and demonstrates 6800+ hours of Sea Water Acetic Acid Testing (SWAAT) per ASTM G85:A3
SOUND RATING
- Outdoor sound level measurements tested per ANSI/AHRI Standard 270
- Refer to Outdoor Sound Rating & Cabinet Air Leakage table for additional details
ALUMINUM LOUVER – PAINT SPECS
- Standard and impact-resistant louvers meet AAMA 2605 specifications
WARRANTY
COMPRESSOR
- Five (5) years limited parts warranty
ALL OTHER COVERED COMPONENTS
- Refer to Equipment Limited Warranty for additional details
STANDARD FEATURES
AIRFLOW CHOICE
-
Factory shipped ready for top supply and return duct connections
-
Return air may be brought in through the optional front return opening
NOTE: If ductwork is attached to the optional front return opening, provisions to service unit filter must be provided
NOTE: Filter may need to be relocated to a suitable location outside the cabinet for ease of service -
Front access panel doubles as cover for top return (except 3.0 ton)
ELECTRICAL CONNECTIONS & GAUGE PORTS
- Line voltage knockouts (two concentric) to accommodate field required wire size
- Thermostat connections are located at the top of the cabinet
- Two gauge ports are located within the lower compartment of the unit
- Refer to Unit Dimension figure for additional details
CABINET
- Embossed galvanized steel cabinet
- Indoor section of the cabinet insulated with 0.5 in. dual density fiberglass insulation
- Outdoor section of the cabinet insulated with 0.5 in. weather-resistant polystyrene insulation
INTERNAL FILTER
- Tool-less filter access
- Factory-installed 1 in. filter rack with washable filter
- Field-supplied filters up to MERV 6 can typically be installed in the filter slot internal to unit in lieu of washable filter, when proper duct design is applied
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop and Blower Performance tables for additional details
VENTILATION AIR
- Units are outfitted with ventilation air openings and are shipped with the openings sealed
- Refer to Ventilation Air Capability table and Optional Field-Installed Accessories section for additional details
- Check that equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation
REFRIGERATION SYSTEM
- Factory charged with R-410A refrigerant
- Factory sealed and tested
- Refer to Unit Electrical and Physical Data table for additional details
Indoor and Outdoor Coils
- Copper tube with aluminum fin coils
High Pressure Switch
- Shuts off unit if abnormal operating conditions cause the refrigerant discharge pressure to rise above acceptable levels
Low Pressure Switch
- Provides loss of charge protection by shutting off unit if refrigerant liquid pressure falls below acceptable levels
TRANSFORMER
- Rated for 40VA
- Factory wired for 230/240V power supply, and includes field selectable terminal for 208V
- Converts line voltage to 24V for the thermostat and control circuits within the unit
SUPPLY AIR BLOWER
Constant Torque ECM Blower Motor
- Motor provides specified air volume at 0.1 in. – 0.5 in. w.c. external static pressure
- Blower assembly is easily removed for servicing
- Refer to Blower Performance tables for additional details
Electronic Blower Control
- Dedicated blower speed taps for continuous fan, cooling, and heating operation are programmed for optimal airflow and controlled by 24V thermostat signals
- Blower speed adjustment is easily accomplished by speed tap selection
- Fixed blower delays have been selected to enhance comfort
- Refer to Blower Performance tables for additional details
OUTDOOR FAN
- Heavy duty, fully enclosed and weatherproof
- Aluminum fan blades
CONDENSATE MANAGEMENT
Primary Drain Pan
- Antimicrobial protection: drain pan is injected with an antibacterial agent that destabilizes the membrane of microorganism cells, disrupting the cellular function of odor-causing mold and bacteria so that they can no longer grow or
reproduce
Overflow Protection
- Indoor drain pan overflow switch monitors the condensate level in primary drain pan
- Prevents unit from running if water is sensed
Secondary Drain Pan
- Polypropylene wall sleeve base is specifically designed to direct rain water out of the building and in the event of any restriction in the primary drain will act as a redundant overflow protection
OPTIONS & ACCESSORIES
FACTORY-INSTALLED OPTIONS
ELECTRIC HEAT
- Mounted internal to unit cabinet
- Multiple kW sizes available; must specify the electric heating element size (0kW to 10kW)
- Optional two stage electric heat wiring on 7 &10kW. In order to utilize this option, it will require a thermostat with single stage cooling and two stage heating
- Compatible with 208V, 230V and 240V
- Helix wound nichrome heating elements exposed directly into the air stream resulting in instant heat transfer and low element temperatures
- Cutoff limit control provides positive protection in case of excessive temperatures
- Refer to Rated Cooling & Heating Performance table for additional details
CORROSION PROTECTION
- Epoxy coated indoor and outdoor coils
FIELD-INSTALLED ACCESSORIES
WALL SLEEVES & LOUVERS
- Units must be installed with approved wall sleeve and louver accessories for safe operation and are required for all installations
- Larger height wall sleeves may be used on smaller tonnage equipment to maintain a uniform wall opening on the building façade
- Refer to Wall Sleeves and Louvers table for additional details
WALL SLEEVES (ASLEEVE)
- Penetrates the building envelope and creates a path for condenser air intake and exhaust
- Provides a sealed connection to the unit and a secure attachment foundation for the louvers
- Available in 6 in. to 12 in. depths
WALL SLEEVE EXTENSION (ASLEEVEXT4)
- Provides an additional 4 in. of depth to the wall sleeve, for a maximum depth of 16 in.
LOUVERS
Polypropylene Louvers (ALVRP)
- Constructed from durable, corrosion-resistant plastic
- Available in four standard colors
Aluminum Louvers (ALVRAL)
- Constructed with 6063-T6 grade aluminum
- Available in anodized clear coat, primer (to be painted in the field), standard paint colors and custom colors with paint matching*
Impact-Resistant Aluminum Louvers (ALVRALC)
- Impact and wind load certified up to 186 MPH, risk categories III and IV, and wind exposures C and D
- ALVRALC-1 & ALVRALC-2: FBC Notice of Acceptance (NOA) 20-0909.03
- ALVRALC-3, -4 & -7: FBC Notice of Acceptance (NOA) 21-1216.11
- Constructed with 6063-T6 grade aluminum
- Available in anodized clear coat, primer (to be painted in the field), standard paint colors and custom colors with paint matching*
CRANKCASE HEATER (ACASE841)
-
Warms compressor crankcase to limit migration of liquid refrigerant back to compressor during off cycle
-
Available for models with scroll compressors
-
Refer to Crankcase Heater table for additional details
-
Certain exclusions apply. Refer to louver manufacturer’s literature and warranty documentation.
SHORT CIRCUIT CURRENT RATING KIT (ASCCR)
- Provides 200kA of SCCR protection
- Refer to SCCR Accessory table for additional details
FILTERS
- Field-supplied filters up to MERV 6 can typically be installed in the filter slot internal to unit
NOTE: Use of paper frame not recommended
VENTILATION DAMPERS
- Check that the equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation
Motorized Damper w/ Controller (AVADAMP1)
- Utilizes a ventilation air control module that is field programmable to assist with meeting ASHRAE 62.2 requirements
- Once programmed with values for ventilation air amounts, the control module opens the damper in response to thermostat inputs and monitors the run time
- Upon meeting the ventilation air needs, the control module will close the damper until the start of the next cycle
- If, during an observation period it is determined that thermostat operation alone may not provide the desired ventilation air, the control module can independently operate the unit’s indoor blower, in continuous fan mode, and open the damper to aid in providing ventilation air needs
Motorized Damper w/ Field-Supplied Relay (AVADAMP2)
- Opens ventilation air damper during indoor blower operation and closes during blower off periods
- Requires field-supplied and installed current sensing relay to detect indoor blower operation
HYDRONIC COIL
- Available on 0MCE models (without electric heat)
- Unit may be adapted to include a field-supplied hydronic/hot water coil
THERMOSTAT
- Required for all installations (field-supplied)
- Units are individually controlled with conventional 24V thermostat
- Thermostat must be capable of:
- Single stage cooling and single stage heating (3 and 5 kW single stage electric heat)
- Single stage cooling and two stage heating (7 and 10 kW two stage electric heat)
- Refer to Unit Electrical and Physical Data table for additional details
UNIT ELECTRICAL AND PHYSICAL DATA (208/230 Volt – 1 Phase – 60HZ)1
- Acceptable voltage range: 197 – 253V
- MCA = Minimum Circuit Ampacity
- MOCP = Maximum Over Current Protection
- SCCR = Short Circuit Current Rating; refer to SCCR Accessory table, up to 200kA
NOTE: Units are rated at 208/230V, but MOCP & MCA values are calculated at 240V
NOTE: The 7.2 and 10 kW heats strips offer a W1 and W2 thermostat connection. Taking advantage of the two heat strip circuits requires a 2-stage thermostat (W1 for electric heat stage 1 and W2 for electric heat stage 2). If a single stage thermostat is used, “pigtail” W1 and W2 wires together when connecting the thermostat wires at the unit.
UNIT DIMENSIONS (IN.)
- Dimension B represents the height of the optional front return air duct opening
- Provisions must be made to properly drain condensate from the primary and secondary drain pans.
MINIMUM CLEARANCES
Accessibility Clearances
The front of the unit must be accessible for service. A minimum clearance of
30” in front of unit is required for service.
If the unit is enclosed, a door or access panel aligned with the front of the
unit is the preferred method of providing access. The door or access panel
opening must be a minimum of 30” wide (centered on the unit) and be as tall as
the unit.
IMPORTANT
The unit must be installed with approved wall sleeve and louver accessories
for safe operation. Improper installations could result in property damage,
personal injury, or death.
Supply Duct Clearances
Minimum Clearances to Combustible Materials 1
Front| Sides| Top
0”| 0”| 0”
1 Accessibility clearances take precedence
Unit Clearances | Minimum Clearances 1 |
---|---|
Return Duct Configuration | Unit Height |
Ducted Top Opening | All |
Ducted Front Opening5 | All |
Non-Ducted/ Free Return | 43” |
48” – 68” | 5” |
- Accessibility clearances take precedence
- Clearance must accommodate field-installed condensate drain line / drain trap
- Additional clearance required if field-installed condensate drain line/drain trap is routed alongside unit
- Consult local codes for other clearance requirements
- If ductwork is attached to the optional front return opening, provisions to service unit filter must be provided
OUTDOOR SOUND RATING & CABINET AIR LEAKAGE
Model | Outdoor Sound Rating (dBa)1 | Cabinet Air Leakage (%)2 |
---|---|---|
MCE4-12-091P | 73 | 1.4 |
MCE4-12-121P | 73 | 1.4 |
MCE4-12-181P | 73 | 1.4 |
MCE4-12-241P | 75 | 1.4 |
MCE4-12-301P | 79 | 1.4 |
MCE4-14-361P | 79 | 1.4 |
1 Per ANSI / AHRI Standard 270
2 Per ASHRAE Standard 193
FACTORY FILTER SIZE (IN.) AND PRESSURE DROP (IN. W.C.)
Model| Filter Size|
Supply Airflow (CFM)
---|---|---
200| 300| 400| 500| 600| 700| 800| 900| 1000| 1100
MCE4-12-091P
MCE4-12-121P
MCE4-12-181P| 18 x 20 x 1| 0.01| 0.01| 0.01| 0.02| 0.03| 0.04| 0.05| —| —| —
MCE4-12-241P| 20 x 22 x 1| —| 0.01| 0.01| 0.02| 0.03| 0.03| 0.04| —| —| —
MCE4-12-301P| 24 x 22 x 1| —| —| —| 0.01| 0.01| 0.02| 0.03| 0.03| 0.04| 0.05
MCE4-14-361P| 28 x 22 x 1| —| —| —| —| 0.01| 0.01| 0.02| 0.02| 0.03| 0.03
Performance based on factory-provided washable filter installed in the unit.
If a higher resistance filter is field installed in the unit, the added
resistance must be included in the external static pressure and must not
exceed 0.5 in. w.c. including ductwork.
VENTILATION AIR CAPABILITY
Chart and figure below show the amount of ventilation air as a function of
unit tonnage and total External Static Pressure (supply and return).
Ventilation Air (CFM) * | |
---|---|
Cumulative Knockouts Removed | Total External Static Pressure (supply + return) |
**
0.1| 0.2| 0.3| 0.4| 0.5
0.75, 1.0, 1.5 TON| # 1 Only| 7| 9| 12| 15| 18
1 thru #2| 10| 15| 20| 24| 28
1 thru #3| 12| 18| 25| 32| 38
1 thru #4| 18| 28| 36| 45| 54
1 thru #5| 23| 35| 46| 57| 69
1 thru #6| 27| 41| 54| 67| 80
1 thru #7| 32| 48| 63| 78| 93
1 thru #8| 37| 55| 73| 90| 107
1 thru #9| 41| 61| 80| 100| 118
2.0, 2.5, 3.0 TON | # 1 Only | 21 | 20 | 19 | 17 | 16 |
---|---|---|---|---|---|---|
#1 thru #2 | 28 | 27 | 25 | 24 | 22 | |
#1 thru #3 | 35 | 33 | 32 | 30 | 28 | |
#1 thru #4 | 45 | 42 | 40 | 38 | 35 | |
#1 thru #5 | 55 | 52 | 49 | 46 | 43 | |
#1 thru #6 | 66 | 62 | 59 | 55 | 52 | |
#1 thru #7 | 79 | 75 | 71 | 66 | 62 | |
#1 thru #8 | 91 | 86 | 81 | 76 | 71 | |
#1 thru #9 | 105 | 99 | 94 | 88 | 82 |
- Assumes proper speed tap adjustments to maintain nominal supply air CFM
** Assumes equal supply and return static pressures
WALL SLEEVES & LOUVERS
Note: Wall Sleeve and Louver size must be coordinated
* Louver colors: WHT = white, SAN = sandstone, BGE = beige, TPST = taupe
stone
^ -P: Option to paint standard, aluminum, and impact-resistant louvers
• Wall sleeve and louver sizes equal to the required wall opening dimensions
for the unit size
◦ Optional: Wall sleeves and louvers can be oversized to maintain a uniform
appearance
WALL SLEEVE & WALL OPENING DIMENSIONS (IN.)**
SCCR ACCESSORY
Model | Kit1 |
---|---|
0MCE4-12-091*P | **** ASCCR1 |
3MCE4-12-091P
5MCE4-12-091P| ASCCR2
0MCE4-12-121*P| ASCCR1
3MCE4-12-121P
5MCE4-12-121P| ASCCR2
0MCE4-12-181*P| *** ASCCR1
3MCE4-12-181P
5MCE4-12-181P| ASCCR2
7MCE4-12-181P| ASCCR3
10MCE4-12-181P| ASCCR5
0MCE4-12-241P| ASCCR1
5MCE4-12-241P| ASCCR2
7MCE4-12-241P| ASCCR3
10MCE4-12-241P| ASCCR5
0MCE4-12-301P| ASCCR2
5MCE4-12-301P
7MCE4-12-301P| ASCCR3
10MCE4-12-301P| ASCCR5
0MCE4-14-361P| ASCCR3
5MCE4-14-361P
7MCE4-14-361P
10MCE4-14-361*P| ASCCR5
CRANKCASE HEATER
Model | Kit |
---|---|
MCE4-12-091P | N/A |
MCE4-12-121P
MCE4-12-181P
MCE4-12-241P
MCE4-12-301P| ACASE841
MCE4-14-361P
RATED COOLING & HEATING PERFORMANCE
^ Not a rated value
† Two-stage heat available for 7kW and 10kW units
S/T = ratio of sensible to total cooling load
For most up to date ratings and values, please view AHRI listing
EXTENDED COOLING PERFORMANCE DATA
NOTE: Values based on 0.1” w.c. external static pressure
EXTENDED COOLING PERFORMANCE DATA
NOTE: Values based on 0.3” w.c. external static pressure for
MHP4-12-091P, MHP4-12-121P, MHP4-12-181P, MHP4-12-241P,
MHP4-12-301P, and 0.5” w.c. external static pressure for MHP4-14-361P
BLOWER PERFORMANCE
- Performance based on factory-provided washable filter installed in the unit.
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop table for additional details
N/A: Do not operate unit using this blower speed at this external static
pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted
to Speed Tap 2 for lower duct static applications.
-
As shipped speed for Heating operation. Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications.
SCFM = standard cubic feet per minute
BLOWER PERFORMANCE CONTINUED- Performance based on factory-provided washable filter installed in the unit.
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop table for additional details
N/A: Do not operate unit using this blower speed at this external static
pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted
to Speed Tap 2 for lower duct static applications.
- As shipped speed for Heating operation. Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications.
SCFM = standard cubic feet per minute
BLOWER PERFORMANCE CONTINUED
- Performance based on factory-provided washable filter installed in the unit.
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop table for additional details
N/A: Do not operate unit using this blower speed at this external static
pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted
to Speed Tap 2 for lower duct static applications.
-
As shipped speed for Heating operation. Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications.
SCFM = standard cubic feet per minute
BLOWER PERFORMANCE CONTINUED- Performance based on factory-provided washable filter installed in the unit.
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop table for additional details
215 Metropolitan Drive | West Columbia, SC 29170
800-448-5872
Product Support866-282-7257
www.magic-pak.com
All specifications and illustrations subject to change
without notice and without incurring obligations.
FORM NO. MCE4-100 (10/2022)
© 2022 Allied Air Enterprises LLC, a
Lennox International Inc. Company
Printed in the U.S.A.
Documents / Resources
|
magic-pak MCE4-12-14 Electric Cooling Heating Packaged