Presence detector
353-7021214 Year Warrenty
Presence detector P42LR, 230 V, master, 32-37 m, 360°, for surface mounting
Wiring
230 V – OFF
- Remove if you want to use the contact as a dry contact (potential-free).
**** This product must be secured with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating is limited by national installation rules.
Dimensions
Installation
230 V – OFF
If a grommet needs to be replaced, please make sure the new grommet is halogen-free.
Dismantling
230 V – OFF
App settings
230 V – ON
| | |
---|---|---|---
Factory settings| Switch ON/OFF| 500 lux| 15 min
LED behaviour
****230 V – ON
Green LED continuous on| | Connection OK|
---|---|---|---
Green LED breathing| | Connection OK, overrule ON|
Green LED flashing| | Warming up| Wait
Red LED continuous on| | Error| More info –> detector tool
Red LED breathing| | Warning
Blue LED flashing| | Walk test active
Specifications
Article number | 353-702121 |
---|---|
Configuration | 230 V Master |
Input voltage | 230 Vac ± 10 %, 50 Hz |
Maximum power consumption | 0.2 W |
Circuit breaker | maximum MCB rating 16 A* |
Relay contact | NO (max. µ10 A), potential-free |
Maximum load incandescent and halogen lamps (cosφ = 1) | 2300 W |
Maximum load fluorescent lamps (cosφ ≥ 0.5) | 1200 VA |
Maximum load economy lamps (CFLi) | 350 W |
Maximum load LED lamps 230 V | 350 W |
Maximum load LED driver | 500 VA |
Maximum load electronic transformer | 500 VA |
Maximum capacitive load | 140 µF |
Maximum switching current | 165 A/20 ms – 800 A/200 µs |
Light intensity range | 20 – 2000 lux, ∞ |
Number of channels | 1 channel |
Maximum number of secondary detectors | 10 |
Switch-off delay | pulse, 15 s – 120 min, ∞ |
Hysteresis on light intensity | 10% |
Detection angle | 360 ° |
Detection range (PIR) | Ø 37 m from a height of 3 m |
Ambient temperature | -25 – +40 °C |
Mounting method | surface mounting |
Mounting height | 2 – 3.5 m |
Colour | white (RAL 9010) |
Dimensions visible (HxWxD) | 100 x 100 x 70.7 mm |
Dimensions (HxWxD) | 100 x 100 x 70.7 mm |
Wire capacity | 1.5/2.5 mm² |
Maximum range Bluetooth® (free field, depending on the device) | 50 m |
Operating frequency | 2.4 GHz |
Maximum radio frequency power | -2 dBm |
Protection degree | IP54 |
Impact resistance | IK04 |
Modification of settings | app (iOS/Android) and 2-way Bluetooth® communication |
Halogen-free | yes |
Marking | CE |
- The MCB rating is limited by national installation rules.
Detection area
H | A Walking | B Across | C Towards | D Presence |
---|---|---|---|---|
2.5 m | ø 32 m | ø 28 m | ø 10 m | ø 8 m |
3.0 m | ø 37 m | ø 30 m | ø 8 m | ø 4 m |
Measured according to EN/IEC63180
Troubleshooting
Problem | Possible cause | Proposed solution |
---|---|---|
Load does not turn on | The wiring is not correct | Check the wiring scheme |
The ambient light is too strong | Check the response value luminosity and raise |
the value if necessary
Load does not turn off| The switch-off delay is too long| Check the switch-off
delay and shorten the delay if necessary
The detector receives false triggers| Check for any objects that may cause
false triggering and remove them from the detection range or lower the
sensitivity
App cannot connect to the detector| Bluetooth® has been disabled on your
mobile device| Enable Bluetooth® on your mobile device
Support & contact
nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
+32 3 778 90 80
support@niko.eu
Niko prepares its manuals with the greatest care and strives to make them as
complete, correct and up to date as possible. Nevertheless, some deficiencies