Schneider Electric MTN6725-0101 SpaceLogic KNX DALI Gateway Instructions

June 9, 2024
Schneider Electric

Schneider Electric MTN6725-0101 SpaceLogic KNX DALI Gateway

Schneider-Electric-MTN6725-0101-SpaceLogic-KNX-DALI-Gateway-
product

About this document

  • You can find all the information required for safe installation in this document.
  • More detailed product information is available on the Internet – > See QR code.
  • http://go2se.com/ret-MTN6725-0101

For your safety

  • DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
  • Safe electrical installation must be carried out only by skilled professionals. Skilled professionals must prove profound knowledge in the following areas:
  • Connecting to installation networks
  • Connecting several electrical devices
  • Laying electric cables
  • Connecting and establishing KNX networks
  • Safety standards, local wiring rules and regulations
  • Failure to follow these instructions will result in death or serious injury.

Getting to know the device

  • The SpaceLogic KNX DALI Gateway Pro (hereinafter referred to as Gateway) is a multi-master application controller for controlling ECGs (electronic control gears) with
    DALI interface via KNX.

  • The Gateway supports DALI-1 and DALI-2 ECGs as well as DALI-2 motion detectors and light sensors. The Gateway has a DALI output that can be used to control 64

  • ECGs. In addition, up to 8 DALI-2 motion detectors or light sensors can be connected.

  • The required power for the connected ECGs and motion detectors is supplied directly from the device. Additional

  • DALI power supplies are not required.

  • The ECGs can be controlled in 16 groups per Gateway.

  • Beyond this, individual control of up to 64 ECGs is possible.

  • Besides controlling all standard control gear, the Gateway also allows the operation of single-battery emergency lighting (EN 62386-202). Emergency lighting systems
    with a central battery are also supported.

  • When using sensors supplied via the DALI bus, the power consumption of all DALI devices must not exceed the guaranteed value.

Connections and operating elements

  • A KNX bus connection terminal
  • B Error-LED
  • C Ethernet-LNK-LED
  • D Mains connection
  • E RJ-45 socket
  • F Display
  • G Operating/programming buttons
  • H DALI output terminals
  • I Programming button
  • J Programming LED

Installation and connection

Schneider-Electric-MTN6725-0101-SpaceLogic-
KNX-DALI-Gateway-fig-4

installing
  • WARNING Risk of death from electric shock.
  • Only install devices with at least basic insulation next to the device.
  • Failure to observe this instruction can result in death or serious injury.
  • WARNING Risk of death from electric shock. The device can be damaged.
  • Safety clearance must be guaranteed in accordance with IEC 60664-1.
  • There must be at least 4 mm between the individual cores of the 230 V supply cable and the KNX line A
Connecting
  • Operating voltage: AC/CDC 100-240 V, 50- 60 Hz
  • Power consumption: max. 8 W
  • Power supply from KNX: DC 24 V (SELV), approx. 5 mA KNX
  • KNX Medium: Twisted Pair
  • Security: KNX Data Secure Ready DALI
  • Outputs: 1 Output D+/DType: Multi-master application
  • controller
  • Number of ECGs: max. 64 (DALI-1, DALI-2)
  • Number of sensors: max. 8 (DALI-2)
  • DALI voltage: typical DC 18 V, short-circuit proof, max 250 mA, basic insulation (no SELV)
  • Power supply current: max. 250 mA, guaranteed: 160 mA
  • Shutdown delay: 600 ms after DALI short-circuit
  • Start-up attempt after
  • shutdown: 5 s after short-circuit detection
  • Ethernet
  • Type: 100BaseT (100 Mbit/s)
  • Supports: IEEE 802.3
  • IP protection rating: IP20
  • Protection class: I
  • Overvoltage category: III
  • Degree of contamination: 2

Environment

  • The temperature in operation: -5 °C … +45 °C
  • Relative humidity (noncondensing): 5% to 95%
  • Device width: 4 TE = approx. 72 mm
  • Dispose of the device separately from household waste at an official collection point. Professional recycling protects people and the
    environment against potential negative effects

Schneider Electric -Contact

  • Schneider Electric Industries SAS
  • 35 rue Joseph Monier
  • Rueil Malmaison 92500
  • France
  • If you have technical questions, please contact the Customer Care Centre in your country. se.com/contact
  • UK Representative
  • Schneider Electric Limited
  • Stafford Park 5
  • Telford. TF3 3 BL. Uk

RU Complies with technical regulations ≪O safety of low voltage equipment≫, ≪On electromagnetic compatibility≫ Date of manufacture: see general packaging: year /a week /weekday A country – manufacturer: Germany Shelf life: 3 years Warranty period: 18 months If a malfunction is detected during the warranty period and after its completion address to the regional Help Center Schneider Electric customers. Authorized Supplier in RF: JSC “Schneider Electric” Address: 127018, Russia, Moscow city, st. Dvintsev, 12, building 1 Tel. +7 (495) 777 99 90 Fax +7 (495) 777 99 92 se.com/ru/ru/

Documents / Resources

| Schneider Electric MTN6725-0101 SpaceLogic KNX DALI Gateway [pdf] Instructions
MTN6725-0101, SpaceLogic KNX DALI Gateway, KNX DALI Gateway, SpaceLogic DALI Gateway, DALI Gateway, Gateway
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals