ActronAir EVA720T Variable Capacity Commercial Installation Guide

June 12, 2024
ActronAir

VARIABLE CAPACITY COMMERCIAL

72 – 96kW Indoor (R-410A Series)

Installation and Commissioning Guide

ActronAir EVA720T Variable Capacity Commercial

Model Numbers
EVA720T
EVA850T
EVA960T

IMPORTANT NOTE:
Please read this manual carefully before installing or operating your air conditioning unit.

ActronAir EVA720T Variable Capacity Commercial - 1

Installation and Commissioning Guide

Introduction

CONGRATULATIONS on your purchase of an ActronAir air conditioning system! This unit has been designed and engineered to provide optimum air conditioning and to achieve maximum energy efficiency.

Your air conditioning system has been manufactured from the highest quality materials. Numerous “in house” and “external” inspection and test procedures were conducted to your air conditioner to ensure satisfactory operation.

Information About This Guide
This guide provides installation instructions, specific to your ducted unit. Read this manual thoroughly and take into consideration all specifications and instructions to ensure correct installation and safe operation of your air conditioning system.

NOTE

Print a copy of this document and keep it for future reference. Ensure all technicians that work on the unit can refer to this manual at any time.

Product Inspections
Check your air conditioning unit and all items against the invoice upon receiving your shipment. Inspect the unit, components and accessories for any sign of damage. If there is any damage to the unit, contact ActronAir Customer Care Department immediately on: 1300 522 722 to obtain a Goods Return Number.

Check the unit nameplate to verify the model, serial number, electrical rated specifications are correct.

Codes, Regulations And Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant council, state / federal codes, regulations and building code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit

Safety Instructions
  • Only licensed HVAC technicians* should install and service air conditioning equipment. Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void. Such unqualified service could also lead to severe physical injury or death. Follow all safety instructions in this literature and all warning labels that are attached to the equipment.
  • Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on this manual. Safe work practices and environment must be the paramount importance in the performance of all the service procedures.
  • Ensure that unit installation complies with relevant council regulations and building code standards.
  • All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided.
  • Secure the fans against accidental contact. Beware of pinch point and sharp edges which can cause cutting injury.
  • Always wear appropriate PPE, remove any dangling jewelery and protect long hair by wearing a cap.
  • Make sure that safety guards and panel covers are always firmly secured and not damaged before and during operation of unit.
  • This appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance.
  • Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance with the latest edition of the AS/NZS 3000 (also known as Australian Wiring Rules).
  • Secure the power cords and control cables that goes in/out the unit. Use the cable ties provided in the control box.
  • This unit is designed for use with R-410A refrigerant only.

*Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training dependent on local State/Territory regulations.

DANGER

Hazardous Voltage – Risk of Electrocution.
TURN-OFF the power from main isolator before proceeding with any service work of the unit. Observe proper LOCK-OUT/TAG-OUT (LOTO) procedures for electrical appliances in order to prevent accidental switching-on of the power supply.
WARNING

EC Motors and Compressor Drives are fitted with high power capacitors and can have dangerous residual voltages at motor/drive terminals after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning service work.
CAUTION

Beware of Rotating Fans !

Ensure that indoor and outdoor fans are isolated and have come to a complete stand still before servicing the equipment.
Beware of pinch point and sharp edges which can cause cutting injury. Secure the fans against accidental contact.
Always wear appropriate PPE and remove any dangling jewellery and protect long hair by wearing a cap. Ensure that no loose clothing can be caught / entangled in moving parts.

VISUAL INSPECTION AND WORK ASSESSMENT

Work areas and conditions must first be assessed and evaluated for any potential hazardous conditions. It is also important to be familiar with the unit parts and components before proceeding with any service task.

Components Overview
Indoor Unit Components Overview

NOTES:

Drawing is subject to change without notice.
Drawing for illustration purposes only (may vary depending on capacity)
EVA720T has a single fan configuration

ActronAir EVA720T Variable Capacity Commercial - a1

  1. TOP PANEL

  2. HEAT EXCHANGER

  3. INTERNAL ACCESS PANEL

  4. ELECTRICAL PANEL

  5. ELECTRICAL BOX COVER

  6. GAS PIPE
    (Crt 1)

  7. LIQUID PIPE
    (Crt 1)

  8. LIQUID PIPE
    (Crt 2)

  9. GAS PIPE
    (Crt 2)

  10. CONDENSATE DRAIN

  11. ACCESS PANEL

  12. FAN 1

  13. FAN 2

Indoor Unit Electrical Panel Overview
  1. CONTROL BOARD
  2. INDOOR CONTROL BOARD POWER SUPPLY
  3. TRANSFORMER
  4. PRESSURE DIFFERENTIAL SENSOR
Unit Dimensions and Clearance
EVA720T
  1. STG1 LIQ
    Ø15.9(5/8″)
    SWAGED

  2. STG1 GAS
    Ø28.6(1-1/8″)
    SWAGED

  3. DETAIL P

ActronAir EVA720T Variable Capacity Commercial - b2

  1. CONDENSATION DRAIN
    Ø25.4(1″) BSP
    FEMALE THREAD

  2. (MTG C-C DIST 1125)

ActronAir EVA720T Variable Capacity Commercial - b4

  1. 6 x Ø15 MTG HOLES
  2. (MTG C-C DIST 950)

NOTES:

Drawing is subject to change without notice.
Use M12 Bolt for feet mounting
Not to scale drawing. All dimensions are in mm unless otherwise specified.
Refer to corresponding unit dimensional drawing for mounting hole details.

  1. THIRD ANGLE
  2. PROJECTION

Unit Model Number

| Overall Nominal Dimension (OA)| MTG C-C DIST
Mounting Distance Base Foot
(Centre to Centre)| Supply Duct| Return Duct| Gas Pipe| Liquid Pipe
---|---|---|---|---|---|---
H| W| D| F| E| H-SD x W-SD|

H-RD x W-RD

EVA720T

| 1085| 2440| 1190| 950| 1125| 659 x 999| 932 x 1982| Ø 28.60 mm (1-1/8″) Swaged|

Ø 15.88 mm (5/8″) Swaged

EVA850T/ EVA960T
  1. STG1 LIQ
    Ø15.9 (5/8″)

  2. STG1 GAS
    Ø28.6 (1-1/8″)
    SWAGED

  3. STG2 GAS
    Ø28.6 (1-1/8″)
    SWAGED

  4. STG2 LIQ
    Ø15.9 (5/8″)

  5. CONDENSATION DRAIN
    Ø25.4(1″) BSP
    FEMALE THREAD

  6. DETAIL P

ActronAir EVA720T Variable Capacity Commercial - c2

ActronAir EVA720T Variable Capacity Commercial - c3

  1. 6 x Ø 15.0
    MTG. HOLES

  2. 1125 (MTG C-C DIST)

  3. CONDENSATION DRAIN
    Ø25.4(1″) BSP
    FEMALE THREAD

ActronAir EVA720T Variable Capacity Commercial - c4

  1. 950 (MTG C-C DIST)

NOTES:

Drawing is subject to change without notice.
Use M12 Bolt for feet mounting
Not to scale drawing. All dimensions are in mm unless otherwise specified.
Refer to corresponding unit dimensional drawing for mounting hole details.

  1. THIRD ANGLE
  2. PROJECTION

Unit Model Number

| Overall Nominal Dimension (OA)| MTG C-C DIST
Mounting Distance Base Foot
(Centre to Centre)| Supply Duct| Return Duct| Gas Pipe| Liquid Pipe
---|---|---|---|---|---|---
H| W| D| F| E| H-SD x W-SD|

H-RD x W-RD

EVA850T

| 1520| 2425| 1190| 950| 1125| 800 x 1150| 1366 x 1982| Ø 28.60 mm
(1-1/8″)
Swaged| Ø 15.88 mm
(5/8″)
Not Swaged

EVA960T

Indoor Unit Service Access Clearances

NOTE

Drawing shown below is for illustration purposes only. Actual unit may vary depending on model.

ActronAir EVA720T Variable Capacity Commercial - d1

  1. TOP VIEW

  2. DUCT WORK

  3. LEFT SERVICE* CLEARANCE
    (ELECTRICAL SIDE)
    1000mm

  4. RIGHT SERVICE CLEARANCE
    1000mm

Notes:
Height Clearance is 500 mm
*Electrical box and/or pipe connections are located on the left side of the indoor unit.

Model Number

| Unit Weight (kg)| Corner Mounting Point Weights (kg)| Centre Of Gravity Position
---|---|---|---
A| B| C| D| XX|

YY

EVA720T

| 296| 76| 34| 74| 112| 1123| 715
EVA850T| 368| 40| 101| 147| 80| 1127|

638

EVA960T

| 387| 108| 59| 90| 130| 1141|

611

NOTES:

  1. Not to scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details.
  2. Service Access Areas and Spaces for Airflow Clearances are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passage of 1000 mm between the units or between the unit and the outside perimeter is available.
  3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
    • Left Service Clearance can be 600mm minimum if Right Service Clearance is applicable.
    • Right Service Clearance can be 100mm minimum if Left Service Clearance is applicable.
    • Height Service Clearance can be 100mm minimum if Left Service Clearance is applicable.
Installation Instructions

The installation instructions provided below are intended as a guide only and does not supersede the relevant council, state and federal codes, regulations and building code standards. Compliance and consultation with the authorities having jurisdiction with the installation of this equipment is the responsibility of the installer. ActronAir will not be held liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit Installation and Commissioning Guide for further information and details.

Lifting The Unit
The installation instructions provided, in Unit Lifting Procedures, adhere to WH&S regulations for safe and secure lifting practices in order to prevent physical injury. The suggested lifting procedures are outlined as reference guide to safely lift and transport the unit, however, this does not over rule the industry WH&S practices.

Location
This unit is intended for indoor installation only. It is highly recommended that this indoor unit and accessories, particularly zone barrels, be mounted in the roof cavity.

Mount the unit in a stable and rigid support wherein the weight is properly distributed, such as roof joist and rafters. Take into consideration the minimum service access clearances provided in the unit drawings.

Locate the indoor unit away from the areas where noise is a critical factor. Use rubber mounting pad (not supplied) in order to minimize the transfer of noise and vibration into building structures.

An optional hanging bracket assembly and rubber grommet (supplied as standard with some models) is also available to secure the indoor unit into the roof rafters. This installation configuration is most suitable for installation that require the unit to be rigidly secured up from the roof joist.

Condensate and Safety Tray Drainage
An integrated safety drain tray is provided as a standard inclusion to your indoor unit in order to reduce the potential of condensate damage to the roof. Drain Kit (not included in some models) is provided for the condensate drain to be externally trapped from the indoor unit. Suggested condensate and safety tray drainage instructions are provided at the proceeding page for your reference.

Supply Air and Return Air Duct
The indoor unit is supplied with duct flange as standard in order to facilitate the system’s duct connection into the unit. Supply and return air duct works must be adequately sized to meet the system’s air flow and static pressure requirements. Refer to the unit drawing for supply air and return air duct dimensions, specific to your requirement.

NOTE

Fit a flexible duct connection in between the unit and the duct system, where noise and vibration is a critical consideration.

Return Air Filter
Air filters must be provided in the return air side of the unit to maintain the efficiency and prolong the operation of the unit. These are also paramount to satisfy requirement for a clean and hygienic room condition. Return Air filters must be placed in an easily accessible location for service and maintenance.

NOTES

  • Return Air filters are not supplied with the unit as individual air filtration requirements vary.
  • Ensure that filters are cleaned / replaced regularly.

Fan Coil With Vertical Discharge (Optional)
An upright Fan Coil with vertical supply air discharge is also available wherein installation applications require the placement of the unit down in a closet, basement or garage. Please refer to the Technical Catalogue of your indoor unit for dimensions, installation details and specifications.

Field Pipe Connections
Specifications and installation requirements for field pipe connections are contained in the Installation and Commissioning Guide of the outdoor unit that matches your indoor unit. Please refer to this guide and thoroughly understand the procedures for safe and correct indoor and outdoor connection.

Field Electrical Connection
The power supply and control communication data to the indoor unit are supplied via the outdoor unit. Please refer to the wiring diagram supplied with the outdoor unit for specifications.

All electrical work must be performed by a licensed electrician and must conform with the wiring diagram and all relevant electrical authorities.

NOTE

This indoor unit is designed to match only with an ActronAir Series outdoor unit as specified in the Technical Selection Catalogue.

The unit is supplied with factory charged dry air. Be aware of the pressurised air charge when purging. Remove the caps from the connection points and purge the system only when the field pipe connections are ready to be completed.

Unit Lifting Instructions

NOTE

All drawings are for illustration purposes only. Actual unit may vary depending on the model.

A. CRANE LIFTING METHOD

NOTE: Crane lifting is recommended over fork lift method.

EQUIPMENT REQUIRED FOR CRANE LIFTING:
– Spreader bar
– 4 x shackles
– 2 x nylon slings

NOTES:
– Refer to catalogue for unit weight before selecting shackles.

PROCEDURE:

  1. Use 4 x Bow or Dee shackles to connect the lifting holes.
  2. Slip nylon slings through all shackles.
  3. Ensure slings are protected by rubber pads or similar if slings 2 are draped across unit ed3ges, corners, supply or re4turn air spigots. This will prevent the unit from being damaged during lifting.
  4. SPREADER BAR must be used when lifting the unit.
  5. Remove all screws and washers that secure the unit to the timber pallet.
  6. Remove pallet from the unit. (See pallet removal instructions below).
PALLET REMOVAL INSTRUCTIONS

PROCEDURE:

  1. Remove the 14G x 50mm screws (x6) from the pallet
  2. Remove Pallet from the unit

WH &S regulations must be observed and will take precedent during lifting process.

ActronAir EVA720T Variable Capacity Commercial - e2

  1. Connect the loop ends of slings into shackle

  2. RUBBER PADS:
    Provide rubber pads to prevent damage to the unit if the sling is touching the unit.

  3. Slip nylon slings between the unit and the pallet

  4. Indoor Unit

  5. Pallet

  6. INSERT FORK LIFT TINES HERE

B. FORK LIFT METHOD

NOTES:
Ensure to remove screws and washers only when it is required to disassemble unit from the pallet.
Do not lift unit using any pipe coming out from the unit
All dimensions are in mm.

ActronAir EVA720T Variable Capacity Commercial - e4

ON THE FRONT AND THE BACK

Condensate and Safety Tray Drainage Instructions

Suggested Minimum Slope to Ensure Correct Drainage

TOP VIEW

ActronAir EVA720T Variable Capacity Commercial - f1

  1. RETURN AIR
  2. Condensate Drain Connection
  3. INDOOR COIL
  4. INTERNAL CONDENSATE DRAIN TRAY
  5. SUPPLY AIR

SIDE VIEW

  1. Provide a minimum slope of 10mm per meter
  2. Seal with Silicone sealant

FRONT VIEW

ActronAir EVA720T Variable Capacity Commercial - f3

  1. Provide a minimum slope of 10mm per meter
  2. Ensure Drain Pipes slope down from the unit at a minimum of 10mm per meter

NOTES

  • Parts for the Condensate Trap are not supplied with the unit.
  • Refer to Unit Dimensions page of the Technical Selection Catalogue For specifications of drain connectors.

Suggested Drain Trap Details

ActronAir EVA720T Variable Capacity Commercial - f4

DETAIL A

  1. Evaporator Condensate Tray
  2. The top of the Trap must be 125mm below the top of the Evaporator Drain Connection
  3. The top of the Vent must be 50mm higher than the top of the Evaporator Condensate Tray
  4. 250mm or high enough to maintain positive Air Seal
  5. Ensure Drain Pipe slopes down from the unit at a minimum of 10mm per meter
  6. Install a T-Piece as an Air Vent for long drain runs
  7. Trap
  8. 4 x PVC Elbow
  9. Clear Plastic Inspection Tube
  10. Condensate Drain Connection
  11. Clamp Bands
Electrical Installation

All electrical work must be carried out by a qualified technician. Make sure all wiring is in accordance with local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided.

DANGER

Live Electrical Supply !

  • During installation of your air conditioning unit, it may be necessary to work in close proximity to live electricity. Only qualified technicians are allowed to perform these tasks.

  • Follow all electrical safety precautions when exposed to live electrical components.

  • Always make sure that all power supply, including remote controls, are disconnected before performing maintenance.
    Observe proper LOCK-OUT / TAG-OUT (LOTO) procedures to ensure that power cannot be inadvertently energised.
    Failure to disconnect power before maintenance procedure can result in serious injury or death.

  • All electrical wiring must be in accordance with the relevant electrical authority rules and regulations.

CAUTION

STATIC SENSITIVE ELECTRONIC DEVICES !

  • DO NOT handle electronic devices unless you are wearing an Anti-Static Wrist Strap that is connected to a EARTH. Failure to protect the electronic devices from static electricity may cause unrepairable damage.
  • Static damaged electronic devices are NOT COVERED for replacement under warranty.

Wiring Diagram
The wiring diagrams specific for your air conditioning system are located on the inside of the electrical access panel.

Always refer all wiring installation, servicing and troubleshooting of this equipment to this diagram to ensure correct electrical connections are satisfied.

Supply and Power Requirements Procedure
It is the installer’s responsibility to provide power supply wiring to the sub-mains isolator. Wiring should conform to the current electrical authority regulations and all wiring connections to be as per electrical diagram provided with the unit.

  • Confirm that the power supply available is compatible with the unit nameplate ratings. The supply power must be within +10% to -6% of the rated voltage as per AS60038.
  • Protect electrical service from over current and short circuit conditions in accordance with the latest edition of the AS/ NZS 3000 “Australian / New Zealand Wiring Rules”. Protection devices are to be sized accordingly as per to the electrical specifications of the unit.
  • Complete the outdoor unit power supply wiring into the sub-mains isolator.
  • Secure the power cords and control cables that enters in/exits out the unit. Use the cable ties provided in the electrical panels.
  • Provide proper unit earthing in accordance with local and national wiring rules.
Wiring Diagram

ActronAir logo2

This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.

| Base Model No.: EVA720T| Variation Code:| Variation:

STANDARD

---|---|---|---
Description:
WIRING DIAGRAM VCC 72kW EVAP
Drawn:| JL| 22/08/2022| Drawing No:

0515-9060

| Sheet:

1/1

| Revision:

A

Approved:| RL| 23/03/2023

LEGEND


IF| INDOOR FAN
ICB| INDOOR CONTROL BOARD
PDS| PRESSURE DIFFERENTIAL SENSOR
SMPS| ICB POWER SUPPLY
TX| TRANSFORMER 240/24VAC
TWC| TOUCH WALL CONTROLLER
WC| WALL CONTROLLER

OPTIONAL REMOTE SENSORS
NOTE: MAX 2 SENSORS
ALLOWED ONLY(REFER TO INSTALLATION & COMMISSIONING GUIDE FOR CONNECTION DETAILS)

ActronAir EVA720T Variable Capacity Commercial -g1

OPTIONAL WC-1, WC-2 & TWC-1 WALL CONTROLLERS
NOTE: MAX 3 WC ALLOWED ONLY
(REFER TO INSTALLATION & COMMISSIONING GUIDE FOR OTHER WIRING CONFIGURATIONS)

WALL CONTROLLER WIRING

POWER:         – BROWN / ORANGE
485 A:              – BLUE
485 B:              – BLUE-WHITE
GND:              – BROWN-WHITE / ORANGE-WHITE
NOT USED:  – GREEN / GREEN-WHITE

  1. OPTIONAL SENSOR 2

  2. OPTIONAL SENSOR 1

  3. FIELD WIRING BY INSTALLER

  4. OPTIONAL FILTER INDICATION RELAY OUTPUT
    (240VAC 10A MAX)

  5. NC OUTPUT

  6. VOLTAGE IN

  7. NO OUTPUT

  8. PDS-1
    DIP SWITCH SETTING

  9. SUPPLY AIR SIDE

  10. FIELD WIRING BY INSTALLER – CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE WITH SCREEN WIRE CONNECTED TO TERMINAL “G” ON OUTDOOR & INDOOR UNIT

  11. POWER & DATA

  12. 2 x FERRITES IF SUPPLIED

  13. FIELD WIRING BY INSTALLER

  14. OPTIONAL 3RD PARTY INDOOR FAN CONTROL INPUT *

  15. OPTIONAL OUTSIDE AIR DAMPER CONTROL OUTPUT

  16. OPTIONAL FAN RUN INDICATION OUTPUT

  17. INDOOR COIL 1

  18. INDOOR COIL 2

  19. FILTER INDICATION

  20. DISPLAY

  21. POT ADJUST

  22. FAN1 OUT

  23. FAN2 OUT

  24. 0-10V FAN1 OUT

  25. 0-10V FAN2 OUT

  26. 485 FAN

  27. AUX SENSOR

  28. 0-10V FAN INPUTS

  29. PWM FAN OUTPUT

  30. MANUAL FAN SPEED POT ADJUST

  31. STANDARD DIP SWITCH SETTING

  32. INTERNAL FAN SPEED

  33. WALL CONTROLLER

  34. OUTDOOR 485

  35. ZONE

  36. +12VDC POWER IN

  37. TO OUTDOOR UNIT

  • REFER TO INSTALLATION & COMMISSIONING GUIDE FOR MORE DETAILS

FINAL COMMISSIONING
FAN SETPOINT VOLTAGE

FAN SPEED:
………………………V or %| DATE:
………/………/……..

A

| DRAWING RELEASE| |

JL

|

8/04/2022

---|---|---|---|---

Rev.

| Description| PCR| By|

Date

Wiring Diagram

ActronAir EVA720T Variable Capacity Commercial -g2

WALL CONTROLLER WIRING

POWER:         – BROWN / ORANGE
485 A:              – BLUE
485 B:              – BLUE-WHITE
GND:              – BROWN-WHITE / ORANGE-WHITE
NOT USED:  – GREEN / GREEN-WHITE

OPTIONAL WC-1, WC-2 & TWC-1 WALL CONTROLLERS
NOTE: MAX 3 WC ALLOWED ONLY
(REFER TO INSTALLATION & COMMISSIONING GUIDE FOR OTHER WIRING CONFIGURATIONS)

  1. OPTIONAL REMOTE SENSORS
    NOTE: MAX 2 SENSORS ALLOWED ONLY(REFER TO INSTALLATION & COMMISSIONING GUIDE FOR CONNECTION DETAILS)

  2. OPTIONAL SENSOR 1

  3. OPTIONAL SENSOR 2

  4. FIELD WIRING BY INSTALLER

  5. INDOOR COIL 2

  6. INDOOR COIL 1

  7. OPTIONAL FILTER INDICATION RELAY OUTPUT
    (240VAC 10A MAX)

  8. NC OUTPUT

  9. VOLTAGE IN

  10. NO OUTPUT

  11. SUPPLY AIR SIDE

  12. PDS-1
    DIP SWITCH SETTING

  13. TO OUTDOOR UNIT

  14. FIELD WIRING BY INSTALLER – CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE WITH SCREEN WIRE CONNECTED TO TERMINAL “G” ON OUTDOOR & INDOOR UNIT

  15. POWER & DATA

  16. 2 x FERRITES IF SUPPLIED

  17. FIELD WIRING BY INSTALLER

  18. OPTIONAL 3RD PARTY INDOOR FAN CONTROL INPUT *

  19. OPTIONAL OUTSIDE AIR DAMPER CONTROL OUTPUT

  20. OPTIONAL FAN RUN INDICATION OUTPUT

  21. FILTER INDICATION

  22. AUX SENSOR

  23. DISPLAY

  24. POT ADJUST

  25. FAN1 OUT

  26. FAN2 OUT

  27. 0-10V FAN1 OUT

  28. 0-10V FAN2 OUT

  29. 485 FAN

  30. 0-10V FAN INPUTS

  31. PWM FAN OUTPUT

  32. MANUAL FAN SPEED POT ADJUST

  33. STANDARD DIP SWITCH SETTING

  34. INTERNAL FAN SPEED

  35. WALL CONTROLLER

  36. OUTDOOR 485

  37. ZONE

  38. +12VDC POWER IN

  • REFER TO INSTALLATION & COMMISSIONING GUIDE FOR MORE DETAILS

FINAL COMMISSIONING
FAN SETPOINT VOLTAGE

FAN SPEED:
………………………V or %| DATE:
………/………/……..

LEGEND


IF| INDOOR FAN
ICB| INDOOR CONTROL BOARD
PDS| PRESSURE DIFFERENTIAL SENSOR
SMPS| ICB POWER SUPPLY
TX| TRANSFORMER 240/24VAC
TWC| TOUCH WALL CONTROLLER
WC| WALL CONTROLLER

B

| ADD CABLE 4080-034 BETWEEN I/D FANS
FOR AUTO ADDRESSING FEATURE| 3730|

JL

|

5/05/2023

---|---|---|---|---

Rev.

| Description| PCR| By|

Date

ActronAir logo2

This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.

| Base Model No.:
EVA850-960T| Variation Code:| Variation:

STANDARD

---|---|---|---
Description:
WIRING DIAGRAM VCC 85-96kW EVAP
Drawn:| JL| 22/08/2022| Drawing No:

0515-9070

| Sheet:

1/1

| Revision:

B

Approved:| RL| 5/05/2023

Electrical Connection

NOTES

  • To minimise noise interference, Data and Power cable clearance should be maintained as much as possible.
  • All drawings are for illustration purposes only. Actual unit may vary depending on the model.
  • All electrical components do not come with the unit, must be purchased separately.

DETAILED WIRING DIAGRAM IS PROVIDED WITH THE UNIT.

Outdoor Unit: Located at the back of electrical/compressor access panel.
Indoor Unit: Located at the back of electrical box cover.

ActronAir EVA720T Variable Capacity Commercial - g4 (1) MAINS WIRING (400VAC)
(Three Phase + Neutral + Earth) 50Hz
ActronAir EVA720T Variable Capacity Commercial - g5 (2) INTER-CONNECTING POWER CABLE (230/400VAC)
2a (Single Phase + Neutral + Earth ) 50Hz
2b (Three Phase + Neutral + Earth) 50Hz
ActronAir EVA720T Variable Capacity Commercial - g6 (3) DATA CABLE TO WALL CONTROLLER
(Cat5E UTP (AWG 24) Data Cable)
ActronAir EVA720T Variable Capacity Commercial - g7 (4) EXTRA LOW VOLTAGE DATA CONTROL WIRING
(2 Core Shielded Twisted Pair 7/0.30 (0.5mm²) Data Cable)

ActronAir EVA720T Variable Capacity Commercial - g3

  1. OUTDOOR UNIT

  2. SUB-MAIN TO UNIT

  3. SUB-MAINS ISOLATOR
    (Field Supplied by Installer)

  4. (1) MAIN SUPPLY FROM DISTRIBUTION BOARD

  5. SUB-MAINS CIRCUIT BREAKER

  6. INDOOR UNIT

  7. (3) DATA CABLE
    (Supplied with the unit)
    20m

  8. WALL CONTROLLER
    (Optional)

  9. (4) INTER-CONNECTING PCB DATA CABLE INDOOR TO OUTDOOR

  10. (2b) INTER-CONNECTING
    POWER CABLE
    OUTDOOR – INDOOR

  11. (2a) INTER-CONNECTING
    POWER CABLE
    OUTDOOR – INDOOR

Data Cable Shielding Instructions

2 Core Twisted (ActronAir Part Number: AEDC2)

NOTES

  • Maintain the twist of the core wires up to the Green Terminal Plug.
  • Maximum strip length of outer insulation to the Green Terminal Plug is 50mm.
  • Make sure the cable colors used for the Data Terminal in Outdoor Unit match the Data Terminal in Indoor unit.

Outdoor Unit Data Terminal (Green Plug)
“Terminal A” – White Wire
“Terminal B” – Black Wire
“Terminal G” – Shield Wire

Indoor Unit Data Terminal (Green Plug)
“Terminal A (+)” – White Wire
“Terminal B (-)” – Black Wire
“Terminal G” – Shield Wire

Insert data cable through the lower snap bushing and first cable tie on the right hand side of the electrical panel.

Connect core wires and shield wire into the Outdoor Board green terminal plug marked “INDOOR A, B and G”. (Refer to unit wiring diagram for complete wiring connection details).

NOTE

All drawings are for illustration purposes only. Actual unit may vary depending on the model.

ActronAir EVA720T Variable Capacity Commercial - g8 Fig. 3

  1. OUTDOOR BOARD TERMINAL PLUG
  2. OUTDOOR BOARD
Circuit Breaker Size Recommendation

Model

| Circuit Breaker Size
---|---

Amps

CRV720T / EVA720T

| 63
CRV850T / EVA850T|

80

CRV960T / EVA960T

| 80
PKV720T|

63

PKV850T

| 80
PKV960T|

80

Notes:
Refer to latest edition of AS/ANZ 3000 or AS/ANZ 3008 Australian/New Zealand Wiring Rules to determine required cable size.

Wiring Connections

NOTE

LR7-1 may be used depending on the unit purchased

LR7-1 and LC7-2 Wall Control Wiring Connections

WALL CONTROL WIRING

POWER:          – BROWN / ORANGE
485 A:              – BLUE
485 B:              – BLUE-WHITE
GND:             – BROWN-WHITE / ORANGE-WHITE
NOT USED:  – GREEN / GREEN-WHITE

ActronAir EVA720T Variable Capacity Commercial - g9

  1. INDOOR CONTROL BOARD

  2. WALL CONTROLLER

  3. CUT OFF
    GR / GR-WH

  4. WALL CONTROL

LM-RS-2 Optional Sensor Wiring Connections

REMOTE SENSOR WIRING

PAIR 1:  – BLUE / BLUE-WHITE
PAIR 2:  – ORANGE / ORANGE-WHITE
PAIR 3:  – GREEN / GREEN-WHITE
PAIR 4:  – BROWN / BROWN-WHITE

NOTE:

  • PAIR 1 AND 2 USED FOR ILLUSTRATION PURPOSES ONLY.
  • CUT OFF AND TERMINATE ANY UNUSED PAIRS TO ENSURE NO WIRING IS LEFT EXPOSED.

ActronAir EVA720T Variable Capacity Commercial - g12

  1. INDOOR CONTROL BOARD
  2. TEMP SENSORS
  3. OPTIONAL SENSOR 3
  4. OPTIONAL SENSOR 2
  5. OPTIONAL SENSOR 1
AERSS Optional Duct Sensor Wiring Connections

REMOTE SENSOR WIRING

PAIR 1:  – BLUE / BLUE-WHITE
PAIR 2:  – ORANGE / ORANGE-WHITE
PAIR 3:  – GREEN / GREEN-WHITE
PAIR 4:  – BROWN / BROWN-WHITE

NOTE:

  • PAIR 1 AND 2 USED FOR ILLUSTRATION PURPOSES ONLY.
  • CUT OFF AND TERMINATE ANY UNUSED PAIRS TO ENSURE NO WIRING IS LEFT EXPOSED.
  1. INDOOR CONTROL BOARD
  2. TEMP SENSORS
  3. OPTIONAL SENSOR 3
  4. OPTIONAL SENSOR 2
  5. OPTIONAL SENSOR 1
  6. AERSS
  7. WIRE JOINER
Maintenance

Maintenance Procedures
This section describes the procedures that must be performed as a part of normal maintenance program. Regular servicing of equipment by licensed technician is highly recommended. Regular servicing of your unit helps in maintaining its optimum performance and reliability. The checklist and service periods provided on this manual are guides only, as some sites may require more frequent servicing. Always disconnect electrical power to the unit before performing these procedures unless otherwise required. It is always a safe practice to observe all safety warnings and cautions when conducting maintenance tasks.

DANGER

Live Electrical Connections!
It may be necessary to work with live electrical components on certain maintenance tasks. Only licensed electricians and qualified technicians are allowed to perform these tasks. Beware of Rotating Fan Blades!
Always make sure that all power supplied to the fans are turned Off and isolated.Observe WH&S safety procedures, do not wear loose clothing and any jewellery when working near the fans.
Wear PPE whenever performing any maintenance procedures.
Observe all necessary procedures when working on a confined space.
WARNING

Hazardous Voltage!
Always make sure that all power supply, including remote controls, are disconnected before performing maintenance.
Observe proper LOCK-OUT/TAG-OUT procedures to ensure that power cannot be inadvertently energised. Failure to disconnect power before maintenance procedures can result in serious injury and/or death.
EC Motors are fitted with high power capacitors and can have dangerous residual voltages at motor terminals after power has been isolated. Wait at least 5 minutes after power isolation and test for any residual voltage before beginning service work.

Annual Maintenance Checklists

  • Perform general maintenance inspections.
  • Perform scheduled start-up checks.
  • Leak test refrigerant circuits.
  • Inspect contacts of all contactors and relays. Replace all worn contacts as required.
  • Inspect, clean and tighten all electrical connections.
  • Check fans for balanced operation. Make sure that there are no loose screws / bolts, no fan blades interference and no damage to the fans and guards.
  • Inspect the air filters, clean or replace as required.
  • Clean and repaint any corroded panel section.
  • Ensure no blockage of airflow through variable speed drive.

Cleaning the Condenser Coils
Clean the coils at least once a year or more frequently if unit is located in a dusty and dirty environment, in order to maintain your system’s proper operating performance. High discharge pressures are good indication that the coils need cleaning. When using detergent or solvents to clean the coils, follow the manufacturer’s instructions to avoid potential damage to the coils and to the unit.

To clean the refrigerant coils, use a soft brush and water spray, such as garden hose or pressure washer with low pressure nozzle.

WARNING

Do Not Use High Alkaline Detergent!
When using detergent for coil cleaning, ensure that the alkaline level is no higher than 8.5, which can cause corrosion damage to the coils.
DANGER

No Water into the Electrical Compartments!
Ensure consideration is given to the possibility of water entering the electrical compartments during cleaning of the condenser coil.

Coil Cleaning Procedures

  • Disconnect power to the unit.
  • Remove the louvered panels from the unit to gain access to the air inlet side of the coils.
  • Use a soft brush to remove loose dirt and debris from both sides of the coils.
  • Straighten bent coil fins with fin comb.
  • Prepare the detergent solutions according to the manufacturer’s instructions.
  • Spray solution at a 90° angle to the coils, keeping a minimum nozzle spray angle of 15°, with at least a 1800mm distance from the coils and 600 psi pressure.
  • Spray leaving air side of the coils first then the air inlet side. Allow the solution to stand on the coils for five minutes.
  • Rinse both sides of the coils with cool clean water.
  • Inspect the coils, if they are still dirty, repeat the cleaning procedure.
  • Clean and wipe dry the outer and inner sides of the unit, the refrigerating parts and other components.
  • Ensure that the condensate drain lines are not blocked.
  • Reinstall all unit panels, covers and guards.
  • Restore electrical power to the unit.
Maintenance Frequency Checklist

Regular servicing of equipment by a qualified technician is recommended every 12 months for residential applications and every quarter for commercial applications. Regular servicing of your unit helps in maintaining its optimum performance and reliability. The following checklist and service periods are provided as a guide only, as some sites may require more frequent servicing.

ELECTRICAL

Parts

| Service Period| Detail of Service Check| Service Methods
1 Mth| 3 Mth| 6 Mth| 1 Yr| 2 Yrs| 3 Yrs| 4 Yrs|

5 Yrs

Printed Circuit Boards

| | | | | | | | | Visual Inspection| Tighten Terminals as necessary on printed circuit boards
Electrical Connections| | | | | | | | | Check all electrical terminals, mains, communications, etc|

Re-tighten if loose.

INDOOR UNIT

Parts| Service Period| Detail of Service Check| Service Methods
1 Mth| 3 Mth| 6 Mth| 1 Yr| 2 Yrs| 3 Yrs| 4 Yrs| 5 Yrs
Casing / Panels and Frames| | | | | | | | | Visual check for damage, rust and dust accumulation.| For highly corrosive environment, wash panels quarterly with water and neutral detergent solution. Wax panels. Repair / re- paint where required.
Insulation| | | | | | | | | Visual check for insulation conditions.| Repair / replace insulation material.
Fan| | | | | | | | | Visual check for run out of balance and dust attached| Clean off dust as necessary to negate possibility of fan running out of balance
Motor| | | | Ω| | | | | Visual check on wiring.
Insulation resistance check to be carried out annually| Measure insulation resistance.
Reading should be more than 1MΩ.
Heat Exchanger| | | | | | | | | Check for clogging by dust.
Check for leaks / damage.| Clean air inlet side as necessary.
Straighten any bent fins using fins comb.
Drain Pan/ Condensation line| | | | | | | | | Check for obstructions and free flow of water| Clean to eliminate obstructions/sludge and check condition of pan. Pour water to ensure flow
**Filter*| | | | | | | | | Check for clogging by dust.| Clean Filter
Temperature Readings| | | | | | | | | Measure air on and air off| Place temperature probe in return and supply air of unit.
Damper Motors
(if fitted)| | | | | | | | | Visual inspection of motors open/closing. Ensure no obstructions| Drive motors opened and closed. Ensure correct operation
Duct Works**| | | | | | | | | Inspect duct works for air gaps.| Re-tape any loose ducts.

  • Service period for filter cleaning may vary depending on operating time and surrounding environment.
Start Up and Commissioning Report

INSTALLATION INFORMATION

CUSTOMER| Name:| Tel. Number:
Address:
INSTALLER| Name:| Tel. Number:
Address:
Site Address:| Date Installed:
Model:| Serial Number:
CIRCUIT TEMPERATURE SETTINGS

Supply Air Temperature| | °C
Return Air Temperature| | °C
Suction Temperature| | °C
Discharge Temperature| | °C
Condenser Coil Temperature| | °C
Ambient Temperature| | °C
INDOOR FAN SETTINGS| OUTDOOR FAN SETTINGS
---|---
Indoor Fan Current|

Amps

| Outdoor Fan Current|

Amps

Indoor Fan Airflow|

l / s

|
Indoor Fan PWM|

%

Set Static|

Pa

Check No Active Error Codes on the Unit| Checked:|
---|---|---
Date Checked:|
---|---

Version History

DOCUMENT VERSION

| BOM VERSION|

UPDATE HISTORY

---|---|---

Ver 1

|

-0100

| Released

Ver 2

|

-0100

| Included lower capacity models


Installation and Commissioning Guide – Variable Capacity Commercial Split Ducted Indoor Units 72-96kW (R-410A Series)
Doc. No. 0525-120    Ver. 2  230812

actronair.com.au
1300 522 722

ActronAir EVA720T Variable Capacity Commercial -
Labels
©Copyright 2022 Actron Engineering Pty Limited ABN 34 002767240. ®Registered Trade Marks of Actron Engineering Pty Limited.
ActronAir is constantly seeking ways to improve the design of its products. Therefore, specifications are subject to change without notice.
Document: 0525-121 Ver. 2 Issue Date: 08/2023

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals