nuaire MR-ECO-COOL-V CV Cooling Module Installation Guide

June 12, 2024
Nuaire

MR-ECO-COOL-V CV Cooling Module

MR-ECO-COOL-V

MRXBOXAB-ECO5-AE(OH)CV Cooling Module

Installation Manual

1.0 SAFETY INFORMATION

• The provision of the electrical supply and the connection of the unit to the mains  must be carried out by a qualified electrician. Ensure that the mains supply (Voltage,  Frequency and Phase) complies with the rating label.

• Isolate from power supply before removing any covers. During installation / maintenance ensure all covers are fitted before switching on the mains supply. •All-pole disconnection from the mains as shown in the wiring diagram must be incorporated within the fixed wiring and shall have a minimum contact separation of  3mm in accordance with latest edition of the wiring regulations.

• This unit must be earthed.

• Ducting must be securely fixed with screws to the spigot to prevent access to live  parts.

• If the supply cord is damaged, it must be replaced by its service agent or similarly  qualified persons in order to avoid a hazard.

• When installing the unit, take care not to damage electrical or other hidden components – do not drill the unit casing.

• Precautions must be taken to avoid the back-flow of gases into the room from the  open flue of gas or other fuel-burning appliances.

• The unit must be installed indoors, and away from direct sources of frost, heat and  water spray or moisture generation. Ambient temperature range -5 to 40 °C.  •The cooling unit is an electro-mechanical device that contains and uses R134a  refrigerant. Refrigerant weight, 0.35kg (Maximum).

• This appliance should not be used by children or persons with reduced physical,  sensory or mental capabilities or lack of experience and knowledge, unless they  have been given supervision or instruction concerning the safe use of the appliance  by a person responsible for their safety. Children shall not play with the appliance.  Cleaning and user maintenance shall not be carried out by children. This unit contains  live electrical components, moving parts and refrigerant under pressure. Always site  out of reach of children and protect from vandalism and accidental damage.

1 Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 02. 08. 23. Document Number 672079

Installation Manual MR-ECO-COOL-V

• Keep the unit upright during installation and level the unit in its final position. Once  in final position, leave unit for a minimum of 4 hours before activation.

• Ensure that the airflow through the unit does not fall below 216 m³/h (60 l/s) during  operation.

• Lifting point to be used for lifting the cooling module ONLY. It must not be used to  lift the Cooling Module plus MVHR.

• Do not damage the pipes of the refrigerant circuit.

• Unit to be maintained by F-Gas qualified persons only.

• Do not use the unit if damaged, contact after sales.

• In the event of gases escaping from damaged pipework, avoid contact with eyes.  1.1 Symbols

GENERAL WARNING
Signifies a general warning regarding hazard specified by supplementary information.

ELECTRIC SHOCK
This unit must be completely electrically isolated before any panels are removed. Check   mains supply and control connections.

COMPRESSED GAS
Liquefied Gas (R134a): H280: Contains gas under pressure; may explode if heated.

REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing, operating or maintaining this product.

1.2 Important Information

This manual contains important information on the safe and  appropriate assembly, transport, commissioning, operation,  maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted  rules of current technology, there is still a danger of personal injury or  damage to equipment if the following general safety instructions and  the warnings contained in these instructions are not complied with.

  • Read these instructions completely and thoroughly before  working with the product.
  • Keep these instructions in a location where they are accessible  to all users at all times.
  • Always include the operating instructions when you pass the  product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is  recommended when interacting with Nuaire product:

  • Protective Steel Toed Shoes – when handling heavy objects.
  • Full Finger Gloves (Marigold PU800 or equivalent) – when  handling sheet metal components. 
  • Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent)  – when conducting light work on the unit requiring tactile  dexterity. 
  • Safety Glasses – when conducting any cleaning/cutting operation  or exchanging filters. 
  • Reusable Half Mask Respirators – when replacing filters which  have been in contact with normal room or environmental air.

Nuaire would always recommend a site specific risk assessment by a  competent person to determine if any additional PPE is required.

2 Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 02. 08. 23. Document Number 672079

Installation Manual MR-ECO-COOL-V

2.0 HANDLING

Offloading and positioning of the equipment is the responsibility of
the purchaser. Items should only be lifted by competent personnel
following appropriate risk assessment.

Cooling Module Weighs 65kg. Appropriate manual handling
assessments must be conducted before work can commence.

Combined weight of MRXBOXAB-ECO5-AE(OH)CV and Cooling
module = 121 kg. Lifting of assembled Cooling Module + MVHR
should be carried out with genie-lift or similar with assembly being
supported from below.

The cooling module is supplied with a lifting point and a lifting
eyelet. This is for the lifting the cooling module ONLY and should
NOT be used to lift the assembled Cooling Module + MVHR.

Once the Cooling Module has been positioned and secured in place
with the side and top brackets, replace the lifting eyelet with the
supplied plug to ensure the unit is sealed.

3.0 DIMENSIONS

dimensions

Installation Manual MR-ECO-COOL-V

mounting bracket

4.0 INSTALLATION

The Cooling Module (MR-ECO-COOL-V) has been designed for use
with the MRXBOXAB-ECO5-AE(OH)CV and 7713807 control only.
Isolate power supply before commencing work. Ensure the Nuaire
controls are electrically isolated from the mains supply.
Recommend mounting method uses the EC05-AE-1Z-STND.
Alternatively angled brackets are available (Part Number:
7713882). However, it is the responsibility of the installer to ensure
the mounting surface for the brackets will adequately support the
combined weight of both MVHR and Cooling module (Combined
Weight = 121kg).

4.1 General Installation

Installation must be carried out by competent personnel in accordance
with the appropriate authority and conforming to all statutory
governing regulations. All mains wiring must be in accordance with the
current I.E.E. Regulations, or the appropriate standards. Ensure that the
mains supply (Voltage, Frequency and Phase) complies with the rating
label.
ADF 2010 DVCG: “Ensure the final location of equipment offers
sufficient space to allow access for maintenance. The fan unit [including
cooling module] should be installed to allow sufficient space for end
of life replacement of the whole unit or key mechanical/electrical
components. This should be achievable without the need to remove
fixed structures or significant lengths of connected ductwork.” In
addition to the space requirement the total weight of the fan unit and
cooling module products should be considered to allow the use of
mechanical lifting equipment required to safely remove and replace the
product.
The unit and its controls must be installed indoors, and away from
direct sources of frost, heat and water spray or moisture generation.
Ambient temperature range -5 to 40°C.
This unit must be earthed.
When installing the unit, take care not to damage electrical or other
hidden components – do not drill the unit casing.
This units contains pressurised components.
The cooling unit is an electro-mechanical device that contains and uses
R134a refrigerant.
This unit contains live electrical components, moving parts and
refrigerant under pressure. Always site out of reach of children and
protect from vandalism and accidental damage.
Keep the unit horizontal during installation and level the unit in its final
position. Once in final position, leave unit for a minimum of 4 hours

Airflows of less than 60 l/s may cause the in-built thermal
overload protection to activate to protect the unit. Ensure airflows
are balanced and commissioned in accordance with the original
design criteria.
The Cooling module MUST not be run without the specified
minimum airflow. This can result in the compressor overheating
and may invalidate the warranty.
Typical installation is Floor Mounted using (ECO5-AE-1Z-STND).

4.2 Unit Installation

The transit bolts must be removed from the
MRXBOXAB-ECO5-AE(OH)CV before placing the Cooling Module on
top of the MVHR unit.
Where the MRXBOXAB-ECO5-AECV and MR-ECO-COOL-V are
assembled prior to transport to site, such as in a packaged utility
cupboard, the installer must ensure that the combined assembly is
secured and transported in the upright position.
Following the MRXBOXAB-ECO5-AE(OH)CV being levelled and
installed on an ECO5-AE-1Z-STND, the supplied gaskets must be
installed as shown in Figure 6. Remove the backing paper of the foam
gaskets and whilst aligned with the holes of the MVHR unit fit each
gasket adhesive side down.
Lift the cooling module (section) above the MVHR unit and lower
into place. Do not drag the unit over the foam gaskets as this may
damage foam gaskets.
Once in position secure the side brackets with the fixings supplied
(fitted to the units) and secure the top of the unit to a suitable surface
with the adjustable top bracket supplied (Figure 6).

4.2.1 Opposite Handed Units

The Cooling Module can be installed on opposite handed MVHR units
by rotating the module 180°. In doing this the drain, fly lead and access
to coils will be flipped to the opposite side. The drain position will be
located towards the front at the bottom of the unit.

4.3 Condensate Drain Installation

The unit provides an external Ø21.5mm (PCV) condensate drain pipe
fitted flush to the outer case to minimize its foot print. Conventional
push on plumbing connections, connect to the drain (MAX Outer
Diameter of fitting: 37mm).
Ensure the cooling module is installed level.
If the condensate pipe is fitted in an unheated space the pipe should be
insulated to prevent freezing. Ensure the cooling module has its own
dry trap separate to the MVHR.

4.3.1 Standard Hand Installation

The drain is positioned at the rear bottom corner on the right-hand side
panel on a standard hand unit.

4.3.2 Opposite Hand Installation

The unit is rotated 180°, positioning of the drain towards the front, at
the bottom corner on the left-hand side panel.

5.0 DUCTING

Before commencing ducting installation reference should be made
to building regulations document “Domestic ventilation compliance
guide”. This document supports ADF2010 and details installation,
testing and commissioning of all ventilation systems.
It is recommended that rigid ducting must be used it all times. Fresh-air
Intake and stale air Exhaust ducts will carry cold air in winter. Supply
air duct will carry cold air when Cooling Module is operating. Therefore
Intake, Exhaust and supply ducts will be at risk of condensation forming
on external surfaces and should all be thermally insulated.
Any duct component including ancillaries such as carbon filters must
be insulated if they are carrying colder air produced by the cooling
module. Flexible connections should be avoided. Nuaire Duct master
thermal ducting should be used on Intake, Exhaust and Supply duct
runs. If flexible connections cannot be avoided, FLDI150 Insulated
Flexible Duct should be used

Ducting must be installed in such a way that resistance to airflow is
minimised. Bends should be kept to a minimum.
Ducting joints must be sealed with suitable duct sealant and needs to
be taped. Ducting shall be adequately and reliably fixed.
Ducting to cooling module must be securely fixed with screws to the
spigots to prevent access to live parts.

6.0 SUPPLY TEMPERATURES

Supply air temperature is critical to ensure good cooling distribution.
There is a possibility of condensation forming on grilles or valves at low
airflows. If this occurs the airflow should be increased.

7.0 ELECTRICAL INSTALLATION

Electrical Details
Voltage: 230V 1ph 50Hz
Running Current: 3.5 A
This unit must be earthed..

7.1 Wiring Diagrams

7.1.1 Unit

wiring diagram

7.1.2 Summer / Winter Switch (Supplied with MVHR)

summer

8.0 CONTROLS / DESCRIPTION OF OPERATION

  • MVHR will run continuously at Background/Whole dwelling duty
    (Speed 1) unless it receives a 230v signal to Switched-Live input
    connections SL1 or SL2.

  • Cooling module will be enabled to run and MVHR enabled to
    speed 3 by a 230v Switched live from wall mounted temperature
    sensor CM-THERM-CONTROL (supplied).

  • The wall mounted temperature sensor will control the cooling
    module and MVHR unit. On reaching the set point (user defined)
    the Cooling Module will operate and the MVHR will increase to
    speed 3. For energy efficient operation, the set point should be
    adjusted to 23 deg C. Note that the wall mounted temperature
    sensor also features an ECO mode which is pre-set to 23°C (not
    adjustable) and can be set to operate between 1 and 24 hours by
    the user. Switching the wall mounted temperature sensor
    (CM-THERM-CONTROL) off will disable the cooling module.

  • It is recommended that, if possible, the cooling unit be interlocked
    with the heating system to prevent triggering when heat is being
    called for. Figure 9 shows connection to a heating system which is
    normally closed via a link. This can be replaced by a suitable VOLT
    FREE connection to the heating device.

  • Summer/Winter switch (Supplied with MVHR). Should be set to
    summer mode when cooling is expected to run.

  • Summer mode can be selected year round to attempt to mitigate
    overheating caused by solar gains but must be selected when
    cooling is expected to run (summer months).

  • Winter mode ensures the MVHR will recover heat at all times.

  • For further details, see MRXBOXAB-ECO5-AE(OH)CV
    installation manual (671861).

9.0 COMMISSIONING

To ensure the cooling module operates correctly and prevent
the thermal overload protection from tripping, there must be a
minimum airflow of 216 m³/h (6v0 l/s).
It is recommended the ventilation unit is set to speed 3 on supply
and extract, potentiometers are set to maximum (fully clockwise).
To commission the MVHR unit providing the air flow through the
cooling module, please refer to MRXBOXAB-ECO5-AE(OH)CV
installation manual (Document number 671861).

10.0 MAINTENANCE

Isolate before commencing work, make sure that the unit, switched
live and Nuaire control are electrically isolated from the mains
supply and switched live supply.
It is important that maintenance checks are recorded and that the
schedule is always adhered to. In all cases, the previous report should
be referred to.

10.1 Access

Access to both Coils for cleaning can be gained by removing the front
cover of the outer case and the inner covers of the Cooling Module.
Depending on the orientation of the unit (standard or opposite hand)
access will be given to one of the two coils. To access the second coil an
internal access panels must be removed.
The compressor requires no maintenance.

10.2 Annual Maintenance – Evaporator and Condenser Coils

  • Inspect all coils for signs of damage or dirt. Loose dirt may be
    removed by using a soft brush, taking care not to brush the dirt
    into the coil, blocking the fins. Damaged fins should be combed
    out using a coil comb.

  • If the coil is excessively dirty check that MVHR filters are still in
    place.

  • MVHR Filters are to be inspected every 6 months and replaced
    every 12 months (or sooner if required).

  • If the coil is excessively dirty, use a proprietary cleaning agent, e.g.
    HYDRO-COIL or MULTISOLVE.

  • Inspect the condensate drain tray and clean as required.

  • Check all electrical connections for tightness.

  • Switch on the power to the unit. Check the operation of the
    mechanical cooling system.
    •Check that all the panels are in place and that the unit is in a clean
    condition.
    •In the event the cooling module is not operating initially inspect
    the MCB in the controls.

10.2.1 Refrigeration Circuit Components

All repair and replacement work on refrigeration components must
be carried out by a fully qualified refrigeration engineer, trained
in maintenance and refrigeration recovery, and with a sound
knowledge of all relevant safety regulations pertaining to the job.
All refrigerant in the unit must be reclaimed and disposed of safely.

11.0 WARRANTY

The warranty starts from the day of delivery and includes parts only.
This warranty is void if the equipment is modified without
authorization, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good practice. Only genuine
Nuaire parts and filters may be used to maintain the unit. Failure to
maintain the unit as recommended will invalidate the warranty.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale. Customers purchasing from
outside of the UK should contact Nuaire International Sales office for
further details.

12.0 END-OF-LIFE AND RECYCLING

Where possible Nuaire use components which can be largely recycled
when the product reaches its end-of-life:

  • Fans, motors, controls, actuators, cabling and other electrical
    components can be segregated into WEEE recycling streams.

  • Sheet metal parts, aluminium extrusion, heating/cooling coils and
    other metallic items can be segregated and fully recycled.

  • EPP, plastic ducting, nylon corner pieces, plastic heat exchangers,
    packaging material and other plastic components can be
    segregated into mixed plastic and widely recycled.

  • Cardboard packaging, wood, used filters and other paper
    components can be largely recycled or fully processed in energy
    from waste centres.

  • Remaining Items can be further segregated and processed in
    accordance with the zero waste hierarchy. Please call After Sales
    Support for further information on items not listed above.
    Ensure that Nuaire product is made safe from any electrical / water
    / refrigerant supplies before dismantling commences. This work
    should only be undertaken by a qualified person in accordance with
    local authority regulations and guidelines, taking into account all
    site based risks.

13.0 AFTER SALES ENQUIRIES

For technical assistance or further product information, including spare
parts and replacement components, please contact the After Sales
Department. Before calling please establish the serial number of the
unit (this information will be available on the unit label).

Telephone 02920 858 400
aftersales@nuaire.co.uk

Technical or commercial considerations may, from time to time,
make it necessary to alter the design, performance and dimensions
of equipment and the right is reserved to make such changes without
prior notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Nuaire User Manuals

Related Manuals