Endress Hauser Liquiphant FTL41 Point Level Switch Instruction Manual

June 12, 2024
Endress Hauser

Endress Hauser - logoOperating Instructions
Liquiphant FTL41
Vibrionic
Point level switch for liquidsEndress Hauser Liquiphant FTL41 Point Level
Switch

Liquiphant FTL41 Point Level Switch

Endress Hauser Liquiphant FTL41 Point Level Switch -
feagerwww.endress.com/deviceviewer

About this document

1.1 Purpose of this document
These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.

1.2 Symbols
1.2.1 Safety symbols

DANGER
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTICE
This symbol contains information on procedures and other facts which do not result in personal injury.

1.2.2 Electrical symbols
Ground connection
Grounded clamp, which is grounded via a grounding system.
ETS-Lindgren 8000-040 RF Power Amplifier - icon 6 Protective earth (PE)
Ground terminals, which must be grounded prior to establishing any other connections.
The ground terminals are located on the inside and outside of the device.
1.2.3 Tool symbols
 Flat-blade screwdriver
 Allen key
Open-ended wrench

1.2.4 Symbols for certain types of information
Permitted
Procedures, processes or actions that are permitted.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information
 Reference to documentation
Reference to another section
1.,2. ,3.  Series of steps
1.2.5 Symbols in graphics
A, B, C …  View
1, 2, 3 …  Item numbers
Hazardous area
Safe area (non-hazardous area)

Basic safety instructions

2.1 Requirements for the personnel
The personnel must fulfill the following requirements to carry out the necessary tasks, e. g., commissioning and maintenance:

  •  Trained, qualified specialists must have a relevant qualification for the specific function and task
  • Are authorized by the plant owner/operator
  • Are familiar with federal/national regulations
  • Must have read and understood the instructions in the manual and supplementary documentation
  • Follow instructions and comply with conditions

2.2 Intended use

  •  Only use the device for liquids
  •  Improper use can pose hazards
  • Ensure that the measuring device is free of defects while it is in operation
  • Use the device only for media to which the wetted materials have an adequate level of resistance
  • Do not exceed or drop below the relevant limit values for the device
     For more details, see the “Technical data” section
     See the Technical Documentation

2.2.1 Incorrect use
The manufacturer is not liable for damage caused by improper or non-intended use.
Residual risks
Due to heat transfer from the process, the temperature of the electronics housing and the assemblies contained therein may rise to 80 °C (176 °F) during operation.
Danger of burns from contact with surfaces!

  • If necessary, ensure protection against contact to prevent burns.

For requirements concerning functional safety in accordance with IEC 61508, the associated SIL documentation must be observed.
2.3 Workplace safety
For work on and with the device:

  • Wear the required personal protective equipment according to federal/national regulations.

2.4 Operational safety
Risk of injury!

  • Operate the device only if it is in proper technical condition, free from errors and faults.
  • The operator is responsible for ensuring the interference-free operation of the device.

Modifications to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers.

  • If, despite this, modifications are required, consult with Endress+Hauser.

Repair
To ensure continued operational safety and reliability:

  • Only perform repair work on the device if this is expressly permitted.
  • Observe federal/national regulations pertaining to the repair of an electrical device.
  • Use original spare parts and accessories from Endress+Hauser only.

Hazardous area
To eliminate danger to persons or the facility when the device is used in the hazardous area (e.g. explosion protection):

  • Check the nameplate to verify whether the ordered device can be used for the intended purpose in the hazardous area.
  • Observe the specifications in the separate supplementary documentation that is an integral part of this manual.

2.5 Product safety
This device is designed in accordance with good engineering practice to meet state-of-threat safety requirements, has been tested, and left the factory in a condition in which it is safe to  operate.
It meets the general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.

Product description

Point level switch for all liquids, for minimum or maximum detection in tanks, vessels and pipes.
3.1 Product design

Endress Hauser Liquiphant FTL41 Point Level Switch - Product
design 1 Product design

  1. Housing with electronic insert and cover
  2. Process connection flange (optional)
  3. Process connection (optional)
  4. Compact probe version with tuning fork
  5. Pipe extension probe with tuning fork
  6. Short tube version of probe with tuning fork

Incoming acceptance and product identification
4.1 Incoming acceptance
Check the following during incoming acceptance:

  • Are the order codes on the delivery note and the product sticker identical?
  • Are the goods undamaged?
  • Do the data on the nameplate match the ordering information on the delivery note?
  •  If required (see nameplate): are the Safety Instructions e.g. XA provided?

If one of these conditions is not met, please contact the manufacturer’s sales office.
4.2 Product identification
The device can be identified in the following ways:

  • Nameplate specifications
  • Extended order code with breakdown of the device features on the delivery note
  • Enter serial number from nameplates in W@M Device Viewer www.endress.com/deviceviewer. All of the information on the measuring device is displayed along with an overview of the scope of technical  documentation provided.
  • Enter the serial number on the nameplate into the Endress+Hauser Operations app or scan the 2-D matrix code on the nameplate with the Endress+Hauser Operations app

4.2.1 Nameplate
The information that is required by law and is relevant to the device is shown on the nameplate, e.g.:

  • Manufacturer identification
  • Order number, extended order code, serial number
  • Technical data, degree of protection
  • Firmware version, hardware version
  • Approval-related information, reference to Safety Instructions (XA)
  • Data Matrix code (information about the device)

4.2.2 Electronic insert
Identify the electronic insert via the order code on the nameplate.
4.2.3 Manufacturer address
Endress+Hauser SE+Co. KG Hauptstraße 1 79689 Maul burg, Germany Place of manufacture: See nameplate.
4.3 Storage and transport
4.3.1 Storage conditions
Use original packaging.
Storage temperature
–40 to +80 °C (–40 to +176 °F)
4.3.2 Transporting the device

  • Transport the device to the measuring point in the original packaging
  • Hold the device by the housing, flange or extension pipe
  • Do not bend, shorten or extend the tuning fork

Endress Hauser Liquiphant FTL41 Point Level Switch -
Transporting

Mounting

WARNING
Loss of protection rating if the device is opened in a wet environment.

  • Only open the device in a dry environment!

Mounting instructions

  • Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
  • Vertical orientation from above for device with long pipe
  • Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)

Endress Hauser Liquiphant FTL41 Point Level Switch -
Transporting1

3 Installation examples for a vessel, tank or pipe

5.1 Mounting requirements
5.1.1 Take switch point into consideration
The following are typical switch points, depending on the orientation of the point level switch.
Water +23 °C (+73 °F)
Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)

Endress Hauser Liquiphant FTL41 Point Level Switch -
Transporting2 4 Typical switch points. Unit of measurement mm (in)

A Installation from above
B Installation from below
C Installation from the side
D Switch point
5.1.2 Take viscosity into consideration
Viscosity values

  • Low viscosity : < 2 000 mPa⋅s
  • High viscosity: > 2 000 to 10 000 mPa⋅s

Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.

Endress Hauser Liquiphant FTL41 Point Level Switch -
Transporting3 5 Installation example for low-viscosity liquids. Unit of measurement mm (in)

High viscosity
NOTICE
Highly viscous liquids may cause switching delays.

  • Make sure that the liquid can run off the tuning fork easily.
  • Deburr the socket surface.
    High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
    The tuning fork must be located outside the installation socket!

Endress Hauser Liquiphant FTL41 Point Level Switch - tuning
fork 6 Installation example for a highly viscous liquid. Unit of measurement mm (in)

5.1.3 Avoid buildup

  • Use short installation sockets to ensure that the tuning fork projects freely into the vessel
  • Leave sufficient distance between the buildup expected on the tank wall and the tuning fork

Endress Hauser Liquiphant FTL41 Point Level Switch -
buildup

7 Installation examples for a highly viscous process medium

5.1.4 Take clearance into consideration
Allow sufficient space outside the tank for mounting, connection and settings involving the electronic insert.

Endress Hauser Liquiphant FTL41 Point Level Switch -
consideration

8 Take clearance into consideration

5.1.5 Support the device
Support the device in the event of severe dynamic load. Maximum lateral loading capacity of the pipe extensions and sensors: 75 Nm (55 lb ft).

Endress Hauser Liquiphant FTL41 Point Level Switch -
consideration1 9 Examples of support in the event of dynamic load

Marine approval: In the case of pipe extensions or sensors longer than 1 600 mm, a support is needed at least every 1 600 mm.
5.1.6 Weld-in adapter with leakage hole
Weld in the weld-in adapter in such a way that the leakage hole is pointing downwards. This enables any leaks to be detected quickly.Endress Hauser
Liquiphant FTL41 Point Level Switch - leakage hole

5.2 Mounting the device
5.2.1 Required tool

  • Open-ended wrench for sensor installation
  • Allen key for housing locking screw

5.2.2 Installation
Align the tuning fork using the marking
The tuning fork can be aligned using the marking. Medium can thus run off easily and buildup is avoided.
Markings may include the following:

  • Material information, thread name or circle on the hexagonal nut or on the weld-in adapter
  • II symbol on the back of the flange or Tri-Clamp

Endress Hauser Liquiphant FTL41 Point Level Switch - leakage
hole1

Installing in pipes

  • Flow velocity up to 5 m/s with a viscosity of 1 mPa⋅s and density of 1 g/cm3 (SGU). Check for correct functioning in the event of other process medium conditions.
  • The flow will not be significantly impeded if the tuning fork is correctly aligned and the marking is pointing in the direction of flow.
  • The marking is visible when installed.

Endress Hauser Liquiphant FTL41 Point Level Switch -
pipes

Screwing in the device

  • Turn by the hex bolt only, 15 to 30 Nm (11 to 22 lbf ft)
  • Do not turn at the housing!

Endress Hauser Liquiphant FTL41 Point Level Switch -
Screwing

Aligning the cable entryEndress Hauser Liquiphant FTL41 Point Level
Switch - cable entry

The locking screw is not tightened when the device is delivered.

  1. Loosen the external locking screw (maximum 1.5 turns).

  2. Turn the housing, align the cable entry.
    Avoid moisture in the housing, provide a loop to allow moisture to drain off.

  3. Tighten the external locking screw.

5.3 Sliding sleeves
For more details, see the “Accessories” section.

5.4 Post-mounting check

  • Is the device undamaged (visual inspection)?
  • Does the measuring device meet the measuring point specifications?

For example:

  • Process temperature
  • Process pressure
  • Ambient temperature
  • Measuring range
  • Are the measuring point number and labeling correct (visual inspection)?
  • Is the device adequately protected from wet conditions and direct sunlight?
  •  Is the device properly secured?

Electrical connection

6.1 Required tool

  • Screwdriver for electrical connection
  • Allen key for screw of cover lock

6.2 Connecting requirements
6.2.1 Cover with securing screw
In the case of devices for use in the hazardous area with a certain type of protection, the cover is sealed by a securing screw.
NOTICE
If the securing screw is not positioned correctly, the cover cannot provide secure sealing.

  • Open the cover: slacken the screw of the cover lock with a maximum of 2 turns so that the screw does not fall out. Fit the cover and check the cover seal.
  • Close the cover: screw the cover securely onto the housing, making sure that the securing screw is positioned correctly. There should not be any gap between the cover and housing.

Endress Hauser Liquiphant FTL41 Point Level Switch - securing
screw

6.2.2 Connecting protective earth (PE)
The protective earth conductor at the device must only be connected if the device’s operating voltage is ≥ 35 VDC or ≥ 16 Acuff.
When the device is used in hazardous areas, it must always be included in the potential equalization of the system, irrespective of the operating voltage.
The plastic housing is available with or without an external protective earth connection (PE). If the operating voltage of the electronic insert is < 35 V, the plastic housing has no external protective earth connection.

6.3 Connecting the device
Housing thread
The thread of the electronics and connection compartment is coated with lubricant varnish.
Avoid additional lubrication.

6.3.1 3-wire DC-PNP (electronic insert FEL42)

  • Three-wire DC version
  • Switches the load via the transistor (PNP) and separate connection, e.g. in conjunction with programmable logic controllers (PLC), DI modules according to EN 61131-2

Supply voltage
WARNING
Failure to use the prescribed power unit.
Risk of potentially life-threatening electric shock!

  • The FEL42 may only be powered by power supply units with secure galvanic isolation in accordance with IEC 61010-1.

U = 10 to 55 VDC
Comply with the following according to IEC/EN61010-1: provide a suitable circuit breaker for the device and limit the current to 500 mA, e.g. by installing a 0.5 A fuse (slow-blow) in the power supply circuit.

Power consumption
P < 0.5 W
Current consumption
I ≤ 10 mA (without load)
The red LED flashes in the event of an overload or short-circuit. Check for an overload or short-circuit every 5 s.
Load current
I ≤ 350 mA with overload and short-circuit protection
Residual current
I < 100 µA (for blocked transistor)
Residual voltage
U < 3 V (for switched through transistor)
Behavior of output signal

  • OK status: switched through
  • Demand mode: blocked
  • Alarm: blocked

Terminals
Terminals for cable cross-section up to 2.5 mm² (14 AWG). Use ferrules for the wires.
Overvoltage protection
Overvoltage category II

Terminal assignment

Endress Hauser Liquiphant FTL41 Point Level Switch -
Terminal

A Terminal assignment at electronic insert
B Terminal assignment at M12 plug according to EN61131-2 standard
Behavior of the switch output and signaling

Endress Hauser Liquiphant FTL41 Point Level Switch -
signaling

MAXDIP switch for setting the MAX safety
MIN DIP switch for setting the MIN safety
RD LED red for warning or alarm
YE LED yellow, switch status
GN LED green, operational status, device on
IL Load current switched through
6.3.2 Universal current connection with relay output (electronic insert FEL44)

  • Switches the loads via 2 potential-free change-over contacts
  • 2 separate change-over contacts (DPDT)

WARNING
An error at the electronic insert can cause the permitted temperature for touch-safe surfaces to be exceeded. This presents a risk of burns.

  • Do not touch the electronics in the event of an error!

Supply voltage
U= 19 to 253 VAC / 19 to 55 VDC
Comply with the following according to IEC/EN61010-1: provide a suitable circuit breaker for the device and limit the current to 500 mA, e.g. by installing a 0.5 A fuse (slow-blow) in the power supply circuit.

Power consumption
S < 25 VA, P < 1.3 W
Connectable load
Loads switched via 2 potential-free changeover contacts (DPDT)

  • IAC ≤ 6 A (Ex de 4 A), U~ ≤ AC 253 V; P~ ≤ 1 500 VA, cos φ = 1, P~ ≤ 750 VA, cos φ > 0.7
  • IDC ≤ 6 A (Ex de 4 A) to DC 30 V, IDC ≤ 0.2 A to 125 V

According to IEC 61010, the following applies: Total voltage from relay outputs and power supply ≤ 300 V.
Use electronic insert FEL42 DC PNP for small DC load currents, e.g. for connection to a PLC.
Relay contact material: silver/nickel AgNi 90/10
When connecting a device with high inductance, provide a spark suppressor to protect the relay contact. A fine-wire fuse (depending on the connected load) protects the relay contact in the event of a short-circuit.
Both relay contacts switch simultaneously.
Behavior of output signal

  • OK status: relay energized
  • Demand mode: relay de-energized
  • Alarm: relay de-energized

Terminals
Terminals for cable cross-section up to 2.5 mm²  (14 AWG). Use ferrules for the wires.
Overvoltage protection
Overvoltage category II
Terminal assignment

Endress Hauser Liquiphant FTL41 Point Level Switch -
signaling1

  1. When bridged, the relay output works with NPN logic
  2. Connectable load

Behavior of the switch output and signaling

Endress Hauser Liquiphant FTL41 Point Level Switch -
Behavior

MAXDIP switch for setting the MAX safety
MIN DIP switch for setting the MIN safety
RD LED red for alarm
YE LED yellow, switch status
GN LED green, operational status, device on

6.3.3 2-wire NAMUR > 2.2 mA/< 1.0 mA (electronic insert FEL48)

  • To connect to isolating amplifiers according to NAMUR (IEC 60947-5-6), e.g. Nivotester FTL325N from Endress+Hauser
  • To connect to isolating amplifiers of third-party suppliers according to NAMUR (IEC 60947-5-6), a permanent power supply for the electronic insert FEL48 must be ensured
  • Signal transmission H-L edge 2.2 to 3.8 mA/0.4 to 1.0 mA according to NAMUR (IEC 60947-5-6) on two-wire cabling

Supply voltage
U = 8.2 VDC
Comply with the following according to IEC/EN61010-1: provide a suitable circuit breaker for the device.

Power consumption
P < 50 mW
Behavior output signal

  • OK state: Current 2.2 to 3.8 mA
  • Demand mode: Current 0.4 to 1.0 mA
  • Alarm: Current 0.4 to 1.0 mA

Terminals
Terminals for cable cross-section up to 2.5 mm 2 (14 AWG). Use ferrules for the wires.
Overvoltage protection
Overvoltage category II
Terminal assignment

Endress Hauser Liquiphant FTL41 Point Level Switch -
Behavior1

Behavior of the switch output and signaling

Endress Hauser Liquiphant FTL41 Point Level Switch - switch
output

MAXDIP switch for setting the MAX safety
MIN DIP switch for setting the MIN safety
RD LED red for alarm
YE LED yellow, switch status
GN LED green, operational status, device on
6.3.4 Connecting the cables
Required tools

  • Flat-blade screwdriver (0.6 mm x 3.5 mm) for terminals
  • Suitable tool with width across flats AF24/25 (8 Nm (5.9 lbf ft)) for M20 cable gland

Endress Hauser Liquiphant FTL41 Point Level Switch - Required
tools

  1. M20 coupling (with cable entry), example
  2. Conductor cross-section maximum 2.5 mm 2 (AWG14), ground terminal on inside in housing + terminals on the electronics
  3. Conductor cross-section maximum 4.0 mm2 (AWG12), ground terminal on outside of the housing (example: plastic housing with outer protective ground connection (PE))
    ⌀d Nickel-plated brass 7 to 10.5 mm (0.28 to 0.41 in)
    ⌀d Plastic 5 to 10 mm (0.2 to 0.38 in)
    ⌀d Stainless steel 7 to 12 mm (0.28 to 0.47 in)

Pay attention to the following when using the M20 coupling
Following cable entry:

  • Counter-tighten the coupling
  • Tighten the union nut of the coupling with 8 Nm (5.9 lbf ft)
  • Screw the enclosed coupling into the housing with 3.75 Nm (2.76 lbf ft)

6.4 Post-connection check

  • Is the device or cable undamaged (visual inspection)?
  • Do the cables used comply with the requirements?
  • Do the mounted cables have adequate strain relief?
  • Are the cable glands mounted and firmly tightened?
  • Does the supply voltage match the information on the nameplate?
  • No reverse polarity, is terminal assignment correct?
  • If supply voltage is present, is the green LED lit?
  • Are all the housing covers installed and tightened?
  • Optional: Is the cover tightened with securing screw?

Operation options

7.1 Overview of operation options
7.1.1 Operation concept
Operation with DIP switches on the electronic insert
7.1.2 Elements on the electronic insertEndress Hauser Liquiphant FTL41
Point Level Switch - electronic insert

  1. LED red, for warning or alarm
  2. LED yellow, switch status
  3. LED green, operational status (LED green lights up = device on)
  4. DIP switch to set the density to 0.7 or 0.5
  5. Relay contact terminals
  6. Power supply terminals
  7. DIP switch for setting MAX/MIN safety

Commissioning

8.1 Function check
Before commissioning the measuring point, check whether the post-mounting and postconvention checks have been performed:

  • Checklist in “Post-mounting check” section
  • Checklist in “Post-connection check” section

8.2 Switching on the device
During the power-up time, the device output is in the safety-oriented state, or in the alarm state if available.
The output is in the correct state after a maximum of 3 s following device power-up.
8.3 Further information
Further information and the documentation currently available can be found on the Endress+Hauser website: www.endress.com → Downloads.

Diagnostics and troubleshooting

The device indicates warnings and errors via the LEDs on the electronic insert. All the device warnings and faults are for information purposes only and do not have a safety function. Depending on the diagnostic  message, the device behaves as per a warning or fault condition.
The device behaves in accordance with NAMUR Recommendation NE131 “NAMUR standard device requirements for field devices for standard applications”.
9.1 LED on electronic insert
Green LED not lit
Possible cause: No power supply
Troubleshooting: Check plug, cable and power supply
LED flashing red
Possible cause: Overload or short-circuit in load circuit
Troubleshooting: Clear the short-circuit
Reduce maximum load current to below 350 mA
Red LED continuously lit
Possible cause: Internal sensor error or electronic fault
Troubleshooting: Replace device
9.2 Firmware history
V01.01.zz (01.2019)

  • Valid for electronic inserts: FEL41, FEL44, FEL48
  • Valid from documentation version: BA01893F/00/EN/01.19
  • Changes: none; 1st version (original software)

Maintenance

No special maintenance work is required.
10.1 Maintenance tasks
10.1.1 Cleaning
It is not permitted to use the device with abrasive media. Material abrasion on the tuning fork can result in the device malfunctioning.

  • Clean the tuning fork as necessary
  • Cleaning is also possible in the installed state, e. g. CIP Cleaning in Place and SIP Sterilization in Place

Repair
11.1 General notes
11.1.1 Repair concept
Endress+Hauser repair concept

  • The devices have a modular design
  • Customers can carry out repairs
    For more information on service and spare parts, please contact your Endress+Hauser sales representative.

11.1.2 Repair of Ex-certified devices
WARNING
Incorrect repair can affect electrical safety!
Explosion Hazard!

  • Only specialist personnel or the Endress+Hauser service team may carry out repairs on Ex-certified devices.
  • Relevant standards and national regulations on hazardous areas, safety instructions and certificates must be observed.
  • Use only original Endress+Hauser spare parts.
  • Please note the device designation on the nameplate. Only identical parts may be used as replacements.
  • Carry out repairs according to the instructions.
  • Only the Endress+Hauser service team is permitted to modify a certified device and convert it to another certified version.
  • All repairs and modifications must be documented.

11.2 Spare parts

  • Some replaceable device components are identified by a spare part nameplate. This contains information about the spare part.
  • All the spare parts for the measuring device, along with the order code, are listed in the W@M Device Viewer (www.endress.com/deviceviewer) and can be ordered. If available, users can also download the  associated Installation Instructions.

Device serial number or QR code:
Located on the device and spare part nameplate.
11.3 Return
The requirements for safe device return can vary depending on the device type and national legislation.

  1. Refer to the web page for information: http://www.endress.com/support/return-material
    Select the region.

  2. Return the device if repairs or a factory calibration are required, or if the wrong device was ordered or delivered.

11.4 Disposal

If required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal  waste. Do not dispose of products bearing this marking as unsorted municipal waste. Instead, return them to the manufacturer for disposal under the applicable conditions.

Accessories

12.1 Device-specific accessories
12.1.1 Protective cover for single compartment housing, aluminum or 316L

  • Material: plastic
  • Order number: 71438291

Endress Hauser Liquiphant FTL41 Point Level Switch - electronic
insert1

12.1.2 Plug-in jack
The plug-in jacks listed are suitable for use in the temperature range –25 to +70 °C (–13 to +158 °F).
Plug-in jack M12 IP69

  • Terminated at one end
  • Elbowed 90 °
  • 5 m (16 ft) PVC cable (orange)
  • Slotted nut 316L (1.4435)
  • Body: PVC (orange)
  • Order number: 52024216

Endress Hauser Liquiphant FTL41 Point Level Switch - electronic
insert2

Plug-in jack M12 IP67

  • Elbowed 90 °
  • 5 m (16 ft) PVC cable (gray)
  • Slotted nut Cu Sn/Ni
  • Body: PUR (black)
  • Order number: 52010285

Endress Hauser Liquiphant FTL41 Point Level Switch -
Plug

12.2 Sliding sleeves for unpressurized operation
Not suitable for use in explosive atmospheres.
Switch point, infinitely adjustable.Endress Hauser Liquiphant FTL41 Point
Level Switch - Switch point

G 1, DIN ISO 228/I

  • Material: 1.4435 (AISI 316L)
  • Weight: 0.21 kg (0.46 lb)
  • Order number: 52003978
  • Order number: 52011888, approval: with inspection certificate EN 10204 – 3.1 material

NPT 1, ASME B 1.20.1

  • Material: 1.4435 (AISI 316L)
  • Weight: 0.21 kg (0.46 lb)
  • Order number: 52003979
  • Order number: 52011889, approval: with inspection certificate EN 10204 – 3.1 material

G 1½, DIN ISO 228/I

  • Material: 1.4435 (AISI 316L)
  • Weight: 0.54 kg (1.19 lb)
  • Order number: 52003980
  • Order number: 52011890, approval: with inspection certificate EN 10204 – 3.1 material

NPT 1½, ASME B 1.20.1

  • Material: 1.4435 (AISI 316L)

  • Weight: 0.54 kg (1.19 lb)

  • Order number: 52003981

  • Order number: 52011891, approval: with inspection certificate EN 10204 – 3.1 material
     More detailed information and documentation are available:

  • Product Configurator on the Endress+Hauser website www.endress.com

  • Endress+Hauser sales organization www.addresses.endress.com

12.3 High pressure sliding sleeves

  • Switch point, infinitely adjustable
  • Use in explosive atmospheres
  • Seal package made of graphite
  • Graphite seal available as spare part 71078875
  • For G 1, G 1½: seal is included in the delivery

Endress Hauser Liquiphant FTL41 Point Level Switch - sliding
sleeves

G 1, DIN ISO 228/I

  • Material: 1.4435 (AISI 316L)
  • Weight: 1.13 kg (2.49 lb)
  • Order number: 52003663
  • Order number: 52011880, approval: with inspection certificate EN 10204 – 3.1 material

G 1, DIN ISO 228/I

  • Material: AlloyC22
  • Weight: 1.13 kg (2.49 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118691

G 1, DIN ISO 228/I

  • Material: AlloyC22
  • Weight: 1.13 kg (2.49 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118691

NPT 1, ASME B 1.20.1

  • Material: AlloyC22
  • Weight: 1.13 kg (2.49 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118694

NPT 1, ASME B 1.20.1

  • Material: AlloyC22
  • Weight: 1.13 kg (2.49 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118694

G 1½, DIN ISO 228/1

  • Material: AlloyC22
  • Weight: 1.32 kg (2.91 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118693

NPT 1½, ASME B 1.20.1

  • Material: 1.4435 (AISI 316L)
  • Weight: 1.32 kg (2.91 lb)
  • Order number: 52003669
  • Order number: 52011883, approval: with inspection certificate EN 10204 – 3.1 material

NPT 1½, ASME B 1.20.1

  • Material: AlloyC22
  • Weight: 1.32 kg (2.91 lb)
  • Approval: with inspection certificate EN 10204 – 3.1 material
  • Order number: 71118695

More detailed information and documentation are available:

  • Product Configurator on the Endress+Hauser website www.endress.com
  • Endress+Hauser sales organization www.addresses.endress.com

Technical data

13.1 Input
13.1.1 Measured variable
Level (point level), MAX or MIN safety
13.1.2 Measuring range
Depends on the installation location and the pipe extension ordered Maximum sensor length 6 m (20 ft)
13.2 Output
13.2.1 Output and input variants
Electronic inserts
3-wire DC-PNP (FEL42)

  • Three-wire direct current version
  • Switches the load via the transistor (PNP) and separate connection, e.g. in conjunction with programmable logic controllers (PLC)

Universal current connection, relay output (FEL44)
Switches the loads via 2 potential-free changeover contacts
2-wire NAMUR > 2.2 mA/< 1.0 mA (FEL48)

  • For separate switching unit
  • Signal transmission H-L edge 2.2 to 3.8 mA / 0.4 to 1.0 mA as per IEC 60947-5-6 (NAMUR) on two-wire cabling

13.2.2 Output signal
Switch output
Preset switching delay times for the point level switches can be ordered for the following areas:

  • 0.5 s when the tuning fork is covered and 1.0 s when it is uncovered (factory setting)
  • 0.25 s when the tuning fork is covered and 0.25 s when it is uncovered (fastest configuration)
  • 1.5 s when the tuning fork is covered and 1.5 s when it is uncovered
  • 5.0 s when the tuning fork is covered and 5.0 s when it is uncovered

13.2.3 Ex connection data
See safety instructions (XA): All data relating to explosion protection are provided in separate Ex documentation and are available from the Downloads Area of the Endress+Hauser-website. The Ex documentation is  supplied as standard with all Ex devices.
13.3 Environment
13.3.1 Ambient temperature range
–40 to +70 °C (–40 to +158 °F)
The minimum permitted ambient temperature of the plastic housing is limited to –20 °C (–4 °F); ‘indoor use’ applies for North America.Endress Hauser
Liquiphant FTL41 Point Level Switch - sliding sleeves1

If operating outdoors in strong sunlight:

  • Mount the device in a shaded location
  • Avoid direct sunlight, particularly in warmer climatic regions
  • Use a weather protection cover, can be ordered as an accessory

Hazardous area
In the hazardous area, the permitted ambient temperature can be limited depending on the zones and gas groups. Pay attention to the information in the Ex documentation (XA).
13.3.2 Storage temperature
–40 to +80 °C (–40 to +176 °F)
13.3.3 Humidity
Operation up to 100 %. Do not open in a condensing atmosphere.
13.3.4 Operating altitude
As per IEC 61010-1 Ed.3:

  • Up to 2 000 m (6 600 ft) above sea level
  • Can be extended to 3 000 m (9 800 ft) above sea level if overvoltage protection is used

13.3.5 Climate class
As per IEC 60068-2-38 test Z/AD
13.3.6 Degree of protection
In accordance with DIN EN 60529, NEMA 250
IP66/IP68 NEMA 4X/6P
Types of housing:

  • Single compartment; plastic
  • Single compartment; aluminum, coated
  • Single compartment; aluminum, coated; Ex d/XP

If the “M12 plug” option is selected as the electrical connection, IP66/67 NEMA TYPE 4X applies for all housing types.
Ordering information: Select the required option in the order code for “Electrical connection”. Exclusion criteria are taken into account automatically.

13.3.7 Vibration resistance
As per IEC60068-2-64-2008
a(RMS) = 50 m/s2 , f = 5 to 2 000 Hz , t = 3 axes x 2 h
13.3.8 Shock resistance
In accordance with IEC60068-2-27-2008: 300 m/s² [= 30 gn] + 18 ms
gn: standard acceleration of gravity
13.3.9 Mechanical load
Support the device in the event of severe dynamic load. Maximum lateral loading capacity of the pipe extensions and sensors: 75 Nm (55 lbf ft).
For more details, see the “Supporting the device” section.

13.3.10 Electromagnetic compatibility

  • Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation EMC (NE21).
  • The requirements of EN 61326-3-1 are fulfilled.

13.4 Process
13.4.1 Process temperature range
–40 to +150 °C (–40 to +302 °F)
Observe pressure and temperature dependency, see the “Process pressure range of the sensors” section.
13.4.2 Thermal shock
≤ 120 K/s
13.4.3 Process pressure range
WARNING
The maximum pressure for the device depends on the lowest-rated element, with regard to pressure, of the selected component. This means that it is necessary to pay attention to the process connection as well as the sensor.

  • For pressure specifications, see the “Mechanical construction” section.
  • Only operate the device within the specified limits!
  • The Pressure Equipment Directive (2014/68/EU) uses the abbreviation “PS”. The abbreviation “PS” corresponds to the MWP (maximum working pressure) of the device.

Refer to the following standards for the permitted pressure values of the flanges at higher temperatures:

  • PR EN 1092-1: With regard to its stability-temperature property, the material 1.4435 is identical to 1.4404, which is classed as 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
  • ASME B 16.5
  • JIS B 2220

In each case, the lowest value from the derating curves of the device and the selected flange applies. Canadian CRN approval: more details about the maximum pressure values are available in the download area of the product page under: www.endress.com→ Downloads.

Process pressure range of the sensors

Endress Hauser Liquiphant FTL41 Point Level Switch -
sensors

PN: 40 bar (580 psi)
13.4.4 Test pressure
PN = 40 bar (580 psi): test pressure = 1.5 · PN maximum 60 bar (870 psi) depending on the selected process connection
The device function is limited during the pressure test.
Mechanical integrity is guaranteed up to 1.5 times the process nominal pressure PN.
13.4.5 Density
Liquids with density > 0.7 g/cm3
Switch position >  0.7 g/cm 3 (as-delivered state)
Liquids with density 0.5 g/cm3
Switch position >  0.5 g/cm3 (can be set via DIP switch)
Optionally available: liquids with density > 0.4 g/cm 3

  • Optionally available, not suitable for SIL applications
  • Fixed value that cannot be edited.
    The function of the DIP switch is interrupted.

13.4.6 Viscosity
≤ 10 000 mPa⋅s
13.4.7 Pressure tightness
Up to vacuum
In vacuum evaporation plants, select the 0.4 g/cm3  density setting.
13.4.8 Solids contents
⌀ ≤ 5 mm (0.2 in)
13.5 Additional technical data
Technical Information TI01402F.
Current Technical Information: Endress+Hauser website: www.endress.com → Downloads.

Endress Hauser - logowww.addresses.endress.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Endress Hauser User Manuals

Related Manuals