Goodman Q104SD Series R410A Single Package Heat Pump Single Phase User Manual
- June 12, 2024
- Goodman
Table of Contents
Goodman Q104SD Series R410A Single Package Heat Pump Single Phase
IMPORTANT ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This
includes being able to install the product according to strict safety
guidelines and instructing the customer on how to operate and maintain the
equipment for the life of the product. Safety should always be the deciding
factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the furnace or failure to
follow safety warnings could result in serious injury, death, or property
damage.
These instructions are primarily intended to assist qualified individuals
experienced in the proper installation of this appliance. Some local codes
require licensed installation/service personnel for this type of equipment.
Please read all instructions carefully before starting the installation.
Return these instructions to the customer’s package for future reference. DO
NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE.
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment. Pay attention to
all safety warnings and any other special notes highlighted in the manual.
Safety markings are used frequently throughout this manual to designate a
degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that if not avoided,
could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that if not avoided,
may result in minor or moderate injury or property damage.
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort-control appliance that will
heat and cool your home year round and provide energy saving comfort. It’s an
unknown fact that heat is always in the air, even when the outside temperature
is below freezing. The heat pump uses this basic law of physics to provide
energy saving heat during the winter months. For example, If the outdoor
temperature is 47° F (8° C), your heat pump can deliver approximately 3.5
units of heat energy per each unit of electrical energy used, as compared to a
maximum of only 1 unit of heat energy produced with conventional heating
systems. In colder temperatures, the heat pump performs like an air
conditioner run in reverse. Available heat energy outside the home is absorbed
by the refrigerant and exhausted inside the home. This efficient process means
you only pay for “moving” the heat from the outdoors to the indoor area. You
do not pay to generate the heat, as is the case
with more traditional furnace designs. During summer, the heat pump reverses
the flow of the heat-absorbing refrigerant to become an energy-efficient,
central air conditioner. Excess heat energy inside the home is absorbed by the
refrigerant and exhausted outside the home.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s User manual for detailed
programming instructions.
Cooling Operation
- Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1.
- Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE : If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Heating Operation
- Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
- Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE : If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat
Some thermostats may include a system mode called EM HT or AUX HT, etc. This
is a back-up heating mode that should only be used if a problem is suspected.
With the mode set to EM HT, etc., the compressor and outdoor fan will be
locked off and supplemental heat (electric resistance heating) will be used as
a source of heat. Sustained use of electric resistance heat in place of the
heat pump will result in an increase in electric utility costs.
Defrost Operation
During cold weather heating operation, the outdoor unit will develop a coating
of snow and ice on the heat transfer coil. This is normal and the unit will
defrost itself. This unit features Demand Defrost that monitors ambient and
coil temperatures to regulate the defrost function accordingly. At the
beginning of the defrost cycle, both the outdoor condenser fan and compressor
will turn off. After approximately 30 seconds, the compressor will turn on and
begin to heat the outdoor coil causing the ice and snow to melt.
NOTE : While the ice and snow is melting, some steam may rise from the
outdoor unit as the warm coil causes the melting frost to evaporate. When
defrost is completed, the outdoor fan motor will start, and the compressor
will turn off again. In approximately 30 seconds the compressor will start up
again and continue normal operation.
Operating the Heat Pump for Automatic
Cooling and Heating
-
Set the thermostat system mode to AUTO and the thermostat fan mode to AUTO. See Figure 1.
NOTE : Thermostat styles vary. Some models will not include the AUTO mode and others will have the AUTO in place of the HEAT and COOL. Others may include all three. Refer to the instructions supplied with your thermostat for specific instructions. -
Set the thermostat’s temperature selector to the desired heating and cooling temperature level(s). The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fireplace operation. Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO. The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
Shutting the Heat Pump Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO. See
Figure 1. NOTE: The system will not operate, regardless of the temperature
selector setting.
HEAT PUMP MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance or
service on the system. Failure to comply may result in personal injury or
death. Proper maintenance is most important to achieve the best performance
from the appliance and should be performed by a qualified service technician
at least once a year. Follow the maintenance schedule and the instructions
below for years of safe, trouble free operation.
Regular Cleaning
- Clean or replace the indoor air filter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air filter.
- Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fins.
- Check for obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
- The thermostat is properly set. See Cooling Operation for air conditioning or Heating Operation for furnace or air handler.
- The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
WARRANTY INFORMATION
A warranty certificate with full details is included with the heat pump. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specific examples of service calls which are not included in the limited warranty are:
- Correcting wiring problems in the electrical circuit supplying the heat pump.
- Resetting circuit breakers or other switches.
- Adjusting or calibrating of thermostat.
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a
degree or level of seriousness and should not be ignored. WARNING indicates a
potentially hazardous situation that if not avoided, could result in personal
injury or death. CAUTION indicates a potentially hazardous situation that if
not avoided, may result in minor or moderate injury or property damage.
WARNING:
Improper installation, service, adjustment, or maintenance may cause explosion, fire, electrical shock or other hazardous conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, only factory authorized kits or accessories may be used with this product.
CAUTION:
This unit uses refrigerant R-410A. DO NOT use any other refrigerant in this
unit. Use of another refrigerant will damage the unit.
WARNING:
Shut off all electrical power to the unit before performing any maintenance or
service on the system. Failure to comply may result in personal injury or
death.
WARNING:
These units are fully charged with R-410A refrigerant and ready for
installation. When a system is installed according to these instructions, no
refrigerant charging is required. If repairs make it necessary for evacuation
and charging, it should only be attempted by qualified, trained personnel
thoroughly familiar with this equipment. Some local codes require licensed
installation service personnel to service this type of equipment. Under no
circumstances should the homeowner attempt to install and/or service this
equipment. Failure to comply with this warning could result in equipment
damage, personal injury, or death.
WARNING:
Do not place combustible material on or against the unit cabinet. Do not place
combustible materials, including gasoline and any other flammable vapors and
liquids, in the vicinity of the unit.
WARNING:
The safety information listed below must be followed during the installation,
service, and operation of this unit. Unqualified individuals should not
attempt to interpret these instructions or install this equipment. Failure to
follow safety recommendations could result in possible damage to the
equipment, serious personal injury or death.
- The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
- This equipment contains liquid and gaseous refrigerant under high pressure. Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment.
- All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
- Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fire extinguisher, etc.) when performing brazing operations.
- Install this unit only in a location and position as specified on page 6. This unit is designed only for outdoor installations and should be located with consideration of minimizing the length of the supply and return ducts. Consideration should also be given to the accessibility of fuel, electric power, service access, noise, and shade.
- Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
GENERAL INFORMATION
The Q104SD series heat pump is designed only for outdoor rooftop or ground
level installations. This unit has been tested for capacity and efficiency in
accordance with AHRI Standards and will provide many years of safe and
dependable comfort, providing it is properly installed and maintained. Abuse,
improper use, and/or improper maintenance can shorten the life of the
appliance and create unsafe hazards.
Before you install this unit
- The cooling load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
- Check the electrical supply and verify the power supply is adequate for unit operation. If there is any question concerning the power supply, contact the local power company.
- All units are securely packed at the time of shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fins are straight. If necessary, comb fins to remove flattened or bent fins. Claims for damage (apparent or concealed) should be filed immediately with the carrier.
- Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.
Locating the Heat Pump
- Survey the job site to determine the best location for mounting the outdoor unit.
- Choose an appropriate location that minimizes the length of the supply and return air ducts.
- Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided.
- Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 2 for minimum clearances to obstructions.
Field Connections for Electrical Power Supply
- All wiring must comply with current provisions of the National Electrical Code (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
- The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
- Electrical power supplied to the unit must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes.
Air Ducts
This unit is designed only for use with a supply and return duct. Air ducts
must be installed in accordance with the standards of the National Fire
Protection Association Standard for Installation of Air Conditioning Systems
(NFPA 90A), Standard for Installation of Residence Type.
Warm Air Heating and Air Conditioning Systems (NFPA90B), and all applicable local codes. NFPA publications are avaialable by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web.
- Design the duct work according to methods described by the Air Conditioning Contractors of America (ACCA).
- The ducts must be properly sized not to exceed .2” W.C. pressure drop at 400 scfm per nominal ton of cooling capacity.
- Duct work should be attached directly to the unit flanges for horizontal applications.
- If roof curb is installed, the ducts must be attached to the curb hangers, not the unit.
Unconditioned Spaces
All duct work passing through unconditioned space must be properly insulated
to minimize duct losses and prevent condensation. Use insulation with an outer
vapor barrier. Refer to local codes for insulation material requirements.
Acoustical Duct Work
Certain installations may require the use of acoustical lining inside the
supply duct work.
- Acoustical insulation must be in accordance with the current revision of the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) application standard for duct liners.
- Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC-25/50 or less.
- Fiber duct work may be used in place of internal duct liners if the fiber duct work is in accordance with the current revision of the SMACNA construction standard on fibrous glass ducts. Fibrous duct work and internal acoustical lining must be NFPA Class 1 air ducts when tested per UL Standard 181 for Class 1 ducts.
Air Filter Requirements
WARNING :
Never operate the unit without a filter in place. Dust and lint could
accumulate on internal parts, resulting in loss of efficiency, equipment
damage, and possible fire.
NOTE TO INSTALLER: After installing or replacing the filtration system for this unit, add the following statement on or adjacent to the filter service panel: “Replace filter(s) installed in your system only with the same dimensional size filters that are being replaced.”
- An air filter is not supplied with this package unit as shipped from the factory. The installer must provide a high velocity filter that is appropriately sized to the return air duct opening or internal filter rack. The filters must comply with ANSI/UL 900 or CAN/ULC-S111.
- Horizontal installations require the air filter system be installed in the return air ductwork.
- For recommended external filter sizes, refer to Table 2 (page 12) under Heat Pump Maintenance
- All return air must pass through the filters before entering the evaporator coil. It is important that all filters be kept clean and replaced frequently to ensure proper operation of unit. Dirty or clogged filters will reduce the efficiency of the unit and result in unit shutdowns.
- Air filter pressure drop is recommended not to exceed 0.08 inches WC.
- Single phase downflow applications require either a Nortek internal filter kit be used, or an air filter system be installed in the return air ductwork. See Table 2 for specific unit model and filter sizes.
- Horizontal installations require the air filter system be installed in the return air ductwork.
HEAT PUMP INSTALLATION
Packaging Removal
Remove the shipping carton and User’s Manual from the equipment. Take care not
to damage the tubing connections when removing the carton. For rooftop
installations, remove and discard the two supports attached beneath the unit.
Rigging & Hoisting
WARNING:
To avoid the risk of property damage, personal injury, or death, it is the
rigger’s responsibility to ensure that whatever means are used to hoist the
unit are safe and adequate:
- The lifting equipment must be adequate for the load. Refer to Table 3 (page 13) for unit weights.
- The unit must be lifted from the holes in the base rails using cables or chains.
- Spreader bars are required to protect the unit and ensure even loading.
- Keep the unit in an upright position at all times. The rigging must be located outside the units center of gravity. Refer to Figure 7 (page 13) for locating the center of gravity.
- All panels must be securely in place during rigging and hoisting.
Minimum Clearances
Q104SD units are certified as combination heating and cooling equipment for
outdoor installation only. Figure 2 (page 6) displays the minimum clearances
to obstructions for both downflow and horizontal discharge. Units may be
installed on wood flooring or on Class A, B, or C roof covering material when
used with bottom supply and return air ducts as long as the following
requirements are met:
- If using horizontal supply and return air ducts, the horizontal roof curb kit and return air kit must be installed prior to unit installation. Horizontal roof curb is required.
- If using bottom discharge with return air ducts a roof curb must be installed prior to unit installation. See Rigging and Hoisting section for setting of the unit.
Ground Level
Ground level installations must be located according to local building codes
or ordinances and these requirements:
- Clearances must be in accordance with those shown in Figure 2. Also consider clearances for access to the internal filter.
- A suitable mounting pad must be provided and separate from the building foundation. The pad must be level to ensure proper condensate disposal and strong enough to support the unit’s weight. The slab height must be a minimum of 2” (5cm) above grade and with adequate drainage. See Figure 3.
- Units require horizontal roof curb and return air kit for horizontal installations.
- Ductwork should be attached directly to flanges on panels supplied in horizontal duct conversion kits.
Rooftop
Rooftop installations must be located according to local building codes or
ordinances and these requirements:
- The roof must be capable of handling the weight of the unit. For unit weights, see Table 3 (page 13).
Reinforce the roof if necessary.
- The appropriate accessory roof curb (Figure 4) must be installed prior to unit installation. The roof curb must be square and level to ensure proper condensate drainage. Please follow all instructions provided with the kit.
- Secure roof curb or frame to roof using acceptable mechanical methods per local codes. NOTE: Make sure the two supports beneath the unit have been removed.
Horizontal to Downflow Conversion
If down flow ducts are required, the unit must be converted following the
steps below for the supply and return ducts.
1. Locate the duct cap inside the duct openings and remove
the screw holding it in place.
2. Lift the cap out of the unit. (Hint: The cap can be pushed
up from the bottom by reaching through the fork slot).
3. Cover the horizontal duct opening with the horizontal
duct cap. The insulation will be on the indoor side.
4. Fasten the cover with screws to seal.
Condensate Drain
Condensate is removed from the unit through the 3/4” female pipe fitting
located on the front side of the unit. Install a 2 inch condensate trap in the
drain line of the same size and prime with water. See Figure 5. When
connecting rigid drain line, hold the female fitting with a wrench to prevent
twisting. Do not over tighten! Refer to local codes and restrictions for
proper condensate disposal requirements.
ELECTRICAL WIRING
WARNING :
To avoid risk of electrical shock, personal injury, or death, disconnect all
electrical power to the unit before performing any maintenance or service. The
unit may have more than one electrical supply. Label all wires prior to
disconnection when servicing the unit. Wiring errors can cause improper and
dangerous operation
- Electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
- For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist:
- Verify that the voltage, frequency, and phase of the supply source match the specifications on the unit rating plate.
- Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. refer to the unit wiring label for proper high and low voltage wiring.
- Verify factory wiring is in accordance with the unit wiring diagram. See Figure 9 (page 15). Inspect for loose connections.
Line Voltage
- A wiring diagram is located on the inside cover of the units electrical box. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.
- An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the unit.
- Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
- The outdoor unit requires both power and control circuit electrical connections. Refer to Figure 8 (page 14) for identification and location of outdoor unit field wiring interfaces. Make all electrical connections in accordance with all applicable codes and ordinances.
- Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.
- Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
- Use only copper wire for the line voltage power supply to this unit. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
- Units are shipped from the factory wired for 240 volt operation. For 208V operation remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V.
- Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or unbroken electrical ground to
minimize personal injury if an electrical fault should occur. Do not use gas
piping as an electrical ground! This unit must be electrically grounded in
accordance with local codes or, in the absence of local codes, with the
National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Use
the grounding lug provided in the control box for grounding the unit.
Blower Speed
The blower speed is preset (for operation) at the factory for heating and
cooling. These factory settings are listed in Table 8 (page 19). For optimum
system performance and comfort, it may be necessary to change the factory set
speed.
Safety Protection
- A high-pressure switch is factory-installed and located in the compressor discharge line of the unit. The switch is designed to de-energize the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the discharge pressure rises above 650 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the liquid pressure decreases to 460 psig. Please note that the switch interrupts the thermostat inputs to the unit. When the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
- A low-pressure switch is factory installed and located on the suction line of the unit. The switch is designed to protect the compressor from a loss of charge by interrupting the thermostat inputs to the unit. If the suction pressure falls below 20 psig, the switch will open and de-energize the unit. The switch will close again when the suction pressure increases above 35 psig. When the switch opens and then closes, there is a 5 minute short cycling delay before the outdoor unit will energize. Under normal conditions the switch is closed.
CAUTION:
To avoid personal injury or property damage, make sure the motor leads do not
come into contact with any uninsulated metal components of the unit.
- Shut off all electrical power to the unit and remove the blower panel. Locate the orange and red wires terminated to the blower motor. NOTE: The orange wire controls cooling operation while the red wire controls heating operation.
- Verify the required speed from the airflow data found in Table 8 (page 19). Place appropriate wire on the correct motor speed tap for the required airflow point. Thermostat Connections
- This heat pump may require a 2-stage cooling / heating thermostat if used in conjunction with certain installed accessories. Refer to your manual for additional instructions.
- The low voltage wires must be properly connected to the units low voltage terminal block as shown in Figure 8 (page 14).
- The L terminal on the defrost control board is used for fault monitoring. This is a 24V output and may be used with compatible thermostats. Refer to the thermostat manufacturer’s manual to ensure compatibility. FAILURE TO ENSURE COMPATIBILITY CAN LEAD TO THERMOSTAT FAILURE.
- The thermostat should be mounted about 5 feet above the floor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces, sunlight, or lighting fixtures, and convective heat from warm air registers or electrical appliances. Refer to the thermostat’s instruction sheet for detailed mounting and installation information.
Ambient Sensor Mounting
For optimum performance of the heat pump system, the ambient sensor must be
mounted on the outside of the unit. See Figure 6 (page 10).
- Remove the mounting bracket wire tied to the control bracket and all hardware included in the packet.
- Remove star bushing from 7/8” hole in corner panel of the unit. See Figure 6.
- Route the ambient sensor through the 7/8” hole in the corner panel of the unit, and then through the 7/8” hole in the mounting bracket.
- Route the sensor through the star bushing. Use the star bushing to secure the mounting bracket to the unit.
- Secure the ambient sensor inside the plastic clip and secure it to the mounting bracket with the screw and nut provided.
- Install one spacer nut between the plastic clip and mounting bracket.
- Bend the mounting bracket into position and screw the mounting bracket to the corner panel.
Defrost Board Operation
- Heat Pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle. The outdoor coil temperature must be at or below 25.5°F before the defrost cycle begins.
- There must be a minimum of 35 minutes between defrost cycles. After this time, coil temperature & outdoor ambient will drive a call for defrost after conditions are met continuously for 30 seconds before a defrost cycle is initiated.
- Outdoor fan is off during defrost operation.
- The defrost cycle ends when the outdoor temperature reaches 50°F-80°F, dependent on TERM TEMP jumper position (default 70°F-no jumper) or if the defrost terminate time of 11 minutes is reached. See “Control Board Status Indicators” for operation and fault codes, Table 4 (page 19).
Forced Defrost When the Following Conditions are Met:
- LPS and HPS are closed
- Y1 input is active
- O input is either active or inactive
- TEST terminals shorted for more than three seconds
Compressor will start and unit will operate in DEFROST mode. Unit will run in
DEFROST mode after pins have been shorted at least 3 seconds regardless of
whether short
is removed or not. Qualifying conditions of minimum ambient or coil
temperature do not need to be met when the unit is forced into defrost. If the
short across the TEST pins exist, the unit will stay in DEFROST as long as the
short remains or until the TERMINATE TIME is reached (11 minutes). This will
happen regardless of coil temperature. W2 OUT is active during this time if
the O input is inactive. If after 11 minutes the short remains, the unit shall
not run in any mode and the display shall flash ‘DF’ until the short is
removed. W2 OUT shall remain on during the whole time that the short exists,
if the O input is inactive.
Crankcase Heater (CCH) Operation
The outdoor temperature is measured by the ambient temperature sensor. The CCH
is enabled during first 2 minutes after board power up regardless of any other
condition.
- The CCH is disabled during compressor operation.
- The CCH is disabled when OD temperature > 70F.
- The CCH is enabled when OD temperature < 71F.
Optional Outdoor Thermostat (Field Supplied)
An outdoor thermostat can be installed in the field with 2-stage electric heat
by removing the orange wire from the W2 terminal on the unit terminal block
and re-connecting it to the outdoor thermostat. Connect the other side of the
outdoor thermostat to W2 on the unit terminal block..
Optional Electric Heater Kits
Optional electric heater kits are available in 5 kw through 20 kw heating
capacities. Single package heat pumps are designed to allow optional electric
heat to be field installed as required by the building’s particular heating
load. The options available for each unit are shown in the heater kit
installation instructions. A heating/cooling 24V thermostat should be used
when an electric heater kit is installed. NOTE: A 2-stage heating thermostat
is required if installing a 2-stage heater kit. As previously noted, a field
installed circuit breaker kit is available as a means of electrical disconnect
for the unit. Install the heater kits as directed by the instructions supplied
with the heater kit. Follow all cautions and warnings as directed.
START UP & ADJUSTMENTS
Pre-Start Check List
- Verify the unit is level and allows condensate to drain.
- Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/ control panels are in place.
- Verify that the duct work is sealed to prevent air leakage.
- Verify that the line voltage power leads are securely connected and the unit is properly grounded.
- Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip.
- Verify that the outdoor fan turns freely.
- Verify that the power supply branch circuit overcurrent protection is sized properly.
- Verify that the thermostat is wired correctly. The thermostat system mode should be set to OFF and the thermostat fan mode should be set to AUTO.
Start-Up Procedure
Close all electrical disconnects to energize the system.
CAUTION:
If the unit is equipped with a crankcase heater, allow 24 hours prior to
continuing the start up procedures to allow for heating of the refrigerant
compressor crankcase. Failure to comply may result in damage and could cause
premature failure of the system. This warning should be followed at initial
start up and any time the power has been removed for 12 hours or longer.
Air Circulation
Leave the thermostat system mode on OFF, and set the fan mode to ON. Blower
should run continuously. Check the air delivery at the supply registers and
adjust register openings for balanced air distribution. Examine ductwork for
leaks or obstruction if insufficient air is detected. Set the thermostat fan
mode to AUTO. The blower should stop running.
Short Cycle Protection
- With the system operating in cooling mode, note the temperature setting of the thermostat and gradually raise the set-point temperature until the unit de-energizes.
- Immediately lower the set point temperature of the thermostat to its original setting and verify that the indoor blower is energized.
- After approximately 5 minutes, verify the compressor and fan energize and the temperature of the discharge air is cooler than the room temperature.
System Cooling
- Set the thermostat’s system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize.
- Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
- Allow the cooling system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower should also stop unless fan mode is set to ON.
System Heating – Heat Pump Mode
- Set the thermostat’s system mode to HEAT and the fan mode to AUTO. Gradually raise the thermostat temperature setpoint above room temperature and verify the compressor, outdoor fan, and indoor blower energize.
- Feel the air being circulated by the indoor blower and verify it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary
System Heating – Electric Heat Mode (If Equipped-Optional)
- Set the thermostat’s system mode to EMER. HEAT and the fan mode to AUTO. Gradually raise the thermostat temperature setpoint above room temperature and verify the compressor and outdoor fan remain off, but that the blower and heaters are energized.
- Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
REFRIGERANT CHARGING
WARNING:
Single Packaged Heat Pumps are shipped fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death. The system refrigerant charge can be checked and adjusted through the service ports provided at the front panel. Use only gauge lines which have a Schrader depression device present to actuate the valve. Draw a vacuum on gauge lines to remove air before attaching them to the service ports on the unit.
IMPORTANT NOTES:
- To achieve rated capacity and efficiency the compressor must be exposed to refrigerant for at least 24 hours prior to running and then must be run for a minimum of 12 hours.
- The refrigerant cooling charging charts are applicable to units at rated factory airflows for the indoor coil. See Figure 10, Figure 11 (page 16), Figure 12, Figure 13 (page 17), Figure 14, Figure 15 (page 18).
Charging an R-410A Unit in AC Mode
(With Outdoor Temperatures Above 60° F)
- With the system operating at steady-state, measure the liquid refrigerant pressure in psig at the service valve. Measure the liquid refrigerant temperature in Fahrenheit on the liquid line before TXV at indoor coil.
- For the temperature measured, determine the required liquid refrigerant pressure from the appropriate charging charts in Figure 10, Figure 11 (page 16), Figure 12, Figure 13 (page 17), Figure 14, Figure 15 (page 18).
- If the pressure measured in step 1 is greater than the required liquid refrigerant pressure determined in step 4, then there is too much charge in the system. Remove refrigerant and repeat steps 1 through 3 until the system is correctly charged.
- If the pressure measured in step 1 is less than the required liquid refrigerant pressure determined in step 4, then there is too little charge in the system. Add refrigerant and repeat steps 1 through 3 until the system is correctly charged.
Charging an R-410A Unit in Heating Mode
Use the steps below for proper charging of unit in heat mode:
- Evacuate the refrigerant system.
- Weigh in the proper charge as shown on the unit rating plate (during heating mode operation).
- Verify the unit is operating properly according to the System Heating-Heat Pump Mode section on page 11. Verification of Charge in Refrigerant Heating Mode
- Block off half of the outdoor fan discharge grille area as shown.
- With the unit in COOLING MODE, use the appropriate charging chart curves shown in Tables 10-15 as a guide to ensure proper operation of your system.
- For units with a TXV, the refrigerant system should be evacuated and the proper charge weighed in as shown on the unit rating plate.
- Return to the system when the outdoor temperature is 60 degrees F or higher and follow the steps defined in Charging an R410A Unit in AC Mode.
NOTE : Unit charge MUST be verified in cooling season.
HEAT PUMP MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or death, disconnect all
electrical power to the unit before performing any maintenance or service.
Unit may have more than one electrical supply.
CAUTION:
Use care when servicing the heat pump or removing components. Personal injury
can result from sharp edges present in equipment constructed with sheet metal
Proper maintenance is important to achieve optimum performance from the heat
pump. The ability to properly perform maintenance on this equipment requires
certain mechanical skills and tools. If you do not possess these skills,
contact your dealer for maintenance. Consult your local dealer about the
availability of maintenance contracts. Routine maintenance should include the
following:
- Inspect and clean or replace air filters at the beginning of each heating and cooling season, or more frequently if required.
- Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
- Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
CAUTION:
The unit should never be operated without a filter in the return air system.
Replace disposable filters with the same type and size.
RECOMMENDED EXTERNAL FILTER SIZES
Nominal Cooling (Tonnage)| Filter Size (in. x in.)| Approximate Air Flow Range
(CFM)| Approximate Filter Area (sq. in.)*
2.0| 20 x 25| 600-900| 480
2.5| 25 x 25| 750-1125| 600
3.0| 25 x 25| 900-1350| 600
3.5| 20 x 25 (2 required)| 1050-1575| 960
4.0| 20 x 25 (2 required)| 1200-1700| 960
5.0| 20 x 25 (2 required)| 1500-2000| 960
Based on velocity of 300ft/min for disposable filters.
Table 1. Recommended External Filter Sizes
The motors for the circulating air blower and the outdoor fan are pre-
lubricated at the factory. No further oiling is required for the life of this
product.
FIGURES & TABLES
Table 2. Center of Gravity & Unit Shipping Weights
MODEL NUMBER Q104SD-
| ****
UNIT WEIGHT
(WITH PACKAGING)
| ****
CENTER OF GRAVITY
| HEIGHT -C- (IN INCHES)
---|---|---|---
– A-| – B-| WITH BASE RAILS| WITHOUT BASE RAILS
X24K| 410| 28.0| 25.5| 39.0| 35.3
X30K| 410| 28.0| 26.0| 39.0| 35.3
X36K| 442| 28.0| 25.5| 39.0| 35.3
X42K| 507| 29.5| 26.0| 43.0| 39.3
X48K| 522| 29.5| 26.0| 43.0| 39.3
X60K| 530| 29.5| 26.0| 43.0| 39.3
Electrical Information
WIRING DIAGRAM
Charging Charts – Cooling
Airflow Data
MODEL NUMBER Q104SD-| ****
TAP
| EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
---|---|---
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
X24K
| Tap T1| 825| 38.4| 785| 40.3| 710| 44.4| 645| 48.9| 580| 54.5| 510| 62.0|
435| 72.5| –| –
Tap T2| 970| 32.6| 925| 34.2| 865| 36.5| 800| 39.5| 715| 44.1| 650| 48.5| 590|
53.5| 520| 60.5
Tap T3*| 1070| 29.6| 1010| 31.3| 9456| 33.4| 905| 34.9| 815| 38.8| 745| 42.5|
675| 46.9| 615| 51.2
Tap T4**| 1190| 26.6| 1140| 27.7| 1070| 29.6| 1020| 30.9| 955| 33.1| 860|
36.7| 805| 39.3| 765| 41.4
Tap T5| 1330| 23.8| 1275| 24.8| 1220| 25.9| 1165| 27.1| 1105| 28.6| 1045|
30.3| 955| 33.0| 880| 35.9
X30K
| Tap T1| 890| 35.5| 830| 38.0| 765| 41.3| 685| 46.0| 625| 50.6| 575| 54.9|
500| 62.9| 420| 75.4
Tap T2*| 970| 32.6| 925| 34.2| 865| 36.5| 800| 39.5| 715| 44.1| 650| 48.5|
590| 53.5| 520| 60.5
Tap T3**| 1190| 26.6| 1140| 27.7| 1070| 29.6| 1020| 30.9| 955| 33.1| 860|
36.7| 805| 39.3| 765| 41.4
Tap T4| 1380| 22.9| 1335| 23.7| 1275| 24.8| 1220| 25.9| 1165| 27.1| 1095|
28.8| 1020| 31.0| 945| 33.4
Tap T5| 1640| 19.3| 1605| 19.7| 1545| 20.4| 1490| 21.2| 1435| 22.0| 1380|
22.9| 1325| 23.9| 1250| 25.3
X36K
| Tap T1| 1135| 27.8| 1075| 29.4| 1010| 31.2| 950| 33.3| 865| 36.6| 770|
41.0| 695| 45.5| 620| 51.0
Tap T2*| 1240| 25.4| 1185| 26.6| 1130| 28.0| 1055| 29.9| 995| 31.8| 920|
34.3| 825| 38.2| 755| 41.9
Tap T3| 1420| 22.3| 1370| 23.1| 1310| 24.2| 1250| 25.3| 1205| 26.2| 1125|
28.1| 1065| 29.7| 975| 32.4
Tap T4| 1630| 19.4| 1590| 19.9| 1530| 20.7| 1465| 21.6| 1410| 22.4| 1345|
23.5| 1270| 24.9| 1195| 26.4
Tap T5| 1700| 18.6| 1660| 19.1| 1595| 19.8| 1535| 20.6| 1480| 21.3| 1420|
22.2| 1360| 23.3| 1280| 24.7
X42K
| Tap T1*| 1260| 25.1| 1200| 26.4| 1135| 27.9| 1070| 29.5| 980| 32.2| 905|
34.9| 830| 38.1| 760| 41.5
Tap T2| 1375| 23.0| 1330| 23.7| 1270| 24.9| 1220| 25.9| 1155| 27.4| 1075|
29.3| 970| 32.5| 900| 35.1
Tap T3| 1575| 20.1| 1520| 20.8| 1470| 21.5| 1420| 22.3| 1355| 23.3| 1295|
24.4| 1215| 26.0| 1095| 28.9
Tap T4| 1655| 19.1| 1600| 19.8| 1555| 20.3| 1500| 21.1| 1445| 21.9| 1380|
22.9| 1315| 24.0| 1215| 26.0
Tap T5| 1850| 17.1| 1795| 17.6| 1740| 18.2| 1710| 18.5| 1640| 19.3| 1595|
19.8| 1540| 20.5| 1475| 21.4
X48K
| Tap T1| 950| 33.2| 900| 35.1| 865| 36.6| 730| 43.4| 670| 47.0| 585| 54.2|
510| 62.2| –| –
Tap T2*| 1645| 19.2| 1595| 19.8| 1520| 20.8| 1475| 21.4| 1415| 22.3| 1350|
23.4| 1265| 25.0| 1200| 26.4
Tap T3| 1765| 17.9| 1705| 18.5| 1625| 19.4| 1570| 20.1| 1525| 20.7| 1450|
21.8| 1405| 22.5| 1305| 24.2
Tap T4| 1995| 15.8| 1945| 16.2| 1875| 16.8| 1790| 17.6| 1725| 18.3| 1660|
19.0| 1610| 19.6| 1550| 20.4
Tap T5| 2390| 13.2| 2335| 13.5| 2300| 13.7| 2240| 14.1| 2180| 14.5| 2130|
14.8| 2075| 15.2| 2015| 15.7
X60K
| Tap T1| 1090| 29.0| 1030| 30.6| 960| 33.0| 880| 36.0| 790| 40.0| 715| 44.2|
640| 49.3| 570| 55.4
Tap T2*| 1765| 17.9| 1705| 18.5| 1625| 19.4| 1570| 20.1| 1525| 20.7| 1450|
21.8| 1405| 22.5| 1305| 24.2
Tap T3| 2000| 15.8| 1945| 16.2| 1890| 16.7| 1835| 17.2| 1785| 17.7| 1735|
18.2| 1690| 18.7| 1635| 19.3
Tap T4| 2235| 14.1| 2180| 14.5| 2125| 14.9| 2075| 15.2| 2035| 15.5| 1985|
15.9| 1940| 16.3| 1895| 16.7
Tap T5| 2390| 13.2| 2335| 13.5| 2300| 13.7| 2240| 14.1| 2180| 14.5| 2130|
14.8| 2075| 15.2| 2015| 15.7
Notes:
- Denotes factory set cooling speed
- Denotes factory set electric heating speed
- Heat rise calculated based on 10KW of electric heat using formula (KW x 3413)/1.08/CFM
- Temperature rises in tables are approximate. Actual temperature rises may vary.
- Shaded areas are not approved for proper electric heat operation above 40F rise.
- Deduct approximately 3% from airflow shown for 208V applications.
Table 3. Q104SD Airflow Data
STATUS INDICATOR | STATUS TYPE | DIAGNOSTIC DESCRIPTION |
---|---|---|
C1 | Operating Status | Cooling, 1st Stage |
H1 | Operating Status | Heating, 1st Stage |
SC | Operating Status | Anti Short Cycle Timer |
dF | Operating Status | Defrost |
_. | Operating Status | Power on, no call for operation |
01 | Fault | Pressure Switch, low |
02 | Fault | Pressure Switch, high |
03 | Fault | Temperature Sensor, Ambient |
04 | Fault | Temperature Sensor, Coil |
05 | Fault | Board |
dF (flashing)
| ****
Input Error
| Forced defrost – test short applied longer than 11 minutes
Table 4. Control Board Status Indicators
INSTALLATION CHECKLIST
INSTALLATION ADDRESS:
CITY:| STATE:
UNIT MODEL #:
UNIT SERIAL #:
Unit Installed Minimum clearances per Figure 2 (page 6)| YES| NO
INSTALLER NAME:
CITY| STATE
Has the owner’s information been reviewed with the customer?| YES| NO
Has the Literature Package been left with the unit?| YES| NO
FILTER SYSTEM
Filter(s) secured in place?| YES| NO
Filter(s) clean?| YES| NO
PROPOSITION 65 WARNING:
WARNING : This product contains chemicals known to the state of
California to cause cancer.
WARNING : This product contains chemicals known to the state of
California to cause birth defects or other reproductive harm.
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period for crankcase heaters (if applicable)?| YES| NO
Stage-1 Liquid Pressure:
| HIGH SIDE:|
Stage-1 Suction Pressure:| LOW SIDE:|
ELECTRICAL SYSTEM
Electrical connections tight?| YES| NO
Line voltage polarity correct?| YES| NO
Rated Voltage:| VOLTS:|
L1-L2 Volts:| VOLTS:|
Has the thermostat been calibrated?| YES| NO
Is the thermostat level?| YES| NO
Is the heat anticipator setting correct?| YES| NO
REPLACEMENT PARTS
Replacement parts are available through your distributor. Please have the
complete model and serial number of the unit when ordering replacement parts.
ELECTRICAL:
- Ambient Sensor
- Contactors
- Capacitors
- Pressure Switches
- Coil Sensor
- Relays
- Compressors
- Transformers
MOTORS :
- Blower Motor
- Fan Motor
COMPONENTS:
- Blower Assembly
- Fan Grille
- Cabinet Panels
- Filter/Driers
- Expansion Valves
Specifications & illustrations subject to change without notice or incurring obligations (08/22). O’Fallon, MO, © Nortek Global HVAC LLC 2022. All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>