nVent Eriflex IBSBADV120-330 IBSB Advanced Insulated Braided Conductor Owner’s Manual

June 12, 2024
nVent ERIFLEX

nVent Eriflex logo IBSB ADVANCED INSULATED BRAIDED CONDUCTOR, 400 A, 1.26″ X 0.17″ X 12.99″nVent Eriflex IBSBADV120 330 IBSB Advanced Insulated
Braided Conductor Owner’s Manual

CATALOG NUMBER

IBSBADV120-330
IBS/IBSB Advanced Insulated Braided Conductor, Halogen Free is the ideal ready-to-install flexible wire replacement solution that is specifically designed for connections to all molded case circuit breakers, including the most compact breakers on the market. IBS/IBSB Advanced connects to the front access terminals of the breakers without any additional accessories, such as angular connectors, spreaders, ring terminal connectors or extenders. IBS/IBSB Advanced is available in cross sections of 25 to 240 mm² (49.34 to 273.65 kcmil), lengths from 230 to 1,030 mm (9.06″ to 40.55″), and 80 to 700 A.
Manufactured in an ISO 9001 certified automated facility, IBS/IBSB Advanced is formed by weaving high-quality electrolytic copper wire to form a durable low voltage connector with maximum flexibility which allows for more compact power connections to circuit breakers. The IBS/IBSB Advanced allows users to reduce the total size and weight of the installation, improving both design flexibility and assembly aesthetics.
The unique manufacturing process of integral pre-punched palms make IBS/IBSB Advanced ready to connect out of the box. There are no lugs to purchase or install, making connections simpler and faster and eliminates faulty connections due to vibration or fatigue.
IBS/IBSB Advanced is compatible with all major brand molded case circuit breakers.
The advanced technology insulation is a high-resistance low smoke, halogen- free and flame retardant thermoplastic.
IBS/IBSB Advanced does not generate corrosive gases and produces a relatively low smoke opacity in accordance with IEC 61034-2 and UL 2885. The low smoke characteristic improves visibility conditions for people to be able to easily
locate the emergency exit and also allows rescue workers to better assess an emergency situation. IBS/IBSB Advanced means greater safety for individuals, less damage for your electrical equipment and less environmental impact.
The halogen–free feature enables a reduction in the quantity of toxic smoke. IBS/IBSB Advanced does not contain any halogens, according to IEC 60754-1 and UL 2885, minimizing toxicity and making it the ideal product for use in enclosed spaces such as data centers, rail, and public facilities such as hospitals and schools. This also facilitates the use of IBS/IBSB Advanced in specific applications such as submarines, switchboards and other enclosed environments that require a low emissions solution.
In addition to the above features, IBS/IBSB Advanced is compliant with the UL 94-V0 testing standard and glow wire test 960 °C. The flame retardant portion of the test illustrates the self-extinguish feature. This superior feature
of IBS/IBSB Advanced is also shown by the Limiting Oxygen Index (LOI) at 30%. In case of fire, IBS/IBSB Advanced generates a limited quantity of smoke that is less damaging to your electrical equipment.

CERTIFICATIONS

nVent Eriflex IBSBADV120 330 IBSB Advanced Insulated Braided Conductor -
CERTIFICATIONS

FEATURES

Suitable for all main molded case circuit breakers
Resistant to vibration, improving reliability and performance
Insulated by high-resistance, halogen free, flame retardant and low smoke material
Tinned copper provides superior corrosion resistance
Improves assembly flexibility and aesthetics
Quick and easy installation
No additional cutting, stripping, crimping and punching needed
Integral palm without lugs or terminals reduces material and assembly weight
Conforms to NF EN 45545 obtaining an HL3 classification for chapters R22 and R23
DNV GL® and Bureau Veritas certified for marine and offshore applications
Small wire diameter provides maximum flexibility
Dramatically smaller and more flexible than comparable cable based on ampacity
Better power density than cable with lower skin effect ratio
Reduces total installation cost
RoHS compliant
Tinned copper allows for copper or aluminum conductor connections

PRODUCT ATTRIBUTES

Article Number: 534429
Typical Application Current Rating: 400 A
Peak Short Circuit Current (Ipk): 70 kA
Finish: Tinned
Material: Copper;Thermoplastic Elastomer
Dielectric Strength: 20 kV/mm
Low Smoke Rating: IEC® 61034-2;ISO 5659-2;UL® 2885
UV Resistance Rating: UL® 854;UL® 2556
Halogen Free Rating: UL® 2885;IEC® 60754-1;IEC® 62821-1
Flammability Rating: UL® 94V-0
Insulation Elongation: 500 %
Insulation Thickness: 0.070″
Max Working Voltage, IEC/UL 758: 1,000 VAC;1,500 VDC
Max Working Voltage, UL 67: 600 VAC/DC
Working Temperature: -58 to 239 °F
Wire Diameter: 0.006″
Complies With: IEC® 60439.1;IEC® 60695-2-11 (Glow Wire Test 960 °C);IEC® 61439.1;IEC® 61439.1 Class II
Certification Details: UL® 67;UL® 758
Cross Section: 236.820 kcmil
Conductor Width: 1.26″
Conductor Thickness: 0.17″
Length: 12.990″
D: 0.470″
C: 1.540″
B: 0.430″
A: 0.430″
Hole Size 1: 0.410″
Hole Size 2: 0.410″
Unit Weight: 1.040 lb

ADDITIONAL PRODUCT DETAILS

∆T = Temperature of conductors – Internal temperature of panel.
This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
IBSB Advanced Insulated Braided Conductor with a cross section of 240 mm² (473.65 kcmil) is constructed of red copper strands with tinned palms.
Distance between supports must not exceed 630 mm (17.8″) according to IEC 61439-1.

DIAGRAMS

Maximum Ampacity Ratings

Cross Section (mm2/kcmil)| ?T 30° C (A)| ?T 40°C (A)| ?T 45°C (A)| ?T 50° C (A)| ?T 55° C (A)| ?T 60° C (A)| ?T 70°C (A)| 2 Bar
Current Coefficient| 3 Bar Current Coefficient
25/49.34| 116| 134| 142| 150| 157| 164| 177| 2.| 2
50/98.68| 213| 246| 260| 274| 288| 301| 325| 2.| 2
70/138.15| 226| 261| 277| 291| 306| 319| 345| 2.| 2
100/197.35| 298| 344| 365| 385| 404| 422| 456| 2.| 2
120/236.82| 363| 419| 444| 468| 491| 513| 554| 2.| 2
185/365.1| 416| 480| 509| 537| 563| 588| 635| 2.| 2
240/473.65| 556| 642| 681| 718| 753| 786| 849| 2.| 2
Cross Section (rnm2/kcmil)| ?T 30° C (A)| ?T 40°C (A)| ?T 45° C (A)| ?T 50° C (A)| ?T 55°C (A)| ?T 60° C (A)| ?T 70°C (A)| 2 Bar
Current Coefficient| 3 Bar Current Coefficient
25/49.34 (IBSB)| 116| 134| 142| 150| 157| 164| 177| 2.| 2
25/49.34 (IBS)| 137| 158| 167| 177| 185| 193| 209| 2.| 2
50/98.68| 213| 246| 260| 274| 288| 301| 325| 2.| 2
70/138.15| 226| 261| 277| 291| 306| 319| 345| 2.| 2
100/197.35| 298| 344| 365| 385| 404| 422| 456| 2.| 2
120/236.82| 363| 419| 444| 468| 491| 513| 554| 2.| 2
185/365.1| 416| 480| 509| 537| 563| 588| 635| 2.| 2
240/473.65| 556| 642| 681| 718| 753| 786| 849| 2.| 2
C Ire Mt Breaker Compatibility

Circuit  Breaker Current Rating| 1251160 A| 250 A| 300 A| 350 A| 400 A| 500A| 630 A
Part Number| IBSBADV2 ex| IBSADV264| IBSBADV6 Ox| IBSADV50 x| IBSBADV 704| IBSBADV1 00x| IBSBADV 120x| IBSBADV 165x| IBSBADV 240x
Schneider
Electric®
Compact® (IEC)| NSA NG 125| NSX 100
NSX 160| NSX 250| NSX 250| NSX 400| NSX 400| NSX 400| NSX 630| NSX 630
Square DO PowerPact® (UL)| H-F rame| J-Frame| U-Frame| U-Frame| L-F rame
T4| L-Frame| L- F ra me| |
ABB® Tmax® (IEC)| T1 T2 XT1 XT2| T3 XT3 XT4| T3 XT3 XT4| T4| 15| 15| 15
ABB® Tmax® (UL)| T1 T2 XT1 XT2| T3| 14 XT3 XT4| T4| 15| 15| 15| |
GE® Record Plus® (IEC/UL)| FD 160| FD 160| FE 250| FE 250| FG 400
VL400 3VL4| FG 400| FG 400| FG 630| FG 630
Siemens® Sentron® (IEC/UL)| VL160 X 3VL1
VL160
3VL2| | VL250 3VL3| VL250 3VL3| VL400 3VL4| VL400 3VL4|
Moeller@ xEnergy® (IEC)| NZM1| | NZM2| NZM2| NZM3
LG Frame| NZM3| NZM3| NZM3| NZM3
Cutler Hammer® Series G (UL)| EG Frame| JG Frame| JG Frame| JG Frame| LG Frame| LG Frame| LG Frame| LG Frame
Legrand® (IEC)| DPX 160 DPX3 160| | DPX 250 DPX3 250| DPX 250 DPX3 250| DPX 630| DPX 630| DPX 630| DPX 630| DPX 630
Hager® (IEC)| h3 160| | h3 250| h3 250| h3 630| h3 630| | |
Rockwell/Allen Bradley (UL)| 0-Frame
H-Frame| | I-Frame J-Frame| I-Frame J-Frame| I-Frame J-Frame| | K-Frame| K-Frame|
Mitsubishi Electric (IEC)| | NF125
NF160 DSN125 DSN160| NF250 DSN250| NF250 DSN250| | N F400 DSN400| | |
OEZ (IEC)| BC160N| | BD250N
ElD2505| | BI-163013
B1-16305| BI-163013
61-16305| BH63013
BI-16305| BH63013
BH6305| BH63013
611630S

WARNING

nVent products shall be installed and used only as indicated in nVent’s product instruction sheets and training materials.
Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.

North America

+1.800.753.9221
Option 1 – Customer Care
Option 2 – Technical Support
Europe

Netherlands:
+31 800-0200135
France:
+33 800 901 793
Europe

Germany: 800 1890272
Other Countries: +31 13 5835404
APAC

Shanghai: + 86 21 2412 1618/19
Sydney: +61 2 9751 8500

Our powerful portfolio of brands:
nVent.com CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER
© 2022 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates.
All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.

Documents / Resources

| nVent Eriflex IBSBADV120-330 IBSB Advanced Insulated Braided Conductor [pdf] Owner's Manual
EFX 534429, IBSBADV120-330, IBSBADV120-330 IBSB Advanced Insulated Braided Conductor, IBSB Advanced Insulated Braided Conductor, Advanced Insulated Braided Conductor, Insulated Braided Conductor, Braided Conductor, Conductor
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals