GEWiSS GW90871 KNX Gateway Instruction Manual

June 13, 2024
GEWiSS

GEWiSS-lgoo

GEWiSS GW90871 KNX Gateway

Product Information

Product Name: Gateway KNX/DMX GW90871

General Warnings: Please follow the instructions carefully before installation and usage.

Package Contents:

  • 1 x Gateway KNX/DMX Device
  • 1 x Installation Manual

General Description:

  • Input Voltage Terminal (9…30Vdc)
  • KNX BUS Terminal
  • DMX/RS485 Terminal
  • USB Connector
  • RS-232 Connector
  • Main Group Setting ETS Toggle Switch
  • KNX Physical Address Programming Button
  • Slow Start-up Function Selector for Light Protection
  • Dimming Function Selector
  • Reset Button

Installation Warnings:

  • The installation should be done by qualified personnel, following the applicable regulations and guidelines for KNX/EIB installations.
  • The maximum length of the bus line should not exceed 700 meters.
  • To avoid unwanted signal interference, do not run the bus line parallel to power lines and maintain a minimum distance of 4mm between them.

Product Usage Instructions

Electrical Connections:

WARNING: Disconnect the power supply before connecting the device to the electrical network!

Follow the steps below for electrical connections:

  1. Connect the red wire of the bus cable to the red(+) terminaland the black wire to the black(-) terminal. Up to 4 bus lines can be connected to the same terminal with wires of the same color.
  2. Connect the bus device.

Programming

Physical Address Programming:

  1. Power the device through the bus.
  2. Press the programming button to prepare the Gateway KNX/DMX for physical address loading from ETS. Both main power and KNX bus power are required to configure the device via ETS.

Functions:

The Gateway KNX-DMX has the following available objects:

  • DPT1.001 (1 bit; single-channel switch)
  • DPT1.001 (1 bit; sequence save/recall)
  • DPT3.007 (4 bit; single-channel relative dimming)
  • DPT5.001 (1 byte; single-channel value display)

The gateway also supports the following functions:

  • Automatic Off Function (S3=0): Reduces or increments the DMX# value gradually by 7..-7 in percentage.
  • Automatic On Function (S30): Allocates a lower group address (bi-level KNX address area). Use DPT 5.001 with a 1-byte value (0..100%) to set the channel value.

Note: For setting a 1-byte value, use lower group addresses (0-511) corresponding to the channels.

GENERAL INFORMATION

Warning!
The safety of this appliance is only guaranteed if all the instructions given here are followed scrupulously.
These should be read thoroughly and kept in a sate place.
Chorus products can be installed in environments which are dust-free and where no special protection against the penetration of water is required.
They shall be installed in compliance with the requirements for household devices set out by the national standards and rules applicable to low-voltage electrical installations which are in force in the country where the products are installed, or, when there are none, following the international standard for low-voltage elec- trical installations IC 60364, or the European harmonization document HD 60364. Gewiss sales organization is ready to provide full explanations and technical data on request. Gewiss SpA reserves the right to make changes to the product described in this manual at any time and without giving any notice.

PACK CONTENT

The delivery package of the Gateway KNX/DMX contains the following components:
N. 1 Device Gateway KNX/DMX
N. 1 Installation instructions

GENERAL DESCRIPTION

  • The KNX-DMX Gateway is an Interface between the KNX bus and the DMX512 bus.
  • It combines elements of building automation with a multitude of lighting and special effects devices for every need.
  • The KNX-DMX Gateway is unidirectional, receives data telegrams on the KNX bus and transmits the data onto the DMX512 bus.
  • The interface allows the DMX512 actuators to communicate via the KNX bus using the full range of the channel.
  • The KNX-DMX Gateway contains 8 adjustable sequence positions within the whole channel range.
  • Individual scenes with all 512 channels can be saved and retrieved using KNX group addresses.
  • This function allows all channels to be connected simultaneously to one single object without causing any undo load on the KNX bus.
  • The sequences are saved internally and can be retrieved even after a power outage.
  • (A sequence can only be saved 10000 times during the lifetime of the device.
  • The automatic save function should not be set for short intervals.)
  • The set value in sequence 8 is also „on” for all channels when using 1 bit objects.
  • The KNX-DMX Gateway is ready to use and can be positioned to the main group addresses with an S1rotary switch.
  • It is not necessary to project via the ETS.
  1. Clamp DC IN (9…30V)
  2. Clamp KNX BUS
  3. Clamp DMX/RS485
  4. USB Connector
  5. RS-232 Connector
  6. Rotary switch Main Group ETS
  7. Push button programming KNX Physical address
  8. Rotary switch for Function Soft Start
  9. Rotary switch for Function Dimming
  10. Reset

INSTALLATION

WARNING: the installation of the device must be exclusively done by qualified personnel, following the regulations in force and the guidelines for KNX/EIB installations.
Warnings for KNX/EIB installations

  1. The length of the bus line between the KNX/DMX Gateway and the power supply unit must not exceed 350 metres.
  2. The length of the bus line between the KNX/DMX Gateway and the most distant KNX/EIB device must not exceed 700 metres.
  3. If possible do not create ring circuits so as to prevent undesirable signals and overloads.
  4. Keep a distance of at least 4 mm between the individually insulated cables of the bus line and those of the electric line.
  5. Do not damage the electrical continuity conductor of the shielding.
  6. Bus cable
  7. Electrical continuity conductor
  8. Shield

WARNING: the unused bus signal cables and the electric continuity cable must never touch powered elements or the grounding cable!

Warnings for installation phase

  • Switch on the voltage supply.
  • The group addresses are coded by S1 when the DC voltage in KNX-DMX Gateway is switched on.
  • Soft-start (slow start-up to protect lights) can be adjusted using S2 and S3 sets the dimming function.
  • If turning the rotary switch afterwards has no effect, it can be reset using T1.
  • The Pr button on device inputs the physical addresses via a dummy application into the ETS.
  • The Jumper J1 (120R TERM) times the RS485 Bus with 120 Ohm load resistance in its initial state.
  • The KNX bus is galvanically separated from the DMX 512 bus!
  • The power supply is galvanically separated from the DMX 512 bus and the KNX bus!

WARNING: disconnect the network voltage before connecting the device to the power network!
For electrical connection diagrams, see the following examples.

  1. Connect the bus cable’s red wire to the terminal’s red connector (+) and the black wire to the black con- nector (-).
    Up to 4 bus lines (wires of the same colour in the same connector) can be connected to the bus terminal.

  2. Bus device connection

  3. Bus cable connection

  4. Insulate the screen, the electrical continuity conductor and the remaining white and yellow wires of the bus cable should a bus cable with 4 conductors be used), which are not needed.

PROGRAMMING

Physical address programming
Physical address programming

  1. Power up the device using the bus.
  2. Press the programming button to set the Gateway KNX/DMX to load the physical address from ETS.
    Both Main Supply and bus power are requie to set the device via ETS.

Functions

The KNX-DMX Gateway has 1556 objects with three types of telegrams available:

  • DPT 1.001 (1bit: switch) single channel
  • DPT 1.001 (1bit; switch) save sequence and retrieve
  • DPT 3.007 (4bit; relative dimming) single channel
  • DPT 5.001 (1byte; show value) single channel
  • The S2 rotary switch adjusts the transition period from one preset brightness to the next, 15 (F) being immediate, O a time period of 1 second from 0% to 100%.
  • The S3 rotary switch automatically sets the dimming function parameters, O is no automatic dimming, other- wise dimming time = 1.5 sec * switch value (S3 = 1 .. 15 (F) ) in increments of 1% (dimming value 0111b or 1111b).
  • The rotary switch settings will be prompted when starting and can be readjusted during operation by using the T1 button.
  • Necessary requirements are a KNX bus, DMX 512 bus and a power supply.
  • The KNX-DMX Gateway in REG casing IP20 is available in sizes of 6 DIN units.
  • Firmware upgrades can be done via USB port.

Automatic Dimming Function:

  • Automatic dimming function can be switched on or off for all channels using an object, or can be parameterized by S3 when booting up.
  • Thereby the properties are controlled when dimming telegram (DPT 3.007) appears.
  • Automatic function Off ( S3 = 0)
  • A dimming object (4 bit) value range +7 .. -7 singularly reduces or increases the DMX value percentagewise.
  • Automatic function On ( S3 <>0)
  • A uniquely transmitted dimming setting is repeated during a time period (dimmer repetition) until it reaches a value of 0 or 100% or until it is manually stopped.
  • When 100% is transmitted, the preset value in „dimming curve” is used (basic setting 1%).
  • This function allows the integration of the KNX-Gateway for an installation with standard key buttons.
  • A standard key button transmits a 100% upward or downward command in dimming function when pushed and held and a stop command when let go.
  • A dimming setting can thus be set.
  • The dimming time period can be adjusted separately using either the parameter repetition or the dimmer curve.
  • The basic setting after booting up is 1% dimming.
  • The repetition rate is controlled by the rotary switch S3 and gives a dimming time result of circa 1.5 sec switching value (S3 = 1 .. 15 (F).

Address Diagram

  • The KNX-DMX Gateway is a master device in the DMX bus.
  • It possesses an internal data memory and constantly transmits the data at a DMX rate of 250k baud to all 512 DMX channels.
  • When receiving valid DMX telegrams the values in the memory are changed.
  • The transfer of the KNX telegram is preconfigured so that individual programming is not necessary.
  • The KNX data points are managed in 3 address rooms.
  • That means that switching or dimming can be accessed on every channel.
  • The group addresses diagram must be set up using the S1 rotary switch before initial operation (voltage supply).
  • Changes become effective after a reset.
  • The main group addresses from 0 – 15 are set up with the 16 stage rotary switch.
  • The middle and lower group addresses are set by the predetermined address rooms (see table 1).
  • The DPT 5.001 allocates the first 512 address on the KNX bus. After that the DPT 1.001 and DPT 3.007.
  • Finally, the sequence commands, a test function and dimming parameters are coded.

Group Address Allocation Lower Group (bi-level KNX Address Room):
Set Channel Value:
Addresses 0 – 511
DMX bus.
with DPT 5.001 1 byte value ( 0 .. 100% )
To set a 1 byte value, use the lower group addresses 0-511 which correspond to the channels 1-512 on the Switch Channel Value:
with DPT 1.001 1 bit Value (Switching)
Addresses 512 – 1023
Using a switch, this function can be used to switch every channel separately.
When the value is 0 the channel is switched off (0), when it is 1 the saved value in sequence 8 is accessed and transmitted to the DMX512 bus.
Every DMX channel can be independently switched.

Group Address Allocation Lower Group (bi-level KNX Address Room):

  • Before the values are transmitted, there must be defined values saved in Sequence 8.
  • This is the case for default settings at the time of delivery (255 for all channels.
  • To reset the default settings use either the defined value with DPT 5.001 (group address ×/0-511) or the function „Central On” (group address ×/1552) all values to 255.
  • Then save this to Sequence 8 (group address ×/1551).
  • This establishes a maximum value for every channel.

Dimming Channel: with DPT 3.007: 4 bit Value (Dimming)
Addresses 1024 – 1535

Table 1:
Possible Dimming Value as 4 bit Object:

  • 0 =Stop
  • 1 = 100% down
  • 2 = 50% down
  • 3 = 25% down
  • 4 = 12% down
  • 5 = 6% down
  • 6 = 3% down
  • 7 = 1% down
  • 8 = Stop
  • 9 = 100% up
  • 10 = 50% up
  • 11 = 25% up
  • 12 = 12% up
  • 13 = 6% up
  • 14 = 3% su
  • 15 = 1% up

Using the automatic dimming function affects the performance when a dimming telgram is received.

Choose Sequence: with DPT 1.001 1 bit Value (Switching)

  • Addresses 1536 – 1543
  • A complete sequence with 512 channels can be output via the DMX bus.
  • All previously saved values are displayed on channels 1-512.
  • There is a choice of 8 sequences at the addresses 1536-1543.
  • The default value at the time of delivery is 255 for sequence 8 and 0 for sequences 1-7.

Save Sequence: with DPT 1.001 1 bit Value (Switching)

  • Addresses 1544-1551
  • Here the current DMX values can be saved in one of the 8 sequences.
  • The current brightness will be saved. There is a choice of 8 sequences at the addresses 1544-1551.

Central On: with DPT 1.001 1 bit Value (Switching)

  • Address: 1552
  • All 512 channels display 100% when a 1 is transmitted and 0% when a 0 is transmitted.

Dimmer Repetition Rate: Set repetition rate parameters

  • Address: 1553
  • The repetition rate affects the dimming time.
  • At increments of 1%, a dimming time of 1.5 sec * is achieved.
  • Standard settings can be set using S3 (1 .. 15 (F) ).
  • with DPT 5.001 1 byte Value ( 0 .. 250 )
  • Suggested values are 2-40.

Downwards Dimming Curve: with DPT 3.007 4 bit Value (Dimming)

  • Address: 1554
  • Set dimming down to 100%.
  • When the automatic dimming function is chosen, the command ,0001b” (100% dim down) is received and the programmed dimming setting will be repeated (see Repetition Rate Object 1553) until 0 has been reached or until it is manually stopped.
  • Standard setting „0111b” = -1%
  • Possible dimming values as 4 bit object, see table 1

Upwards Dimming Curve: with DPT 3.007 4 bit Value (Dimming)

  • Address: 1555
  • Set dimming up to 100%.
  • When the automatic dimming function is chosen, the command “1001h” (100% dim up)is received and the programmed dimming setting will be repeated (see Repetition Rate Object 1553) until 255 has been reached, or until it is manually stopped.
  • Standard setting „1111b” =+1%
  • Possible dimming values as 4 bit object, see table 1

Group address Table on three levels:

KNX 3 Level Structure| Value| DMX512

Chan- nel Nr.

| Se- quence Nr.| KNX-DMX Gate-

way Function

| Detail
---|---|---|---|---|---
Main Groups| MG| UG
0-15 (S1)| 0| 0-255| 0..255| 001-256| –| DPT 5.001 transmits 1byte value (Absolute value)| 1 Byte value is stored into the corresponding DMX-Channel directly
0-15 (S1)| 1| 0-255| 0..255| 257-512| –| DPT 5.001 transmits 1byte value (Absolute value)
0-15 (S1)| 2| 0-255| 0/1| 001-256| –| DPT 1.001 value transmission| When a 1 is received the value stored in sequence Nr. 8 is sent to the correspond-

ing DMX-Channel When a 0 is received the DMX-Channel

is turned off.

0-15 (S1)| 3| 0-255| 0/1| 257-512| –| DPT 1.001 value transmission
0-15 (S1)| 4| 0-255| -7..+7| 001-256| –| DPT 3.007 value transmission| Relatively lighter or darker dimming than the current level
0-15 (S1)| 5| 0-255| -7..+7| 257-512| –| DPT 3.007 value transmission
0-15 (S1)| 6| 0-7| 0/1| ALL| 0-7| DPT 1.001 value transmission

Access saved sequences

| The selected sequence values of all 512 chan- nels are transmitted

on the DMX512 bus

0-15 (S1)| 6| 8-15| 0/1| ALL| 0-7| DPT 1.001 value transmission

Save the new sequence

| All current DMX values in channels 1-512 are stored in the selected sequence position
0-15 (S1)| 6| 16| 0/1| ALL| –| DPT 1.001 value transmission

All channels central on

| All 512 channels

display 100% when

1 is transmitted, 0% when 0 is transmitted

0-15 (S1)| 6| 17| 0..255| ALL| –| DPT 5.001 value transmission

Repetition rate parameters

| Repetition rate of 10msec Value default 3
0-15 (S1)| 6| 18| 0..7| ALL| –| DPT 3.007 value transmission

Set downward dim-

ming curve

| Dim repitition value Value Default 15=1%
0-15 (S1)| 6| 19| 0..7| ALL| –| DPT 3.007 value transmission

Set upward dimming curve

| Dim repitition value Value Default 15=1%
0-15 (S1)| 6| 20| 0/1| ALL| –| DPT 1.001 value transmission Deactivate auto- matic dimming| Disables auto- matic dimming when value = 0

Group address Table on two levels:

KNX 2 Level Structure| Value| DMX512

Chan- nel Nr.

| Sequence Nr.| KNX-DMX Gate-

way Function

| Detail
---|---|---|---|---|---
Main Groups| UG
0-15 (S1)| 0-511| 0..255| 001-512| –| DPT 5.001 trans- mits 1byte value (Absolute value)| 1 Byte value is stored into the corresponding DMX-Channel directly
0-15 (S1)| 511-1023| 0..255| 001-512| –| DPT 1.001 value transmission| When a 1 is received the value stored in sequence Nr. 8 is sent to the correspond-

ing DMX-Channel When a 0 is received the DMX-Channel

is turned off.

0-15 (S1)| 1024-1535| -7..+7| 001-512| –| DPT 3.007 value transmission| Relatively lighter or darker dimming than the current level
0-15 (S1)| 1536-1543| 0/1| ALL| 0/7| DPT 1.001 value transmission Access saved sequences| The selected sequence values of all 512 chan- nels are transmitted

on the DMX512 bus

0-15 (S1)| 1544-1551| 0/1| ALL| 0/7| DPT 1.001 value transmission Save the new sequence| All current DMX values in channels 1-512 are stored in the selected sequence position
0-15 (S1)| 1552| 0/1| ALL| –| DPT 1.001 value transmission

All channels

central on

| All 512 channels

display 100% when

1 is transmitted, 0% when 0 is transmitted

0-15 (S1)| 1553| 0..255| ALL| –| DPT 5.001 value transmission Repetition rate parameters| Repetition rate of 10msec Value default 3
0-15 (S1)| 1554| 0..7| ALL| –| DPT 3.007 value transmission

Set downward

dimming curve

| Dim repitition value Value Default 15=1%
0-15 (S1)| 1555| 0..7| ALL| –| DPT 3.007 value transmission

Set upward

dimming curve

| Dim repitition value Value Default 15=1%
0-15 (S1)| 1556| 0/1| ALL| –| DPT 1.001 value transmission Deactivate auto- matic dimming| Disables auto- matic dimming when value = 0

TECHNICAL DATA

  • Measurements: 107x75x31mm

  • Degree of Protection: IP20

  • Mounting: modular device with 92mm

  • Surrouding Temperature: -5 °C to 45 °C

  • Control Element: N°3 for 16 staged rotary switch

    • N°1 for Push Button (User)
    • N°2 for LED (User)
    • N°1 for EIB-Push Button+LED
  • KNX Connection: KNX clam block

  • KNX Power Supply: 20 – 32V DC, approx. 150 mW

  • DMX Connection: 3 screw clamps 0.8mm² KL1 GND, KL2 Data – (B), KL3 Data+ (A)

  • Load ResistanceDMX512: 120 Ohm via jumper

  • Power Supply: 9-30V DC, 100mA, internal galvanically separated 2 screw clamps
    KL1 – GND
    KL2 – +V

  • DMX512 Bus: RS485 – 250Kbaud, incl. galvanic separation DMX512 log
    Please note the DMB512 specific connecting configurations (bus connection, number of receiving slaves, bus topology)

Contact details according to the relevant European Directives and Regulations:
GEWISS S.p.A. Via A.Volta, 1 IT-24069 Cenate Sotto (BG) Italy tel: +39 035 946 111 E-mail: [email protected]

www.gewiss.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GEWiSS User Manuals

Related Manuals