Qlima P420 Portable Air Conditioner Instruction Manual
- June 12, 2024
- Qlima
Table of Contents
Qlima P420 Portable Air Conditioner
Product Information
This user manual is for the P420 product. It provides information on safety precautions, installation guidelines, operating instructions, maintenance tips, and troubleshooting. The manual also includes information on energy classification and warranty terms.
Product Usage Instructions
- Safety Precautions:
- Before using the device, make sure it is properly connected to a power source and visually inspect it for any damages.
- Do not use the device if it is damaged or if there are any signs of malfunction.
- Follow the recommended installation guidelines to ensure safe usage.
- Avoid placing the device near heat sources, direct sunlight, or areas with excessive moisture.
- Do not block the air vents or obstruct the airflow of the device.
- Do not touch the device with wet hands or insert any objects into the device.
- Keep the device away from flammable materials and avoid exposing it to water or other liquids.
- Installation Guidelines:
- Prepare the necessary tools and materials for installation.
- Follow the recommended installation method provided in the manual.
- Use the provided safety bracket and screws to secure the device in place.
- Install the air exhaust hose according to the instructions provided.
- Optional: Use a saw to shorten the window adapter for narrow windows.
- Operating Instructions:
- Familiarize yourself with the control panel functions as described in the manual.
- Use the buttons and settings on the control panel to adjust temperature, humidity, and other features.
- Follow the recommended operating instructions to achieve desired results.
- Refer to the manual for additional features and functions of the device.
- Maintenance:
- Follow the safety precautions when performing maintenance tasks.
- Regularly clean the air filter to ensure optimal performance.
- Check for any signs of damage or malfunction during maintenance.
- Refer to the troubleshooting section for tips on resolving common issues.
Please note that this is a brief summary of the information provided in the
user manual.
For detailed instructions and specific guidelines, please refer to the
complete user manual that came with the product.
IMPORTANT NOTE:
Read this manual carefully before installing or operating your new air
conditioning unit. Make sure to save this manual for future reference.
SAFETY PRECAUTIONS
Read Safety Precautions Before Operation and Installation. To prevent death or
injury to the user or other people and property damage, the following
instructions must be followed. Incorrect operation due to ignoring of
instructions may cause death, harm or damage.
WARNING
This symbol indicates the possibility of personnel injury or loss of life.
CAUTION
This symbol indicates the possibility of property damage or serious
consequences.
WARNING
-
Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire.
-
Use only the included accessories and parts, and specified tools for the installation. Using nonstandard parts can cause water leakage, electrical shock, fire, and injury or property damage.
-
Make sure that the outlet you are using is grounded and has the appropriate voltage. The power cord is equipped with a three-prong grounding plug to protect against shock.
-
Voltage information can be found on the nameplate of the unit.
-
Your unit must be used in a properly grounded wall receptacle. If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker (the fuse or circuit breaker needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on unit), have a qualified electrician install the proper receptacle.
-
Install the unit on a flat, sturdy surface. Failure to do so could result in damage or excessive noise and vibration.
-
The unit must be kept free from obstruction to ensure proper function and to mitigate safety hazards.
-
Do not modify the length of the power cord or use an extension cord to power the unit.
-
Do not share a single outlet with other electrical appliances. Improper power supply can cause fire or electrical shock.
-
Do not install your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit. Do not install the unit in a
-
location that may be exposed to combustible gas, as this could cause fire.
-
The unit has wheels to facilitate moving. Make sure not to use the wheels on thick carpet or to roll over objects, as these could cause tipping.
-
Do not operate a unit that it has been dropped or damaged.
-
The appliance with electric heater shall have at least 1 meter space to the combustible materials.
-
Do not touch the unit with wet or damp hands or when barefoot.
-
If the air conditioner is knocked over during use, turn off the unit and unplug it from the main power supply immediately. Visually inspect the unit to ensure there is no damage. If you suspect the unit has been damaged, contact a technician or customer service for assistance.
-
In a thunderstorm, the power must be cut off to avoid damage to the machine due to lightning.
-
Your air conditioner should be used in such a way that it is protected from moisture. e.g.
condensation, splashed water, etc. Do not place or store your air conditioner where it can fall or be pulled into water or any other liquid. Unplug immediately if it occurs. All wiring must be performed strictly in accordance with the wiring diagram located inside of the unit. -
The unit’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board, such as:
T 3.15A/250V, etc. -
When the water drainage function is not in use, keep the upper and the lower drain plug firmly to the unit to get rid of choking. When the drain plug is not in use, keep it carefully to prevent children from choking.
CAUTION
-
This appliance can be used by children aged from 8 years and above and person with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. (be applicable for the European Countries)
-
This appliance is not intended for use by persons (including childern) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
-
Children must be supervised around the unit at all times.(be applicable for other countries except the European Countries )
-
If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or similarly qualified persons in order to avoid a hazard.
-
Prior to cleaning or other maintenance, the appliance must be disconnected from the supply mains.
-
Do not remove any fixed covers. Never use this appliance if it is not working properly, or if it has been dropped or damaged.
-
Do not run cord under carpeting. Do not cover cord with throw rugs, runners, or similar coverings. Do not route cord under furniture or appliances. Arrange cord away from traffic area and where it will not be tripped over.
-
Do not operate unit with a damaged cord, plug, power fuse or circuit breaker. Discard unit or return to an authorized service facility for examination and/or repair. To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
The appliance shall be installed in accordance with national wiring regulations. -
Contact the authorized service technician for repair or maintenance of this unit. Contact the authorised installer for installation of this unit.
-
Do not cover or obstruct the inlet or outlet grilles.
-
Do not use this product for functions other than those described in this instruction manual.
-
Before cleaning, turn off the power and unplug the unit.
-
Disconnect the power if strange sounds, smell, or smoke comes from it.
-
Do not press the buttons on the control panel with anything other than your fingers. Do not remove any fixed covers. Never use this appliance if it is not working properly, or if it has been dropped or damaged.
-
Do not operate or stop the unit by inserting or pulling out the power cord plug.
-
Do not use hazardous chemicals to clean or come into contact with the unit. Do not use the unit in the presence of inflammable substances or vapour such as alcohol, insecticides, petrol,etc.
-
Always transport your air conditioner in a vertical position and stand on a stable, level surface during use.
-
Always contact a qualified person to carry out repairs. If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired.
-
Hold the plug by the head of the power plug when taking it out.
-
Turn off the product when not in use.
SOCIABLE REMARK
When using this air conditioner in the European countries, the following
information must be followed:
DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary. It is prohibited to dispose of this appliance in domestic household waste.
For disposal, there are several possibilities:
- The municipality has established collection systems, where electronic waste can be disposed of at least free of charge to the user.
- When buying a new product, the retailer will take back the old product at least free of charge.
- The manufacture will take back the old appliance for disposal at least free of charge to the user.
- As old products contain valuable resources, they can be sold to scrap metal dealers. Wild disposal of waste in forests and landscapes endangers your health when hazar do us substances leak into the ground-water and find their way into the food chain.
WARNING FOR USING R32/R290 REFRIGERANT
-
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater). -
Do not pierce or burn.
-
Be aware that the refrigerants may not contain an dour.
-
Appliance should be installed, operated and stored in a room with a floor area according to the amount of refrigerant to be charged. For specific information on the type of gas and the amount,
-
please refer to the relevant label on the unit itself. When there are differences between the label and the manual on the Min. room area description, the description on label shall prevail.
For R290
amount of refrigerant (kg)| Min. room area(m)| amount of refrigerant (kg)|
Min. room area(m)
---|---|---|---
0.0836 and 0.1045| 5| 0.2090 and 0.2299| 11
0.1045 and 0.1254| 6| 0.2299 and 0.2508| 12
0.1254 and 0.1463| 7| 0.2508 and 0.2717| 13
0.1463 and 0.1672| 8| 0.2717 and 0.2926| 14
0.1672 and 0.1881| 9| 0.2926 and 0.3135| 15
0.1881 and 0.2090| 10| |
- Compliance with national gas regulations shall be observed. Keep ventilation openings clear of obstruction.
- The appliance shall be stored so as to prevent mechanical damage from occurring. A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
- Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognized assessment specification.
- Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
- The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater).
Explanation of symbols displayed on the unit(For the unit adopts R32/R290 Refrigerant only):
| WARNING| This symbol shows that this appliance used a flammable
refrigerant. If the refrigerant is leaked and exposed to an external ignition
source, there is a risk of fire.
---|---|---
| CAUTION| This symbol shows that the operation manual should be read
carefully.
| CAUTION| This symbol shows that a service personnel should be handling this
equipment with reference to the installation manual.
| CAUTION| This symbol shows that information is available such as the
operating manual or installation manual.
-
Transport of equipment containing flammable refrigerants. See transport regulations.
-
Marking of equipment using signs. See local regulations.
-
Disposal of equipment using flammable refrigerants. See national regulations.
-
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions. -
Storage of packed (unsold) equipment. Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
-
Information on servicing
-
Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
-
Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed. -
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material. -
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. -
Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. -
No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed. -
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. -
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: The charge size is in accordance with the room size within which the refrigerant containing parts are installed; The ventilation machinery and outlets are operating adequately and are not obstructed; If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded. -
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include: That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; That there no live electrical components and wiring are exposed while charging, recovering or purging the system; That there is continuity of earth bonding. -
Repairs to sealed components
-
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
-
Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them. -
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. -
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. -
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. -
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. -
Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. -
Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. -
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.-
Become familiar with the equipment and its operation
-
Isolate system electrically.
-
Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders
conform to the appropriate standards -
Pump down refrigerant system, if possible.
-
If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
-
Make sure that cylinder is situated on the scales before recovery takes place.
-
Start the recovery machine and operate in accordance with manufacturer’s instructions.
-
Do not overfill cylinders. (No more than 80 %volume liquid charge).
-
Do not exceed the maximum working pressure of the cylinder, even temporarily.
-
When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
-
Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
-
-
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. -
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely..
Fuse | FUSE-T-3.15A/250VAC |
---|---|
Rated current | 3.15A |
Rated Voltage | 250VAC |
INSTALLATION INSTRUCTIONS
Preparation
- NOTE:
All the illustrations in the manual are for explanation purpose only. Your machine may be slightly different. The actual shape shall prevail. The unit can be controlled by the unit control panel alone or with the remote controller. This manual does not include Remote Controller Operations, see the <> packed with the unit for details.
- Control panel
- Remote signal receptor
- Horizontal louver control lever (adjust manually)
- Vertical louver control lever (adjust manually)
- Panel
- Caster
- Handle (both sides)
- Air filter
- Upper air intake
- Drain outlet
- Air outlet
- Lower air intake
- Bottom tray drain outlet
Design Notice
In order to ensure the optimal performance of our products, the design
specifications of the unit and remote control are subject to change without
prior notice.
Energy Rating Information
The Energy Rating for this unit is based on an installation using an un-
extended exhaust duct without window slider adaptor (as shown in the
Installation section of this manual). At the same time, the unit must be
operate on the COOL MODE and HIGH FAN SPEED by remote controller.
Ambient Temperature Range For Unit Operating
MODE | Temperature Range |
---|---|
Cool | 17-35°C (62-95°F) |
Dry | 13-35°C (55-95°F) |
Exhaust hose installation
The exhaust hose and adaptor must be installed or removed in accordance with
the usage mode. For COOL,HEAT (heat pump type) or AUTO mode must be instal-led
exhaust hose. For FAN, DRY or HEAT (electrical heat type) mode must be removed
exhaust hose.
Choosing The Right Location
Your installation location should meet the following requirements:
- Make sure that you install your unit on an even surface to minimize noise and vibration.
- The unit must be installed near a grounded plug, and the Collection Tray Drain (found on the back of the unit) must be accessible.
- The unit should be located at least 30cm (12”) from the nearest wall to ensure proper air conditioning. The horizontal louver blade should be at least 50cm (19.7”) away from obstacles.
- DO NOT cover the Intakes, Outlets or Remote Signal Receptor of the unit, as this could cause damage to the unit.
Recommend Installation
Energy Rating Information
The energy rating and noise information for this unit is based on the standard
installation using an un-extended exhaust duct without window slider adaptor
(as shown in the Installation section of this manual). At the same time, the
unit must be operate on the COOL MODE and HIGH FAN SPEED by remote controller.
The unit with 3 meters extended exhaust duct is running by using 2 exhaust
ducts (Diameter:150mm, Length:1.5m + Diameter: 130mm, Length: 1.5m) .The
Energy rating and noise information for unit with 3 meters extended exhaust
duct is not assessed.(For some models)
NOTE:
We recommend that operating the unit at room temperature below 35°C . Since
there is a risk that the unit with 3 meters extended exhaust duct would not
work at room temperature above 35°C under some extreme conditions, such as the
lower air intake be blocked for 50%.
Tools Needed
- Medium Philips screwdriver;
- Tape measure or ruler;
- Knife or scissors;
- Saw (optional, to shorten window adaptor for narrow windows)
- Exhaust hose
- Exhaust hose assembly
- Unit Adaptor
- Wall exhaust adaptor A
NOTE: Items with (*) are on some models. Slight variations in design may occur.
Window Installation Kit
-
Step One: Preparing the Exhaust Hose assembly
Press the exhaust hose(or extended exhaust hose) into the window slider adaptor(or wall exhaust adaptor) and unit adaptor, clamp automatically by elastic buckles of the adaptors. -
Step Two: Install the Exhaust hose assembly to the unit
Push the Exhaust hose into the airoutlet opening of the unit along the arrow direction.
Installation
NOTE:
Once the Exhaust Hose assembly and Adjustable Window Slider are prepared,
choose from one of the following two installation methods.
- Security Bracket
- 2 Screws
NOTE: Cover the hole using the adaptor cap when not in use.
- Expansion anchor position
- Wall exhaust Adaptor B
- Adaptor cap
NOTE:
To ensure proper function, DO NOT overextend or bend the hose. Make sure that
there is no obstacle around the air outlet of the exhaust hose (in the range
of 500mm) in order to the exhaust system works properly. All the illustrations
in this manual are for explanation purpose only. Your air conditioner may be
slightly different. The actual shape shall prevail.
OPERATING INSTRUCTIONS
Control Panel Features
NOTE:
The following control panels are for explanation purpose only. The control
panel of the unit you purchased may be slightly different according to the
models. Your machine may not contain some indicators or buttons. The actual
shape shall prevail.
MODE button
Selects the appropriate operating mode. Each time you press the button, a mode
is selected in a sequence that goes from COOL, FAN, DRY, HEAT (on some
models), and AUTO(on some models). The mode indicator light illuminates under
the dif-ferent mode setting.
NOTE: On above modes, the unit operates the auto fan speed automatically.
Up (+) and Down (-) buttons
Used to adjust (increasing/decreasing) temperature settings in 1°C/2°F(or 1°F)
increments in a range of 17°C/62°F to 30°C/88°F (or 86°F).
NOTE: The control is capable of displaying temperature in degrees
Fahrenheit or degrees Celsius. To convert from one to the other, press and
hold the Up and Down buttons at the same time for 3 seconds.
Power button
Power switch on/off.
LED display
Shows the set temperature while on cool,heat or auto mode. While on DRY and
FAN modes, it shows the room temperature. Shows Error codes:
- E0-EEPROM error.
- E1-Room temperature sensor error.
- E2-Evaporator temperature sensor error.
- E3-Condenser temperature sensor error (on some models).
- E4-Display panel communication error.
- EC-Refrigerant leakage detection malfunction(on some models).
Shows protection code:
P1-Bottom tray is full–Connect the drain hose and drain the collected water
away. If protection repeats,call for service.
NOTE: When one of the above malfunctions occurs, turn off the unit, and
check for any obstructions. Restart the unit, if the malfunction is still
present, turn off the unit and unplug the
power cord. Contact the manufacturer or its service agents or a similar
qualified person for service.
Operation Instructions
COOL operation- Press the “MODE” button until the “COOL” indicator light comes
on.Press the ADJUST buttons “+” or “-” to select your desired room
temperature. The temperature can be set within a range of
17°C~30°C/62°F~88°F(or 86°F).
- Press the “FAN SPEED” button to choose the fanspeed.
DRY operation
- Press the “MODE” button until the “DRY” indicator light comes on.
- The fan speed or the temperature cannot be adjusted. The fan motor operates at LOW speed.
NOTE:Keep windows and doors closed for the best dehumidifying effect. Do not put the duct to window.
FAN operation
- Press the “MODE” button until the “FAN ” indicator light comes on.
- Press the “FAN SPEED” button on the remote controller to choose the fan speed. The temperature can not be adjusted.
- Do not put the duct to window.
AUTO operation
When you set the air conditioner in AUTO mode, it will automatically select
coo-ling, heating(cooling only models without), or fan only operation
depending on what temperature you have selected and the room temperature.
- The air conditioner will control room temperature automatically round the temperature point set by you.
- Under AUTO mode, you can not select the fan speed.
NOTE: Under AUTO mode, both the AUTO mode and the actual operation mode indicator lights illuminate for some models.
Other features
- SLEEP
This feature can be activated from the remote control ONLY. To activate SLEEP feature, the set temperature will increase(cooling) or decrease(heating) by 1°C/2°F (or 1°F) in 30 minutes. The set temperature will then increase(cooling) or decrease(heating) by another 1°C /2°F (or 1°F) after an additional 30 minutes. This new temperature will be maintained for 7 hours before it returns to the originally selected temperature. This ends the Sleep mode and the unit will continue to ope-rate as originally programmed.
NOTE: This feature is unavailabe under FAN or DRY mode.
AUTO-RESTART
If the unit breaks off unexpectedly due to the power cut, it will restart with
the previous function setting automatically when the power resumes.
AIR FLOW DIRECTION ADJUSTMENT
Adjust the air flow direction manually:
- The louver can be set to the desired position manually.
- Do not place any heavy objects or other loads on the louver, doing so will cause damage to the unit.
- Ensure the louver is fully opened under heating operation.
- Keep the louver fully opened during operation.
WAIT 3 MINUTES BEFORE RESUMING OPERATION
After the unit has stopped, it can not be restarted operation in the first 3
minutes.
This is to protect the unit. Operation will automatically start after 3 minutes.
POWER MANAGEMENT FEATURE
Under cooling operation, when the ambient temperature is lower than the
setting temperature for a period of time, the unit will be automatically
operate power management feature. The compressor and fan motor stop. When the
ambient temperature is higher than the setting temperature, the unit will be
automatically quit the power management feature. The compressor and (or) fan
motor run.
WATER DRAINAGE
- During dehumidifying modes, remove the drain plug from the back of the unit, install the drain connector (5/8″ universal female mender) with 3/4″ hose (locally purchased). For the models without drain connector, just attach the drain hose to the hole. Place the open end of the hose directly over the drain area in your basement floor.
- Remove the drain plug
- Continuous drain hose
NOTE: Make sure the hose is secure so there are no leaks. Direct the hose toward the drain, making sure that there are no kinks that will stop the warter flowing. Place the end of the hose into the drain and make sure the end of the hose is down to let the water flow smoothly. When the continuous drain hose is not used, ensure that the drain plug and knob are installed firmly to prevent leakage.
- During heating pump mode, remove the lower drain plug from the back of the unit, install the drain connector(5/8″ universal female mender) with 3/4″ hose(locally purchased). Carefully move the unit to a drain location, and let the water drain away.
NOTE: Make sure the drain hose is lower than the bottom tray drain outlet.
- Remove the drain plug
- Continuous drain hose
- When the water level of the bottom tray reaches a predetermined level, the unitbeeps 8 times, the digital display area shows “P1” . At this time the air conditioning/dehumidification process will immediately stop. However, the fan motor will continue to operate(this is normal). Carefully move the unit to a drain location, remove the bottom drain plug and let the water drain away. Reinstall the bottom drain plug and restart the machine until the “P1” symbol disappears. If the error repeats, call for service.
NOTE: Be sure to reinstall the bottom drain plug firmly to revent leakage before using the unit.
- Bottom drain plug
MAINTENANCE
Safety Precautions
- Always unplug the unit before cleaning or servicing.
- DO NOT use flammable liquids or chemicals to clean the unit.
- DO NOT wash the unit under running water. Doing so causes electrical danger.
- DO NOT operate the machine if the power supply was damaged during cleaning. A damaged power cord must be replaced with a new cord from the manufacturer.
Air Filter Cleaning
- CAUTION:
DO NOT operate the unit without filter because dirt and lint will clog it and reduce performance.
Maintenance Tips
- Be sure to clean the air filter every 2 weeks for optimal performance.
- The water collection tray should be drained immediately after P1 error occurs, and before storage to prevent mold.
- In households with animals, you will have to periodically wipe down the grill to prevent blocked airflow due to animal hair.
Unit Cleaning
Clean the unit using a damp, lint-free cloth and mild detergent. Dry the unit
with a dry, lint-free cloth.
Store the unit when not in use
- Drain the unit’s water collection tray according to the instructions in the following section.
- Run the appliance on FAN mode for 12 hours in a warm room to dry it and prevent mold.
- Turn off the appliance and unplug it.
- Clean the air filter according to the instructions in the previous section. Reinstall the clean, dry filter before storing.
- Remove the batteries from the remote control.
NOTE: Be sure to store the unit in a cool, dark place. Exposure to direct sunshine or extreme heat can shorten the lifespan of the unit.
NOTE: The cabinet and front may be dusted with an oil-free cloth or washed with a cloth dampened in a solution of warm water and mildliquid dishwashing deter-gent. Rinse thoroughly and wipe dry. Never use harsh cleansers, wax or polish on the cabinet front. Be sure to wring excess water from the cloth before wiping around the controls. Excess water in or around the controls may cause damage to the unit.
TROUBLESHOOTING TIPS
Problem | Possible causes | Solution |
---|
Unit does not turn on when pressing ON/ OFF
button
| P1 Error Code| The Water Collection Tray is full. Turn off the unit, drain the water from the Water Collection Tray and restart the
unit.
In COOL mode: room temperature is lower than the set temperature| Reset the
temperature
E0 EEPROM error| Contact the manufacturer or its service
agents or a similar qualified person for service.
Unit does not cool well| The air filter is blocked with dust
or animal hair
| Turn off the unit and clean the filter
according to instructions
Exhaust hose is not connected or is blocked| Turn off the unit, disconnect the
hose, check for blockage and reconnect the hose
The unit is low on refrigerant| Call a service technician to inspect the
unit and top off refrigerant
Temperature setting is too high| Decrease the set temperature
The windows and doors in the room are open| Make sure all windows and doors
are closed
The room area is too large| Double-check the cooling area
There are heat sources inside the
room
| Remove the heat sources if possible
The unit is noisy and vibrates too
much
| The ground is not level| Place the unit on a flat, level surface
The air filter is blocked with dust
or animal hair
| Turn off the unit and clean the filter
according to instructions
The unit makes a gurgling
sound
| This sound is caused by the flow of refrigerant inside the unit| This is normal
IMPEDANCE INFORMATION
To be in compliance EN 61000-3-11, the product shall be connected only to a
supply of the system impedance: | Zsys|=0.451 ohms or less, the product shall
be connected only to a supply of the system impedance: | Zsys|=0.437 ohms or
less, Before con-nect the product to public power network, please consult your
local power supply authority to ensure the power network meet above
requirement.
The design and specifications are subject to change without prior notice for
pro-duct improvement. Consult with the sales agency or manufacturer for
details. Any updates to the manual will be uploaded to the service website,
please check for the latest version.
GUARANTEE CONDITIONS
The air conditioner is supplied with a 24-month guarantee, commencing on the
date of purchase. All material and manufacturing defects will be repaired or
repla-ced free of charge within this period. The following rules apply:
- We expressly refuse all further damage claims, including claims for collateral damage.
- Repairs to or replacement of components within the guarantee period will not result in an extension of the guarantee.
- The guarantee is invalidated if any modifications have been made, non gen-uine parts are fitted or repairs are carried out by third parties.
- Components subject to normal wear, such as the filter, are not covered by the guarantee.
- The guarantee is valid only when you present the original, dated purchase invoice and if no modifications have been made to the product nor to the purchase invoice.
- The guarantee is invalid for damage caused by neglect or by actions that deviate from those in this instruction booklet.
- Transportation costs and the risks involved during the transportation of the air conditioner or air conditioner components shall always be for the account of the purchaser.
- Damage caused by not using suitable filters is not covered by the guarantee.
To prevent unnecessary expense, we recommend that you always first carefully consult the instructions for use. Take the air conditioner to your dealer for repairs if these instructions do not provide a solution.
Do not dispose of electrical appliances as unsorted municipal waste, use
separate collection facilities. Contact your local government for information
regarding the collection systems available. If electrical appliances are
disposed of in landfills or dumps, hazardous substances can leak into the
groundwater and get into the food chain, damaging your health and well-being.
When replacing old appliances with new once, the retailer is legally obligated
to take back your old appliance for disposal at least for free of charge. Do
not throw batteries into the fire, where they can explode or release dangerous
liquids. If you replace or destroy the remote control, remove the batteries
and throw them away in accordance with the applicable regulations because they
are harmful to the environment.
Environmental information: This equipment contains fluorinated greenhouse
gases covered by the Kyoto Protocol. It should only be serviced or dismantled
by professional trained personnel.
This equipment contains R290 / R32 refrigerant in the amount as stated in the
table above. Do not vent R290 / R32 into atmosphere: R290 / R32, is a
fluorinated greenhouse gas with a Global Warming Potential (GWP) = 3.
References
- Qlima homepage
- Home page Qlima.es
- Page d'accueil Qlima
- Qlima, esperti del comfort domestico
- Qlima homepage
- Qlima
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>