JOSMA 48V LifePo4 Battery Pack User Manual

June 12, 2024
JOSMA

JOSMA 48V LifePo4 Battery Pack

JOSMA-48V-LifePo4-Battery-Pack \(33\)

Product Information

Layout of Front Panel

NO. Name
1 Positive Terminal
2 SOC
3 ALM
4 RUN
5 ADD
6 Negative Terminal
7 Power Switch
8 Reset
9 RS4852/CAN2
10 LCD Screen

Battery Specifications

Nominal Parameters LFP48100P LFP48150P
Model No LFP48100P LFP48150P
Voltage 51.2 V 51.2 V
Capacity 100Ah 150Ah
Energy 5KWh 7KWh
Dimensions (L W H mm) 480440160 480440200
Weight (KG) Approx 48 Approx 60
Built-in BMS 16S 100A 16S 200A
Electrical Parameters
Operation Voltage 51.2 VDC 51.2 VDC
Max. Charging Voltage 58.4 VDC 58.4 VDC
Cut-off Discharge Voltage 43.2 VDC 43.2 VDC
Max. Continous Charging and Discharging Current 100A 150A
Peak Discharge Current 150A (5s) 250A (5s)
Basic Parameters
Cycles 6000 times
Communication Method RS485/CAN
Display Method and Language LCD, English
Operating Temperature Range -20~70
Operating Humidity Range 10%~85%
Additional Model LFP48200P
Voltage 51.2 V
Capacity 200Ah
Energy 10KWh
Dimensions (L W H mm) 480440255
Weight (KG) Approx 85
Built-in BMS 16S 200A
Electrical Parameters
Operation Voltage 51.2 VDC
Max. Charging Voltage 58.4 VDC
Cut-off Discharge Voltage 43.2 VDC
Max. Continous Charging and Discharging Current 200A
Peak Discharge Current 250A (5s)

Working Mode

Basic Mode

LED Indicator Description

Four green capacity indicators, one red alarm indicator, one green operation indicator

SOC Capacity Indicator

Status L1 L2 L3 L4
0-25% OFF OFF OFF Flash 2
25-50% OFF OFF ON Flash 2
50-75% OFF ON ON Flash 2
75-100% ON ON ON Flash 2

Status Indicator

Status RUN ALM
Standby OFF OFF
Charge ON OFF
Discharge OFF ON
Warning/Normal ON OFF

Flash Instruction of LED Indicators

Flash 1 Flash 2 Flash 3
ON 0.25 S ON 0.5 S ON 0.5 S
OFF 3.75 S OFF 0.5 S OFF 1.5 S

Communication

With RS485 and CAN interface, which supports communicating with multiple machines in parallel and with the upper computer. RS485 baud rate is 19200, CAN baud rate is 500K.

RS485 INTERFACE

8P8C RJ45 Pins Assignment (RS485)

Pins Definition

JOSMA-48V-LifePo4-Battery-Pack \(2\)

NO. Name Function
1 Positive Terminal Charge & Discharge
2 SOC Indicators For Capacity
3 ALM Indicator For Alarms
4 RUN Indicator For Running Status
5 ADD Dial Code Of Communication
6 Negative Terminal Charge & Discharge
7 Power Switch ON/OFF Switch
8 Reset Activate/Hibernate BMS
9 RS4852/CAN2 Communication Interface
10 LCD Screen Display Battery Information

Battery Specifications

Nominal Parameters

Model No| LFP48100P| LFP48150P| LFP48200P
Voltage| 51.2 V| 51.2 V| 51.2 V
Capacity| 100Ah| 150Ah| 200Ah
Energy| 5KWh| 7KWh| 10KWh
Dimensions (L W H mm)| 480440160| 480440200| 480440255
Weight (KG)| Approx 48| Approx 60| Approx 85
Built-in BMS| 16S 100A| 16S 200A| 16S 200A
Electrical Parameters
Operation Voltage| 51.2 VDC| 51.2 VDC| 51.2 VDC
Max. Charging Voltage| 58.4 VDC| 58.4 VDC| 58.4 VDC
Cut-off Discharge Voltage| 43.2 VDC| 43.2 VDC| 43.2 VDC
Max. Continous Charging and Discharging Current| 100A| 150A| 200A
Peak Discharge Current| 150A (5s)| 250A (5s)| 250A (5s)
Basic Parameters
Life Time(25°C)| 10 years
Communication Method| RS485/CAN
Display Method and Language| LCD, English
Life Cycles (70% DOD, 25°C)| ≥6000 times Cycles
Operating Temperature Range| -20℃~70℃
Operating Humidity Range| 10%~85%

Working Mode

Basic Mode

Charging Mode
The BMS turns on the charging MOSFET for charging when it detects an external charging voltage of ≥48V, and the cell voltage and temperature are within the chargeable range. When the charging current reaches the effective charging current, it enters the charging mode. Both charging and discharging MOSFETs are on in charge mode.

Discharging Mode
The BMS enters the discharge mode when it detects that the load is connected and the cell voltage and temperature are within the dischargeable range and the discharge current reaches the effective discharge current.

Standby Mode
When neither of the above two modes is met, it enters standby mode.

Hibernation Mode
The BMS will enter sleep (shutdown) mode after a specific time of standby, or when the battery triggers undervoltage protection, or when the key is executed to shutdown or when the upper computer executes the shutdown command mode.
The wake-up conditions of hibernation mode:

  1. Make charging to activation;
  2. Press the button to power on.

Description of Buzzer
Buzzer function can be enabled or disabled via the upper computer, factory default is disabled.

Description of Reset Button

  • When the BMS is dormant, press the button for 1S and then release it, the protection board will be activated and the LED will light up from “L4” for 0.5 seconds.
  • When the BMS is active, press the button for 3S and then release it, the board will be dormant and the LED will light up from “RUN” for 0.5 seconds.
Dormancy and Activation

Dormancy
The system will enter low-power mode when any of the following conditions are met.

  1. Single cell undervoltage protection or overall undervoltage protection is not released within 30 minutes.
  2. Press the button for 3 seconds and then release the button.
  3. The minimum individual voltage is lower than the sleep setting voltage (default value 3150mV) and the duration reaches the sleep delay time (default value 1440 minutes), and there is no communication and no charging/discharging in meanwhile.
  4. Forced shutdown via the upper computer software.

Note: Before entering hibernation, make sure that no external voltage is connected to the P-terminus, otherwise it will not be able to enter the low- power mode.

Activation
When the system is in low-power mode and any of the following conditions are met, the system will exit low-power mode and enter normal operation mode.

  1. Connect to the charger, the charger output voltage should be greater than or equal to 48V.
  2. Press the button for 1S, after releasing the button.

LED Indicator Description

LED Indicator Description
Four green capacity indicators, one red alarm indicator, one green operation indicator

SOC Capacity Indicator

Status Charge Discharge
Capacity Indicator L1● L2●
0~25% OFF OFF
25~50% OFF OFF
50~75% OFF Flash 2
75~100% Flash 2 ON
Running Indicator● ON Flash 3

Status Indicator

Status Warning/Normal RUN ALM SOC LED Mark
OFF OFF OFF ALL OFF
Standby Normal Flash 1 OFF ****



ON as battery capacity indicates

|
Warning| Flash 1| Flash 2|



Charge

| Normal| ON| OFF|
Over Voltage Warning| ON| OFF|
Over Current, Over Voltage

and Temperature Warning

| ON| Flash 2|
Over Voltage Protection| Flash 1| OFF|
Over Current Protection| ON| OFF|



Discharge

| Normal| Flash 3| OFF|
Warning| Flash 3| Flash 2|
Low Voltage Protection| Flash 1| Flash 2|
Protection of Overcurrent,

Short Circuit, Temperature, Reverse Polarity etc

| ****

OFF

| ****

ON

| ****

ALL OFF

|

Flash Instruction of LED Indicators

| ON| OFF
---|---|---
Flash 1| 0.25 S| 3.75 S
Flash 2| 0.5 S| 0.5 S
Flash 3| 0.5 S| 1.5 S

Communication

With RS485 and CAN interface, which supports communicating with multiple machines in parallel and with the upper computer. RS485 baud rate is 19200, CAN baud rate is 500K.

8P8C RJ45 Pins Assignment (RS485)

Pins| Definition
1、3| RS485_B
7| RS485_A
2、6| GND
4| CANH
5| CANL
8| NC

RS485 INTERFACE

The multi-unit parallel bus connections are shown in the following figure.

Instructions For Compatibility With Inverters

Instructions For Compatibility With Inverters

1. Compatible inverter brands list| Victron, Pylontech, Goodwe, Growatt, Voltronic, Deye, LXP, Sofar, GinLong, SMA, 拓宝, Salocor

2. If your inverter not on our list above

| ① If you can provide the communication protocol (a kind of code) of your inverter, we can customize the BMS to be compatible with your inverter, minimum order quantity for customzed is 50 pcs.

② Without communication protocol, inverter cannot communicate with our battery. You need to make some setting on your inverter, for example, select the user-defined mode and set the corresponding voltage level(according to the inverter user manual), so that they can work together without communication.

More questions about inverter communication, pls contact our customer service.

Assignment of ID Addresses

When performing parallel communication operation of multiple machines, you need to configure the dialing address of each PACK first. When the BMS is configured for stand-alone operation, and the dialing address can be any address; when the BMS is configured for cascade operation mode, the slave dialing address is selected from 1 to 31, and the host dialing address is selected from 32 or 48 according to the inverter brand.
You can enter the address code of the master or slave battery in the system parameters of the upper computer to detect and communicate.

Code| ADD| PACK

NO.

| Remarks
---|---|---|---
1| 2| 3| 4| 5| 6
ON| OFF| OFF| OFF| OFF| OFF| 1| PACK 1|

Slave Pack

OFF| ON| OFF| OFF| OFF| OFF| 2| PACK 2
ON| ON| OFF| OFF| OFF| OFF| 3| PACK 3
OFF| OFF| ON| OFF| OFF| OFF| 4| PACK 4
ON| OFF| ON| OFF| OFF| OFF| 5| PACK 5
OFF| ON| ON| OFF| OFF| OFF| 6| PACK 6
ON| ON| ON| OFF| OFF| OFF| 7| PACK 7
OFF| OFF| OFF| ON| OFF| OFF| 8| PACK 8
ON| OFF| OFF| ON| OFF| OFF| 9| PACK 9
OFF| ON| OFF| ON| OFF| OFF| 10| PACK 10
ON| ON| OFF| ON| OFF| OFF| 11| PACK 11
OFF| OFF| ON| ON| OFF| OFF| 12| PACK 12
ON| OFF| ON| ON| OFF| OFF| 13| PACK 13
OFF| ON| ON| ON| OFF| OFF| 14| PACK 14
ON| ON| ON| ON| OFF| OFF| 15| PACK 15
OFF| OFF| OFF| OFF| ON| OFF| 16| PACK 16
ON| OFF| OFF| OFF| ON| OFF| 17| PACK 17
OFF| ON| OFF| OFF| ON| OFF| 18| PACK 18
ON| ON| OFF| OFF| ON| OFF| 19| PACK 19
OFF| OFF| ON| OFF| ON| OFF| 20| PACK 20
ON| OFF| ON| OFF| ON| OFF| 21| PACK 21
OFF| ON| ON| OFF| ON| OFF| 22| PACK 22
ON| ON| ON| OFF| ON| OFF| 23| PACK 23
OFF| OFF| OFF| ON| ON| OFF| 24| PACK 24
ON| OFF| OFF| ON| ON| OFF| 25| PACK 25
OFF| ON| OFF| ON| ON| OFF| 26| PACK 26
ON| ON| OFF| ON| ON| OFF| 27| PACK 27
OFF| OFF| ON| ON| ON| OFF| 28| PACK 28
ON| OFF| ON| ON| ON| OFF| 29| PACK 29
OFF| ON| ON| ON| ON| OFF| 30| PACK 30
ON| ON| ON| ON| ON| OFF| 31| PACK 31

OFF

|

OFF

|

OFF

|

OFF

|

OFF

|

ON

|

32

|

PACK 32

| Master Pack : if your inverter is from other brands except

Victron, SMA and Growatt, the ADD of master pack is 32

OFF

|

OFF

|

OFF

|

OFF

|

ON

|

ON

|

48

| Master Pack : if your inverter is from Victron, SMA or

Growatt, the ADD of master pack is 48

LCD Display Introduction

Button description:

  • MENU:Enter the management system.
  • ENTER:Enter to the sub-menu.
  • ∇:Move the cursor down or to next page.
  • ESC:Return to the previous menu.

Power-on screen

System Date SOH
Charging/Discharging Current Environmental Temperature
Total Voltage Max. Temperature of Battery Cell
Remaining Capacity SOC
Max. Voltage of Single Unit Min. Voltage of Single Unit

Battery protection status:

  • Over Voltage: OV
  • Low Voltage: LV
  • Over Temp: OT
  • Low Temp: LT
  • Over Current: OC
  • Short Circuit: SC

Note: When there is protection situation of the battery, there will show the corresponding protection status, otherwise, the protection status will not be showed.

Press “MENU” to enter the main menu
(Note: “》” means there is a sub-menu, press “ENTER” to enter the sub-menu)

BMS Parameter
Battery Status
GYRO Status
Version Number

Move the cursor to “BMS Parameter” and press “Enter” to enter.

Voltage 0.00V
Current 0.0A
Cell Temp
Cell Volt

Move the cursor to “Cell Temp” and press “Enter” to check the battery temperature information, then press ” ∇ ” to turn the page.

Temp 01 xx℃
Temp 02 xx℃
Temp 03 xx℃
Temp 04 xx℃
MOS Temp xx℃
Env Temp xx℃

Move the cursor to “Cell Volt” and press “Enter” to check the battery voltage information, then press “▼” to turn the page.

JOSMA-48V-LifePo4-Battery-Pack \(11\)

Cell 01 xxxxmV
Cell 02 xxxxmV
Cell 03 xxxxmV
Cell 04 xxxxmV
Cell 05 xxxxmV
Cell 06 xxxxmV
Cell 07 xxxxmV
Cell 08 xxxxmV
Cell 09 xxxxmV
Cell 10 xxxxmV
Cell 11 xxxxmV
Cell 12 xxxxmV
Cell 13 xxxxmV
Cell 14 xxxxmV
Cell 15 xxxxmV
Cell 16 xxxxmV
SOC xx%
Nominal Capacity 0.0AH
Remain Capacity 0.0AH
BMS Cycles 0

Move the cursor to “Battery Status” and press “Enter” to check the battery status information, then press “▼” to turn the page.

Status IDLE/DISCHG/CHARGE/FULL
Alarm Status
Protect Status
Failure Alarm

Move the cursor to “Alarm Status” and press “Enter” to check the battery alarm information, then press “▼” to turn the page.

Over Volt YES/NO
Low Volt YES/NO
Over Temp YES/NO
Low Temp YES/NO
Low SOC YES/NO
Diff Volt YES/NO
Over Curr YES/NO
Reverse YES/NO

Move the cursor to “Protect Status” and press “Enter” to check the battery protection information, then press “▼” to turn the page.

Over Volt YES/NO
Low Volt YES/NO
Over Temp YES/NO
Low Temp YES/NO
Over Curr YES/NO
Short Curr YES/NO

Move the cursor to “Failure Alarm” and press “Enter” to check the battery fault information, then press “▼” to turn the page.

Sample Line

|

N/Y

---|---

Charge MOS

|

N/Y

Dis CHG MOS

|

N/Y

Sample Chip

|

N/Y

SC Times

|

0

Over Temp CNT

|

0

Over Cur CNT

|

0

OVER Chg CNT

|

0

Over Dchg CNT

|

0

Move the cursor to “GYRO Status” and press Enter to check the gyroscope information, then press “▼” to turn the page. (Note: This gyroscope is optional)


Set X axis:

|
---|---


Place Option:

|

Move the cursor to “Version number” and press Enter to check the version information, then press “▼” to turn the page.


BMS Version

| ****

---|---


LCD Version

| ****

Move the cursor to “BMS Version” and press “Enter” to check the BMS version information.

BMS SW Version

|
---|---

BMS HW Version

|

Move the cursor to “LCD Version” and press “Enter” to check the LCD version information.

LCD SW Version

|
---|---

LCD HW Version

|

Dormancy and Activation Function
After 1 minute of no button operation in normal running, the display screen will be off (only the backlight is off). Pressing any button while the screen is off will allow the screen light and operate normally.

Upper Computer Software Introduction

Enable the monitoring software, select the communication interface of the corresponding device, select the corresponding baud rate, and finally click “Open Serial Interface” to communicate with BMS and get the basic parameters.

You can switch the version in Chinese or English in help center

After the BMS communicates with the upper computer, you can monitor the basic parameters and status of the battery in real time. These information include battery voltage, current, SOC, SOH, cycle count, battery temperature, alarm status, protection status, etc.

You can view the real-time data storage of the BMS and export as excel tables.

When monitoring multiple packs, you need to set the start and end address of packs manually, you can check and comparethe data of each pack. And you can also export as excel table.

Basic parameters 1. Click “Read All” when enter for the first time. This section includes reading basic parameter information, restoring default parameters, writing individual parameters, writing all parameters, importing parameters and exporting parameters (it is not recommended to manually modified default parameters).

Basic parameters 2. Click “Read All” when enter for the first time. This section includes heating settings, other BMS parameter information, etc. (it is not recommended to manually modified default parameters).

System parameter setting.
Click “Read All” when enter for the first time. You can monitor the BMS parameters configuration, sleep settings and BMS information in
real-time(it is not recommended to manually modified default parameters).

Data calibration: Here is calibration content of BMS data (all has calibrated by factory, not recommended for private calibration).
Plug-in modules: Here will contains information about some additional functional modules.

Normal remote control: Here includes the control of charging and discharging MOS, heating and other states (please consult the manufacturer for operation).
Online upgrade: software online upgrade function of BMS (please consult the manufacturer for operation).

System Parameters 1. Here includes some basic parameter information and dormancy settings.

Click “Read Data” to get real-time history data and export data, and view basic data information of battery packs.

List of Accessories

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>