DENT INSTRUMENTS CT-HSC-020-U 20A High Performance Mini Current Transformers Owner’s Manual

June 12, 2024
DENT INSTRUMENTS

**DENT INSTRUMENTS CT-HSC-020-U 20A High Performance Mini Current Transformers Owner’s Manual

**

Instruction

The hinged “Mini” CTs are small, low-cost current transformers with high accuracy (<0.5%) over a wide dynamic range with excellent phase shift. The “Minis” are ideal where space is limited such as when metering multiple loads within a panel board. Use for current measurement, energy metering, load surveys, demand metering, energy research, and submetering.

DIMENSIONS

Dimensions

GRAPH

Graph

KEY SPECIFICATIONS

Window Size 0.4” (10 mm)
Current Range* 0.25 – 40A AC
Output 333 mV @ 20A AC 16.65 mV/A AC
Ratio Error** <0.5% from 0.25 to 40A Ac ( Typical)
Phase Error <1.5 from 1 to 40A AC

<2 from 0.25 1A Ac

Depending on meter compatibility. See ELITEpro™ and PowerScout™ specifications for details.

For maximum performance, keep CT contact surfaces wiped clean and free of debris

ELECTRICAL

  • Output:   333 mV @ 20 A
  • Wire Polarity: White = Hi, positive (+)
  • Black: Low, negative (-)
  • Phasing
  • Orientation
  • Arrow: On Case Points
  • Toward: Load
  • Frequency Range: 50 to 400 Hz

MECHANICAL

  • Case Material: White Nylon, UL 94 V-0
  • Leads:   600V, 20 gage
  • Working Temperature: -15 to 60°C (5 to 140°F)

SAFETY

  • Working Voltage: 600 VAC, Category III
  • Dielectric Strength:   3520 VAC for 1 minute
  • Certifications Conforms to:
    UL STD 61010-1
    Certified to:
    CAN/CSA STD C22.2
    No. 61010-1

PART NUMBERS

| 3 M Leads| 7 M Leads
---|---|---
20A Mini Hinged CT| CT-HSC-020-U| CT-HSC-020-U-7M

CONTACT US

DENT Instruments, Inc.
Energy & Power Measurement Solutions

925 SW Emkay Drive
Bend, Oregon 97702 USA
541.388.4774 | 800.388.0770
www.DENTinstruments.c

References