EMERSON PS1/PS2 Series Pressure Controls Instruction Manual
- June 12, 2024
- Emerson
Table of Contents
PS1/PS2 Series Pressure Controls
Instruction Manual
Pressure Controls Series PS1 / PS2
OPERATING INSTRUCTIONS
General information:
For application in refrigeration systems and heat pumps.
The device has a potential ignition source and has not been qualified
according to ATEX standards. Installation only in “non-explosive location”.
Safety instructions:
-
Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
-
This product is intended for use by qualified personnel having the appropriate knowledge and skills like trained according to EN 13313 or a specific training for flammable refrigerants.
-
Flammable refrigerants require special handling and care due to its flammability. Sufficient ventilation is required during service of the system.
-
Contact with rapidly expanding gases can cause frostbite and eye damage. Proper protective equipment (gloves, eye protection, etc.) must be used.
-
Ensure that the system is correctly labeled with applied refrigerant type and a warning for explosion risk.
-
In a severely contaminated system, avoid breathing acid vapors and avoid contact with skin from contaminated refrigerant / lubricants. Failure to do so could result in injury.
-
Before opening any system make sure pressure in system is brought to and remains at atmospheric pressure.
-
Do not release any refrigerant into the atmosphere!
-
Do not exceed the specified maximum ratings for pressure, temperature, voltage and current.
-
Ensure that the system piping is grounded.
-
Before installation or service disconnect all voltages from system and device.
-
Observe and avoid mechanical damage of housing in order to maintain protection class.
-
Do not use any other fluid media without prior approval of EMERSON.
Use of fluids not listed could result in:
– Change of hazard category of product and consequently change of conformity assessment requirement for product in accordance with European Pressure Equipment Directive 2014/68/EU. -
Ensure that design, installation and operation comply with European and national standards/regulations.
-
For flammable refrigerants only use valves and accessories approved for it!
Function:
Fig. 1a: automatic reset function:
- PS1/PS2 Pressure switches are equipped with SPDT snap action contacts switching from 1-2 to 1-4 on rising and from 1-4 to 1-2 on falling pressure.
Fig. b: manual reset function for low pressure reset /
Fig. 1c: manual reset function for high pressure reset:
- PS1/PS2 with manual reset (high pressure/low pressure reset): Reaching the preset switching point contact 1-4 switches to 1-2 (low pressure switch) or from 1-2 to 1-4 (high pressure switch) and locks in this position. After the pressure rises or drops by a fixed differential the switch can be reset by pushing the reset button.
Mounting location :
Any direction except upside down
Installation: (Fig. 2)
- PS1/PS2 controls may be installed by using a mounting plate or as a wall-mounted device against a flat surface.
- Use universal thread M4 or UNC8-32 mounting holes for installation via mounting plate.
- Use the standard mounting holes at the backside for wall mounting.
- Use mounting screws supplied with control.
- Mounting screws must not penetrate control backside by more than 8 mm to ensure proper operation.
- Do not use PS1/PS2 in pulsating operating conditions! To achieve protection class IP44, the following instructions must be observed:
- Cover must be closed, and cover screw fastened
- Control must be mounted against a flat surface so that all openings on the housing backside are fully covered
Pressure connection: (Fig. 3)
- Connection of the pressure side depends on the exact model / pressure connector.
- When connecting PS1/PS2 to the hot gas line of a refrigeration system, a pipe, capillary or flexible tube of at least 80 mm shall be used to allow sufficient temperature drop between refrigeration line and pressure switch bellows.
Threaded connection:
- Connectors A & C: Do not apply torsional load to pressure connector; use second spanner to counterbalance torque when tightening pressure connection.
- K-type connectors: use copper gasket supplied with control.
Brazing connection:
- Perform the brazing joint as per EN 14324.
- Before and after brazing clean tubing and brazing joints.
- Minimize vibrations in the piping lines by appropriate solutions.
- Do not exceed the max. surface temperature of 70 °C!
Pressure Test:
After completion of installation, a pressure test must be carried out as
follows:
– according to EN 378 for systems which must comply with European pressure
equipment directive 2014/68/EU.
– to maximum working pressure of system for other applications.
Tightness Test:
Conduct a tightness test according to EN 378-2 with appropriate equipment and
method to identify leakages from joints and products. The allowable leakage
rate must be according system manufacturer’s specification.
WARNING:
- Failure to pressure test or tightness test as described could result in loss of refrigerant, damage to property and/or personal injury.
- The tests must be conducted by skilled personnel with due respect regarding the danger related to pressure.
Electrical connection: (Fig. 4)
- Range spindle
- Lock plate
- Differential spindle
- Electrical terminals
- Check-out lever
- Cable entry grommet
- Pressure Connection
- Entire electrical connections have to comply with local regulations.
- Wire size must match the electrical load connected to the switch contacts.
- Ensure that the cables are mounted without tension; always leave the cable a bit loose.
- Ensure that cables are not mounted near sharp edges.
- Do not bend or mechanically stress the cable outlet, maintain a clearance of 20 mm to neighboring parts.
- Feed cables through rubber grommet at switch bottom.
- Optionally, the rubber grommet may be replaced by a standard PG 13.5 cable gland.
- Connect wires to terminals by considering switch functions as shown in Fig. 1a to Fig. 1c.
- Fasten terminal screws with torque 1.2 Nm max.
- For electronic applications with low electrical loads (voltage < 24 V and current <50 mA) gold plated contacts are recommended.
Setpoint adjustment: (Fig. 5)
- PS1/PS2 pressure switches come with individually adjustable range and differential depending on the exact model.
- Manual reset switches always have a fixed differential.
- Use a flat screwdriver or a 1/4” refrigeration (square) wrench to adjust setpoints as described below.
- Adjust upper setpoint using the range spindle.
- Adjust lower setpoint by turning the differential spindle.
Upper setpoint – Differential = Lower setpoint
(1) Upper setpoint
(2) Lower setpoint
(3) Differential = constant
(4) Turning range spindle| (5) Upper setpoint
(6) Lower setpoint
(7) Differential = variable
(8) Turning differential spindle
---|---
- A separate gauge must be used for exact adjustment of the setpoints. The integrated display scale can only be used for obtaining approximate settings.
- When changing the upper setpoint the lower setpoint must be re-checked.
- Refer to the Emerson catalogue or Technical Information for standard factory settings.
Manual reset / Universal reset: (Fig. 6a-c)
- Manual reset (external): press the reset button (1) as indicated by Fig. 6a.
- Manual reset (internal): remove the housing cover and press the reset button (2) as indicated by Fig. 6b.
- Note that the reset is ‘trip-free’, i. e. reset is only possible if the pressure has reached its reset threshold.
- Universal reset: remove the cover and change the universal toggle to the desired position (manual (3) or auto reset (4).(Fig. 6c)
Check- out lever: ((5) Fig. 4 & Fig. 7)
- Use the check-out lever to manually override the electrical contact position for testing out the system.
- Use the check-out lever on low pressure switches to manually override the electrical contact position for evacuating the refrigeration system.
Service / Maintenance:
- Disconnect electrical power before service.
- In case of repair work or replacing the control always use a new gasket. (K-Types)
- According to EN 378-4 during each periodic maintenance, tightness tests shall be carried out at the relevant part of the refrigerating system. This shall apply where appropriate following any repair.
Technical Data:
Medium compatibility| Fluid Group II
R448A, R449A, R513A, R450A, R134a, R452A, R23, R410A, R407C, R404A, R507,
R124, R1234ze (A2L)| Fluid Group
R32, R452B, R454B, R454A, R454C, I R455A, R1234yf
---|---|---
Electrical rating| Resistive load (AC1) 24 A / 230 VAC
Inductive load (AC15) 10 A / 230 VAC
Inductive load (DC13) 0.1 A / 230 VDC
3 A / 24 VDC
6 A / 12 VDC
Start-up (AC3) 144 A / 120 VAC / 230 VAC
Motor rating (FLA) 24 A / 120 VAC / 240 VAC
Locked rotor (LRA) 144 A / 120 VAC / 240 VAC| Resistive load (AC1) 10
A / 230 VAC
Inductive load (AC15) 1 A / 230 VAC; 10 A / 24 VAC
Inductive load (DC13) 0.1 A / 230 VDC
3 A / 24 VDC
6 A / 12 VDC
Start-up (AC3) –
Moto rating (FLA) –
Locked rotor (LRA) –
*) Acc. IEC 60335-2-40 max. electrical load = 2.5 kVA
NOTE: Use proper fuse for short circuit case by considering above
voltages/currents
Protection class
(IEC 529/EN 60529)| IP44
Temperature range TS
|Storage / Transport / Ambient / Medium| -50 °C…+70 °C
Max. allowable pressure PS/
Test pressure PT
| See Type code table
Vibration resistance (acc. EN 12263)| 4 g (10…1000 Hz)
Standards| – EN 12263
– PED 2014/68/EU, Category IV for all devices with TÜV approval under EN12263|
– LVD 2014/35/EU,
– EN 60947-1, EN 60947-5-1
Marking| 0035 for devices under PED ****pending
for devices under LVD ****all types
| all types (E85974)
all types
Dimensions| See Fig. 2
Type Code:
Emerson Climate Technologies GmbH
Pascalstrasse 65 I 52076 Aachen I Germany
www.climate.emerson.com/en-gb
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>