MLC E2 Electric Temperature Controller ElEctric tEmpEraturE
controllEr
MLC E2
MLCD E2
USER’S MANUAL
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the MLC(D) E2 unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Cleaning and user maintenance shall not be made by children without
supervision. Children shall not play with the appliance.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for design of electrical units, and has a contact separation in all poles that
allows for full disconnection under overvoltage category III conditions.
Ensure that the unit is switched off from the supply mains before removing the
guard.
All operations described in this manual must be performed by qualified
personnel only, properly trained and qualified to install, make electrical
connections and maintain ventilation units.
Do not attempt to install the product, connect it to the mains, or perform
maintenance yourself.
This is unsafe and impossible without special knowledge.
Disconnect the power supply prior to any operations with the unit.
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation. The present user’s manual should be
carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the
casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments. Never touch the unit with wet or damp
hands.
Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
The temperature controller is designed to control the temperature of
ventilation, heating and air conditioning systems. Can be used to control fans
and dampers of fan coil units, air heating units with three-speed fans. Allows
for automatic change of heating/cooling intensity.
The temperature controller is not designed for standalone operation.
It is rated for continuous operation.
DELIVERY SET
NAME | NUMBER |
---|---|
Temperature controller | 1 pc. |
Remote control (only for the MLCD E2 model) | 1 pc. |
User’s manual | 1 pc. |
Packing | 1 pc. |
TECHNICAL DATA
Unit voltage | 220 V, 50 (60) Hz |
---|---|
Maximum current | 3 A |
Temperature setting range | +5 °C … +37 °C |
Electric shock protection class | II |
Protection degree against dust and moisture | IP20 |
Ambient air temperature | -5 °C … +50 °C |
Overall dimensions | 86х86х15 [mm] |
DESIGN
Display 1
Power button 2
Mode selection button (COOLING, HEATING) 3
Fan speed selection button (HIGH, MEDIUM, LOW, AUTO) 4
Button to switch to “night” mode 5
Increasing setpoint temperature 6
Decreasing setpoint temperature 7
IR receiver 8 (for MLCD E2 model)
Display (Fig. 2):
indicates that the temperature controller is in night mode 9
indicates that the temperature controller is in cooling mode 10
indicates the room temperature or the setpoint temperature 11
indicates the setpoint temperature or the room temperature 12
indicates whether the damper with an actuator is switched on or off 13
indicates fan speed selection 14
indicates operation of the temperature controller in heating mode 15
INSTALLATION AND CONNECTION
CUT OFF POWER SUPPLY BEFORE ANY OPERATIONS ARE PERFORMED.
DO NOT LAY THE CABLE IN CLOSE PROXIMITY TO THE CONTROL PANEL CABLE!
WHILE ROUTING THE CONTROL PANEL CABLE DO NOT COIL THE EXTRA LENGTH.
-
Fix the junction box to the wall.
-
Remove the packaging material from the temperature controller. Carefully detach the front control panel from the casing.
Using excessive force can cause a breakdown of the temperature controller. -
Connect the wires to the terminals of the temperature controller according to the wiring diagram.
-
Insert the casing into the junction box 86×86 mm.
-
With the help of two mounting screws, fix the casing of the temperature controller to the junction box.
-
With the help of a level, adjust the position of the temperature controller casing, then tighten the fastening screws (levelling effects only the appearance and has no influence on operation of the temperature controller).
-
Install the front panel on the casing of the temperature controller by pressing it until it clicks.
Wiring diagrams
Ventilation with heating and cooling|
---|---
Ventilation with heating and cooling 3-wire system of SPDT valves|
Ventilation with heating and cooling 2-wire system of SPST valves|
| 3-speed fan
---|---
| 2-wire SPST valve
| 3-wire SPDT valve
OPERATION ALGORITHM
Switch on the temperature controller by pressing the power button (2). Press
the fan speed selection button. The display will show one of the characters
(14 in Fig. 2) or AUTO. This means that the fan will rotate at HI (high), MED
(medium), LOW or AUTO (automatic mode) speed. If AUTO mode is selected, the
fan speed will vary according to the difference between the actual room
temperature and the set temperature. If the room temperature is more than 3
degrees above the set temperature when cooling or more than 3 degrees below
the set temperature when heating, the fan will run at its highest speed. If
the room temperature is 2-3 degrees higher than the set temperature for
cooling or 2-3 degrees lower than the set temperature for heating, the fan
will run at medium speed. If the room temperature is 0-1 degrees above the set
temperature when cooling or 0-2 degrees below the set temperature when
heating, the fan will run at low speed.
Heating system operation.
Set the heating operation with the mode button (15 in Fig. 2). Press “+” to
increase the control temperature value. If the room temperature is lower than
the set temperature, the heating system will start. Press “-” to decrease the
control temperature value. If the room temperature is higher than the set
temperature, the heating system will stop.
Operation of the cooling system.
Set the cooling operation with the mode button (10 in Fig. 2). Press “-” to
decrease the control temperature value. If the room temperature is higher than
the set temperature, the cooling system will start.
Press “+” to increase the control temperature value. If the room temperature
is lower than the set temperature, the cooling system will stop.
Operation in the night mode.
Press the button to switch to the night mode (5 in Fig. 1). The night mode
symbol (9 in Fig.2) appears. This mode will be active for 8 hours and the
temperature controller will control heating or cooling according to the
schedule below. Press the night mode button again, the corresponding symbol
will disappear, which means that the night mode is cancelled.
Features of the night mode operation
The temperature controller is set to the cooling mode: For a gradual change in
temperature, one hour after setting the night mode, the set temperature will
automatically rise by 1 degree, and 2 hours later, the set temperature will
rise by 2 degrees and will be held at this level for 8 hours until the timer
is switched off. When the timer is switched off, the setpoint will be restored
to its original level automatically.
The temperature controller is set to the heating mode: To obtain a better
temperature variation smoothly, 30 minutes after setting the night mode, the
set point temperature will automatically decrease by 1 degree, and one hour
later, it will decrease by 2 degrees. After 2 more hours, the set temperature
will decrease by 3 degrees and this temperature will be maintained until the
timer is switched off, which is 8 hours. When the timer is switched off, the
set point will automatically return to its initial state.
ADJUSTMENT OF CONTROL MODES
Setting the control modes allows you to set certain operating characteristics
of the temperature controller for the automatic mode, according to your
requirements. Switch off the temperature controller by pressing the power
button then press and hold the night mode button (5, Fig.1) for at least 4
seconds until the display switches on. This means that you have entered the
first menu control mode setting item. There are a total of 4 of these items,
which are shown on the display accordingly. The relevant menu item is selected
by pressing the button (5). In each menu item, use the “+” or “-” button to
change the settings. To exit the menu and return to normal operation, switch
off the temperature controller by pressing the power button and switch it on
again.
If no button is pressed within 20 seconds, the temperature controller will
switch off.
Menu item 1: Temperature accuracy. The display will show “Temp adjust”. The
default value is 0, it is blinking in the configuration menu.
Any value from “-3” to “+3” may be selected. You can set the room temperature
in the display up to 3 degrees above or below.
Menu item 2: Entering the upper limit of the temperature setting. The display
shows 37°C, which is the maximum default value set by the manufacturer. Use
the “+” and “-” buttons to set the maximum limit. It can be set between 26°C
and 37°C.
Menu item 3: Entering the lower limit of the temperature setting. The display
shows 5’C, which is the minimum default value set by the manufacturer. Use the
“+” and “-” buttons to set the minimum limit. It can be set between 5°C and
24°C.
Menu item 4: Fan control. The display shows “ON”, which is the default value
set by the manufacturer. Use the “+” and “-” buttons to select between “ON”
and “OFF”. If “ON” is selected, the temperature controller will switch the fan
on at the set speed and will not stop until the mode selection button or fan
speed selection button is pressed. When selecting “OFF”, if the set
temperature is lower than the room temperature when heating or the set
temperature when cooling is higher than the room temperature, the temperature
controller will stop the fan and will remain in this mode until the mode
selection button is pressed.
Remote control
To operate the temperature controller using the remote controlpoint the remote
control towards the front panel of the controller at a distance of no more
than 4 m. In the process of long-term usethe battery of the remote control may
discharge. If this occurs, the
battery needs to be replaced. To do this, remove the battery holder from the
bottom of the remote control and replace the battery assuring correct
polarity.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s
manual with the purchase date stamp, and the payment paperwork certifying the
purchase. The unit model must comply with the one stated in the user’s manual.
Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Electric temperature controller |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The _____ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation|
Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Electric temperature controller |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
www.blaubergventilatoren.de
B21EN-04
Documents / Resources
|
BLAUBERG Ventilatoren MLC E2 Electric Temperature
Controller
[pdf] User Manual
MLC E2, MLCD E2, MLC E2 Electric Temperature Controller, Electric Temperature
Controller, Temperature Controller, Controller
---|---
Read User Manual Online (PDF format)