MDT TECHNOLOGIES AMS-0416.02 Switch Actuator AMI Instruction Manual
- June 12, 2024
- MDT technologies
Table of Contents
MDT TECHNOLOGIES AMS-0416.02 Switch Actuator AMI
Product Information
- Measuring inaccuracy: 2% – Sampling rate: 2000 samples/500ms
- Output switching ratings: 10mA – 20A –
- Ohmic loads: 16A – Capacitive loads: 140uF – Maximum lamp loads: –
- Halogen lamp 230V: 2500W – Halogen lamp, electronic transformer:3680W – Fluorescent lamp not compensated: 1500W
- Fluorescent lamp
- parallel compensated: 2000W – Permitted wire gauge: 20 – Screw terminal torque: 0.5Nm
- Power Supply: KNX bus – Power consumption
- KNX bus typ.: < 0.3W – Operation temperature range: IP 20 –
- Dimensions MDRC (Space Units): – AMS-0416.02: 4TE – AMS-0816.02:
- 8TE – AMS-1216.02: 12TE
Product Usage Instructions:
Installation and Commissioning: – Installation and commissioning of the device
should only be carried out by authorized electricians. – Observe the relevant
standards, directives, regulations, and instructions. – The devices are
approved for use in the EU and have
the CE mark. Use in the USA and Canada is prohibited. – All screw terminals
and connections under the current must be covered completely against touching
by the switch panel. – The switch panel cover should not be possible to open
without using tools. 2. Connection and Operation: – Connect the device to the
KNX bus using the bus connection terminal. – Use the programming key to assign
the physical address and set parameters with the ETS (Engineering Tool
Software). – After successful programming, the red programming LED will turn
off. 3. Manual Operation: – To manually operate the switch actuator, refer to
the instructions provided for the specific model (AMI/AMS-04xx.02 or AMI/AMS-
08xx.02). – The specific instructions for manual operation are not included in
the provided text extract. Please refer to the complete user manual for
detailed instructions. Note: Before commissioning, please download the
application software from the website
www.mdt.de/Downloads.html.
Operating Instructions Switch Actuator AMI/AMS – for authorized
electricians
Important safety notes
- Danger High Voltage
- Installation and commissioning of the device only be carried out by authorized electricians.
- The relevant standards, directives, regulations, and instructions must be observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
- supply the outputs can be alive. The outputs can be switched OFF using the push buttons on top of the device.
- After installation, a KNX bus telegram can switch the outputs alive
- Disconnect the mains power supply prior to installation or disassembly
- All screw terminals and connections under the current must be covered completely against touching by the switch panel.
- It should not be possible to open the switch panel cover without using tools
Terminals, Operating and Display Switch Actuator AMI/AMS
- KNX bus connection terminal
- Red programming LED
- Green ON/OFF Led
- Programming key
- Output power terminal
- Buttons for manual actuation
Technical Data
Technical Data| | AMS-0416.02
AMS-0816.02 AMS-1216.02
| | | AMI-0416.02
AMI-0816.02 AMI-1216.02
|
---|---|---|---|---|---|---
**Number of outputs**|
4
|
8
|
12
|
4
|
8
|
12
Current measurement range
| |
10mA – 20A
| | |
10mA – 20A
|
Measuring inaccuracy| | 2%| | | 2%|
Abtastrate Sampling rate| 2000 Messungen/500ms
2000 samples/500ms
| 2000 Messungen/500ms
2000 samples/500ms
Maximale Schaltleistung Output switching ratings| |
Ohmsche Last Ohmic loads| |
16A
| | |
16/20A
|
Kapazitive Last Capacitive loads| | 140uF| | | 200uF|
Spannung Voltage| | 230VAC| | | 230VAC|
Maximaler Einschaltstrom Maximum inrush current| 600A/150µs
250A/600µs
| 600A/150µs
300A/600µs
Maximale Last Maximum lamp loads
Glühlampen Incandescent lamps| | 2500W| | |
3680W
|
HV- Halogenlampen Halogen lamp 230V| | 2500W| | | 3680W|
NV- Halogenlampen, elektr. Tranformator Halogen lamp, electronic transformer|
| 1500W| | | 2000W|
Fluorescent lamp not compensated
| | 2300W| | | 3680W|
Leuchtstofflampen parallelkompensiert
Fluorescent lamp parallel compensated
| | 1500W| | | 2500W|
max. Anzahl EVG (elektronischer Trafo) max. number of electronic transformers|
| 20| | | 28|
Mech. Schalthäufigkeit
Output life expectancy (mechanical.)
| 1.000.000|
1.000.000
Spezifikation KNX Schnittstelle Specification KNX interface| TP-256
mit Long Frame Unterstützung für ETS5 TP-256 with long frame support for ETS5
Verfügbare KNX Datenbanken
Available application software
| ETS 4/5
Project file for ETS 3 (*.pr5)
| ETS 4/5
Project file for ETS 3 (*.pr5)
Max. Kabelquerschnitt Permitted wire gauge
Schraubklemmen Screw terminal| 1 x (0,5 – 4,0mm²)
2 x (0,5 – 2,5mm²)
| 1 x (0,5 – 4,0mm²)
2 x (0,5 – 2,5mm²)
KNX Busklemme
KNX busconnection terminal
| 0,8mm Ø, solid core| 0,8mm Ø, solid core
Anzugsmoment Schraubklemme Torque screw terminal| |
0,5Nm
| | |
0,5Nm
|
Versorgungsspannung Power Supply| | KNX bus| | | KNX bus|
Leistungsaufnahme KNX Bus typ.
Power consumption knx bus typ.
|
< 0,3W
|
< 0,4W
|
< 0,4W
|
< 0,3W
|
< 0,4W
|
< 0,4W
Umgebungstemperatur Operation temperature range| | 0 bis + 45°C| |
| 0 bis + 45°C|
Schutzart Enclosure| | IP 20| | | IP 20|
Abmessungen REG (Teilungseinheiten) Dimensions MDRC (Space
Units)|
4TE
|
8TE
|
12TE
|
4TE
|
8TE
|
12TE
Installation Switch Actuator AMI/AMS
- Place the Switch Actuator on DIN 35mm rail.
- Connect the Switch Actuator to the KNX bus
- Wire up the Switch Actuator as described in the circuit diagram. The switching contacts must be fused with a circuit breaker
- Switch on the KNX power supply.
- Exemplary circuit diagram AMI/AMS-0816.02
The total current carrying capacity neighboring outputs is max. 32A
Description Switch Actuator AMI/AMS
The MDT Switch Actuators receive KNX/EIB telegrams and switch up to 12 independent electrical loads. Each output uses a bistable relay and can be operated manually via a push button. A green LED indicates the switching status of each channel. The outputs are parametrized individually via ETS. The device provides extensive functions like logical operation, status response, block functions, central functions, delay functions, and staircase lighting functions. Additionally, the device provides several time and scene control. The Switch Actuator offers current measurement for each channel and measurement of the total current. In dependence on the parameterization, the measured data can be transmitted in different data formats (mA/A/kW) onto the KNX bus. Additionally, the device provides an hour/service interval meter. The integrated counter allows to capture the power consumption easily. The active power is calculated by the voltage and the factor cos phi. If the mains voltage fails, all outputs hold their current position. After bus voltage failure or recovery, the relay position is selected in dependence on the parameterization. The Switch Actuator is a modular installation device for fixed installation in dry rooms. It fits on DIN 35mm rails in power distribution boards or closed compact boxes.
Commissioning Switch Actuator AMI/AMS
Note: Before commissioning please download the application software at www.mdt.de/Downloads.html
- Assign the physical address and set parameters with the ETS.
- upload the physical address and parameters into the Switch Actuator.
- After the request press the programming button.
- After successful programming, the red LED turns off.
Manually operating Switch Actuator AMI/AMS
Each output can be operated manually via its particular push button. A green
LED indicates the switching status of each channel.