ALORAIR Storm Ultra and Pro Dehumidifer User Manual

June 12, 2024
Alorair

ALORAIR Logo User Manual

ALORAIR Storm Ultra and Pro Dehumidifer DEHUMIDIFIER
INSTALLATION AND OPERATIONS MANUAL
– READ AND SAVE THESE INSTRUCTIONS –

Safety Notes

  • The Storm Pro / Storm Ultra dehumidifier must always be connected using a grounded electrical connection as required for all electrical appliances. The warranty is voided and all responsibility for the operation transfers to the owner if non-grounded  wiring is utilized.
  • Your Storm Series dehumidifier must be maintained and serviced by qualified technicians.
  • Storm dehumidifiers are intended for use only when the unit is installed in a level and upright position. Operating the unit in any other position could cause water to come in contact with the electrical components.
  • Before moving the dehumidifier, turn off the unit and allow the pump reservoir to empty (if unit is already off, press “PURGE” button to confirm drain reservoir is empty). After the pump has finished operation, unplug the power cord and relocate the unit to the desired position.
  • If the inside of the machine has gotten wet for any reason, the unit should be opened and allowed to dry thoroughly before reconnecting it to electric and restarting.
  • For proper operation, neither the in letor discharge should be positioned against a wall. A minimum of 6’clearance between the Storm and any obstruction i s required.
  • Do not insert any objects or fingers into the in letor discharge.
  • All work on the machine should be done with the unit off and unplugged.
  • Do not spray water or cleaner directly on the exterior of the unit. Only use a damp cloth to clean the exterior and always unplug the unit first.
  • Do not use unit as shelf or device to hang clothes as this could cause damage to unit.
  • Do not stand on the machine.

Introduction

Identification
Congratulations o n purchasing a Storm Pro / Storm Ultra dehumidifier! The Storm Pro / Storm Ultra comes with an extensive warranty plan. To ensure you are eligible, be sure to note the serial number and date of purchase. The serial number can be found on the data on the back of the unit.
Model Name: Storm Pro Storm Ultra
Serial Number:……..
Date of Purchase:………

Customer Service
For additional questions concerning the operation fo your dehumidifier, please

Features

  • Storm Pro:85 pints per day at AHAM
  • Storm Ultra:90 pints per day at AHAM
  • Only 58 dBA
  • Automatic Humidistat
  • Built-in Pump with Overflow Protection
  • Self Monitoring System
  • Eco-Friendly R410A Refrigerant
  • Easy Access to Internal Components
  • Auto Restart After a Power Outage.
  • The Unit can be Ducted on the Supply/Outlet, if Necessary

How Your Storm Dehumidifier Works
The Storm Pro dehumidifier /The Storm Ultra dehumidifier utilize its integral humidistat to monitor the conditioned space. Once conditions are outside the desired setpoint, the compressor energizes and air is drawn across an evaporator coil. The evaporator coil is cooler than the dew point of the air so water vapor will turns into liquid condensation. The air is then reheated through the condenser coil and distributed back into the room.

Electrical Supply
WARNING 240 Volts may cause serious injury from electric shock.

Power Supply: 115V, 60 HzAC Only 1 Phase
Outlet Requirement: 3-Prong, GFI
Circuit Protector: 15 Amp Time Delay Fuse or Circuit Breaker
  1. Disconnect electrical power before servicing
  2. Only plug unit into grounded electrical outlet
  3. Do not use an extension cord
  4. Do not use a plug adapter

Installation
Place the Pro in your desired location. The in let of the machine should be at least 8″ from any obstructions. If the unit has been transported i n a horizontal position, allow it to sit in an upright position for at least 30 minutes before operating.

WARNING
Do not use dehumidifier in an environment where corrosive or high VOC materials are applied.

Unit Overview

Storm Pro Dehumidifier

ALORAIR Storm Ultra and Pro Dehumidifer - Storm

Storm Ultra Dehumidifier

ALORAIR Storm Ultra and Pro Dehumidifer - Storm 2

LCD Display Instructions

When the machine is powered on but not working:
(After power on, the buzzer makes a sound) Boot display : The LOGO interface will disappear after 2 seconds. Enter the following interface The machine displays when it is not working. (Power off state but have electricity)

Main interface display of dehumidification state:
The following information is displayed when the machine is working:
* 000 JOB HRS:
Refers to the working time, which is defined as the time from starting up to shutting down, including the defrost time during a the period, and the standby time after the humidity. The aco submenu has a reset function . If not, the working time shall Ctbe accumulated. Out   Total time 9999 hours, the largest cumulative to the largest automatically reset after restart, and display units for hours. (round off).

  • 000 LIFE HRS:
    Refers to the total working time, i.e. the total working time (hours), which is in hours. (Press the mode key + select the confirmation key, and the total working time will be cleaned after 3 seconds.)

  • IN/OUT 00°F 00% 00 gr/ Ib:
    Indicates the temperature, humidity and moisture content of the air inlet and outlet {GPP – grain per pound (gr/Ib)}.

  • Set 00%:
    Indicates set humidity.

  • If the main interface does not operate for 10 minutes, the screen will go out.Press any key to wake up.

  • Other icons light up or flicker when opened
    The total working time is the accumulation o f each working time (hours) in hours. (Press the mode key + select to confirmation key, and the total working time will be cleaned after 3 seconds.

3.Dehumidification status submenu interface display

3.1 Device name displayed on the screen:
You can change the device name on the APP application

3.2 “Indicates”:Do
“Indicates”:Do I need to clear out this time?”, press “>”if you need to clear. When the operation is completed, the working time of the main interface and the working time of this interface will be reset and started to be instant again.
After accumulation (9999), clean up and round.

3.3 “Coil Temp 000°C ” : Used to display the current temperature of the coil.When it is below zero, the “-” symbol is displayed in front. “-”  s not required on zero.

3.4 Wifi hotspot: Factory setting is “OFF”, press > to enable wifi hotspot and switch ON/OFF. The device can transmit data and receive APP commands. The icon flickers when connected on the main interface. After successful connection, the icon displays normally.
3.5.1 The power down time is adjusted according to”>” and the power down time increases from 3 t o 20 minutes (3-5-10-15-20), which is the so-called stop time of the fan after shutdown, in order to better drain the water.Factory set for 3 minutes.
(the other state of the fan is still 15 seconds.)

3.5.2 The screen displays when you press shut down:
Indicates: the fan is closed after a few minutes, and the standby page UNIT OFF is displayed after the fan is closed.

3.6 “Temp Units °F/°C”: Used for temperature scale switching.Press the “>” button to switch ° F / °C,  after switch symbol of corresponding parts is also changing.

3.7 “MOISTURE CONTENT UNITS”: It is used to switch the unit of GPP value with moisture content. Press > to switch the LB or Kg, after switch symbol of corresponding parts is also changing.

3.8 “Humidistat Setpoint 00%” : Used for setting dehumidification mode humidity. Press “>” to set the humidity. The adjustment range of humidity setting is between 25 and 80%.
Each key rises or falls 5%, which can be recycled.
When the setting is completed, do not operate for 5 seconds and begin to take effect. (Otherwise, the compressor will be shut down immediately after it is below ambient humidity at the time of setting.) Humidity below 25 percents “CO” mode recyclable. The main interface displays the set parameters.

4 . Main interface frosting status display:
The machine will display this after defrost when running

When the machine is running normally, “Defrost SHUTDOWN IN 06:00’ will occurs in the interface after defrosting. It’s defrost countdown use seconds as units. This screen displays only 3 seconds. Displays the previous interface and status after restoration. If it is the home screen, the frost icon will flash.

When the user is operating in the submenu, the machine is in the frosting state. At this point, the frosting interface displays 3 seconds, and returns to the submenu program in the background countdown. When the user returns to the main interface without any operation, the frosting state is displayed in the main interface in the way of icon flicker.

5. Compressor on waiting interface display
Compressor protection time not shown:

“Compressor ready IN 03:00” indicates: That the interface will be displayed when the compression is in a protected state. (including power-on and shutdown, the humidity rises immediately after the arrival of LOHI, and the shutdown resumes immediately after the emergence of LOHI ) . Displays the countdown in seconds. If the above situation does not occur within 3 minutes, it is not shown.

6. Water Pump working interface display
Compressor protection time not shown:

ALORAIR Storm Ultra and Pro Dehumidifer - Pump

“Pump working countdown”: Indicates: No matter in which working state and interface, as long as the pump works, this interface appears and counts down t o 28 seconds.However, the interface only displays the previous working status and interface after 3 seconds. For example, after 3 seconds, there is a drainage icon on the main interface and it will flash until the drainage is finished.

7. Interface display i n case of failure
Machine running time fault display:

Make fault judgment and take corresponding actions after starting up. Regardless of the state, the fault i s executed first and the fault code is displayed on the interface. If there is a fault in the sub-menu operation, immediately return to this interface display
fault (including defrosting state). (The fault is judged when the pump works, and the fault is displayed as usual, but the pump needs to complete the water pumping this time). Multiple faults can be displayed at the same time.

Description of fault display:

  • Humidity sensor fault: when the humidity sensor unit fault or signal can not be transmitted, the fault is judged t o be E1. The machine i s out o f operation (power on again after troubleshooting). Pump button can operate.

  • Ambient temperature T<2: When the sensor continuously detects the ambient temperature of inlet air T=2 degrees for 600 seconds, the fault is judged t o be LO and the whole machine is stopped. Other values, corresponding to the temperature region operation. (recoverable). At this time, the interface cannot be operated. The pump button can be operated.

  • Ambient temperature T=45: When the sensor continuously detects the inlet air environment temperature T=45 degrees for 15 seconds, the fault i s judged t o be HI and the whole machine i s stopped.
    Other values, corresponding to the temperature region operation. (recoverable). At this time, the interface cannot be operated. The pump button can be operated.

  • When the compressor is started, if the coil temperature value detected is greater than or equal to (ambient temperature -3 degrees) for 30 minutes continuously, it is judged t o be fluorine deficient (except defrosting), E5 is displayed, and the machine cannot be stopped for operation (It needs to be powered up again after troubleshooting). After the power is back on, the machine runs continuously for another 30 minutes for judgment. (The temperature probe is broken, the temperature needs to be minimal). The pump button can be operated.

  • After the pump works for 28 seconds when the high water level is switched on, E4 fault i s judged when the high water level switch is switched on for 3 consecutive seconds, and E4 fault is displayed. The machine stops and cannot be operated (The pump needs to be powered up again after troubleshooting).
    The pump can be operated.

Preparing the Unit for Use

Setup

  1. Position the machine so there is a minimum of 8″ clearance for the back and sides. or directly to a specific location for spot dry . If the compressor didn’t remain vertical during transportation, wait a minimum o f 30 minutes before turning the unit on.
  2. The included drain line attaches to the unit via a quick connection fitting that is located on the base of the unit. The drain line should be routed to a suitable drain or outside. Since the unit has an integral drain pump, the drain line may go up vertically (no more than 15’) prior to reaching the final drain location.ALORAIR Storm Ultra and Pro Dehumidifer - Connections
  3. Firmly insert the power cord in to the socket on back of the unit under the air outlet.
  4. Turn on the dehumidifer and use the control panel to set up the dehumidifier as desired.

Optional Duct Installation
Ducting of the unit allows you to condition an adjacent room or focus the discharge to a specific area. The diameter for the supply/discharge ducting is 6″.Flex or layflat ducting can be used for this purpose.

ALORAIR Storm Ultra and Pro Dehumidifer - Ducting'

Maintenance and Repair

Cleaning the Machine Body
Use a soft, damp cloth to clean the exterior parts of the unit. Do not use any soap or solvents.

Procedure for filter maintenance
The dust and obstacles on the filter should be removed regularly. You may need to clean and replace the filter.
Step:

  1. Unplug the unit .
  2. Remove the filter by sliding it upward from the bottom byhand to remove it.
  3. Check for dirt and build-up.
  4. For Pre-filter, wash it in warm water or vacuum it. Do not use soap or cleaners. Also, shake it gently and ensure the filters are dry before reinserting it.
  5. For MERV-8, Replace it as necessary, we recommend checking the filters a t least 1x/year

Accessing Internal Components
WARNING   Always unplug unit prior t o performing any maintenance.

  1. Remove the bottom two screws on the front of the machine.ALORAIR Storm Ultra and Pro Dehumidifer - machine 2
  2. Remove the upper two screws on the back of the machine.ALORAIR Storm Ultra and Pro Dehumidifer - machine 3
  3. Take Off the casing/Remove the outer shell of the machine.

Advanced Pump Cleaning:

  1. a. Use the manual pump button (PURGE), to drain any water from reservoir.
    b . Unplug the unit, and remove pump from reservoir (see page 13).
    c. Use a wet dry vac or paper towels t o remove any remaining water from the pump reservoir.

  2. Fill the pump reservoir with cleaning solution (15 oz water/ 1 oz bleach or 12 oz water / 4 oz white vinegar).

  3. Reassemble the pump and use the manual pump button t o flush the mixture through the discharge tubing.

  4. Mix another batch of cleaning solution then pour i t slowly into drain pan under evaporator c o i l and allow i t to clean the hose from pan to pump. This process can be stopped when the pump energizes 1 time.
    NOTE: If you get any bleach/water mixture on coils, flush with water.

  5. Pour sufficient clean water through the drain pan so that the pump activates twice (16-32 ounces).

  6. Reassemble the unit and return i t to operational status.

Cleaning the Coils
The coils on your dehumidifier also need to be cleaned once per year. To clean, simply spray with a self-rinsing, foaming coil cleaner (such as WEB Coil Cleaner).

ALORAIR Storm Ultra and Pro Dehumidifer - Maintance

Integral Pump Maintenance
NOTE: This pump requires routine maintenance that is not covered by your 1 year parts warranty. Only a defective pump will be repaired or replaced under the warranty.
As with all pumps, preventative maintenance is necessary to prevent issues from dirt and slime th at may accumulate in the drain system. This includes the drain pan, hose to the condensate pump, pump reservoir, pump head, float assembly, and discharge
tubing.
The pump is designed with quick connection construction, making it easy to access the pump and components for service and maintenance.
To Remove Pump from Reservoir:

  1. Unplug the unit.
  2. Open the back housing as shown on page 12.
  3. Remove the condensate tube from the pump.
  4. Use the quick connect fittings t o disconnect the main power and float switch electrical cables.
  5. Use a flathead screw driver to gently pry the the pump off the reservoir .

At least once per year, clean your pump system.
Basic Pump Cleaning:

  1. Press the pump button (PURGE) to drain any water from reservoir .

  2. Disconnect power to the dehumidifier .

  3. Mix a 16 oz cleaning solution of one of the following: 1 oz bleach/ 15 oz water or 4 oz white vinegar / 12 oz water. Pour the solution into the drain tray at the base of the coils.
    NOTE: /f you get any cleaning solution on the coils , flush with water

  4. Allow cleaning solution to soak for 15 minutes.

  5. Reconnect power to dehumidifier.

  6. Pour clean water into reservoir so the pump activates twice (about 16-32 oz. water).

  7. Repeat i f needed or refer t o Advanced instructions.

Storing Your Dehumidifier

If you plan on storing your dehumidfier for an extended period of time:

  1. Turn unit off and allow to d r y .
  2. Manually drain pump reservoir.
  3. Wrap and secure the power cord.
  4. Clean the filter.
  5. Store i n clean,dry environment.

Troubleshooting

Symptom Cause Solution
Display is Blank Poor Connection Verify that both ends of the Power cord are

plugged in
Power Outage| Reset power
No Airflow| Filter is Dirty| Clean the filter
Air Inlet or Outlet is Blocked| Clear the blockage
Error Code: El| Humidity Sensor or Communication Error| Check to ensure that the sensor wire is connected at both ends.
if no issues are visible, the sensor may be faulty.
Error Code: E4| Problem with Pump| Verify that the pump is properly installed and functioning. If so, unplug the unit for two minutes, then restart.
Error Code: LO| Room Temperature is below 33.8°F| Increase the room temperature so it is within operating range (above 33.8°F). If error still displays, check sensor.
Error Code: HI| Room Temperature is above 110°F| Decrease the room temperature so it is within operating range (below 110°F). If error still
displays, check the sensor.
E5 Error Code| Refrigerant Leak| Contact Your Installer for Assistance

Pump Alarm-Error Code E4

If an E4 code appears on the display:

  1. Reset the unit by disconnecting the power cord and then reconnecting it.
    NOTE: The unit will not function until the code has been cleared.

  2. Manually check to see if pump is operational by pressing the drain button. Verify that The pump energizes and de-energizes properly. Additionally, check to see i f any w a t e r purged from the system.

  3. If you haven’t cleaned the system recently, check the discharge l i n e for an obstruction, then clean the balance of the pump system (see “Maintenance” section for details).

  4. Replace the hoses and/or pump, i f maintenance alone isn’t sufficient.

Limited Warranty

This limited warranty starts from the date o f purchase. Alorair Solutions Inc. warrants t o the original purchaser that this ALORAIR product i s f r e e from manufacturing defects in material or workmanship for the limited warranty period of:
Six (6) Month parts and labor. This includes the shipments charges for replacement parts or unit.
One (1) year parts and labor. This does not include the shipment charge to send the defective product back to be repaired or replaced.
Three (3) years parts and labor on Refrigeration System ONLY (Compressor, Condenser, and evaporator). Transportation cost, not included Five (5) years parts on Refrigeration System ONLY(Compressor, Condenser, and evaporator).
Transportation cost, not included This limited warranty i s valid only on products purchased from the manufacturer or ALORAIR authorized dealer and operated, installed, and maintained according to the instructions included in this user guide or furnished with the product. Alorair Solutions Inc w i l l not provide in-home service during or after the warranty period. You may be responsible for the shipping charge to bring the product to the manufacturer for service.
To receive warranty service, the purchaser must contact ALORAIR at 888-990-7469 or [email protected]. A proof of purchase or order number i s required to receive warranty service.
During the applicable warranty period, a product w i l l be repaired or replaced at the sole option of ALORAIR.

IMPORTANT NOTICE: Keep the item’s packaging in case warranty service is required.

Limited Warranty Exclusions
This limited warranty covers manufacturing defects in materials or workmanship encountered in  normal household, commercial or noncommercial use of this product and shall not cover the following:

  • Damage occurs in uses for which this product was not intended for.
  • Damage caused by unauthorized modification or a l t e r a t i o n of the p r o d u c t .
  • Cosmetic damage including scratches, dents, chips, and other damage to the product’s finishes.
  • Damage caused by abuse, misuse, pest infestation, accident, f i r e , floods, or other acts of nature.
  • Damage caused by incorrect electrical line current, voltage, fluctuations, and surges.
  • Damage caused by failure t o perform proper maintenance of the p r o d u c t .

The use o f this product in SPA or a room with OUTDOOR POOL invalidate or voids limited warranty.

ALORAIR Logo AlorAir Solutions INC.
Add: 14752 Yorba Ct Chino CA 91710 US
Tel: 1-888-990-7469
E-mail: [email protected]
Note: as we keep upgrading our product, we reserve the right to modify the product without notice in advance.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Alorair User Manuals

Related Manuals