THERMON PN50852U Terminator ZP-Ambient-WP Thermostat Connection Kit Instruction Manual
- June 12, 2024
- THERMON
Table of Contents
Terminator™
ZP-Ambient-WP
Thermostat Connection Kit
INSTALLATION PROCEDURES
Instruction Manual
For Ambient Sensing Thermostat Connection Applications
(Pilot Control or Direct Switching of 1-2 Heating Cables)
Terminator™ ZP-Ambient-WP
The following installation procedures are suggested guidelines for the installation of the Terminator ZP-Ambient-WP Kit. For translations other than English and local language translation provided here, please contact Thermon. The English language installation procedure shall govern.
Kit Contents
Item | Quantity | Description |
---|---|---|
1 | 1 | Expediter Assembly |
Support Cap with O-Ring
Threaded Grommet Compressor Grommet
Support Base with O-Ring
2| 1| Junction Box Lid
3| 1| Junction Box Base with O-Ring
4| 1| Nut
5| 1| Banding
6| 1| Terminal Blocks with DIN Rail
(Refer to terminal specifications for maximum allowable wire size)
7| 1| Junction Box Cord
8| 2| Blind Plug
9| 1| Bracket
10| 3| Screws
11| 3| Washers
12| 1| Ambient Temperature Sensor
Order Separately
PETK Power and End Termination Kits (per cable)
PETK-1 | for RSX, VSX-HT, BSX |
---|---|
PETK-2 | for KSX, HTSX, USX |
PETK-3 | for HPT, FP |
Item | Quantity | Description |
---|---|---|
1 | 1 | RTV Tube |
2 | 1 | Power Connection Boot |
3 | 2 | Conductor Wire Pins |
4 | 1 | Braid Wire Pin |
5 | 1 | Ground Sleeve |
6 | 1 | End Cap |
7 | 1 | Tape Strip (PETK-3 only) |
8 | 1 | GRW-G Grommet (PETK-3 only) |
9 | 1 | End Termination Caution Label |
IEK Insulation Entry Kit (per cable)
IEK-SXL: | for RSX, VSX-HT |
---|---|
IEK-SXM | for BSX |
IEK-SXS | for KSX, HTSX, USX |
IEK-HPT | for HPT |
Dimensions
Warnings
- Due to the risk of electrical shock, arcing and fire caused by product damage or improper usage, installation or maintenance, a ground-fault protection device is required.
- Installation must comply with Thermon requirements (including form PN 50207U for Ex systems) and be installed in accordance with the regulations as per the norm EN IEC 60079-14 for hazardous areas (where applicable), or any other applicable national and local codes.
- Component approvals and performance ratings are based on the use of Thermon specified parts only.
- De-energize all power sources before opening enclosure.
- Avoid electrostatic charge. Clean only with a damp cloth.
- Keep ends of heating cable and kit components dry before and during installation.
- Minimum bending radius of heating cable is 32 mm (except HPT is 57 mm and FP is 19 mm).
- The thermostat must be protected with an IECEx/ ATEX certified max. 16A circuit breaker (fuse) on power lead.
- Individuals installing these products are responsible for complying with all applicable safety and health guidelines. Proper Personal Protective Equipment (PPE) should be utilized during installation. Contact Thermon if you have any additional questions.
Tools Required
Specific Conditions of Use
Avoid electrostatic charge. Clean only with damp cloth.
Certifications/Approvals
IP66 -50°C ≤ Ta ≤ +50°C
Ordinary & Hazardous Locations
FMG 10.0022X Ex eb mb IIC T6…T4 Gb
2 G Ex eb mb IIC T6…T4 Gb, FM 10ATEX0058X
| |
---|---|---
1. Slide appropriate IEK insulation entry kit components onto cable.| 2a.
Mounting Method 1: Secure wall mount bracket to mounting surface using pipe
band provided with kits.| 2b. Mounting Method 2: Secure wall mount bracket to
mounting surface using customer supplied screws, flat washers, and nuts.
| |
3. Mount expediter to bracket using M5 x 8 mm screws and M5 lock washers.|
4. Locate bus connection (HPT and FP only) as shown. Cut end of cable at
angle to aid in piercing grommet.
Leave additional cable for expansion as needed.| 5. Insert cable into
expeditor. Make sure bus connection (HPT and FP only) remains outside of
expediter.
Note: For HPT and FP cable, exchange grommet in Terminator with GRW-G provided
in PETK-3.
| |
6. Cut off end of cable.| 7. Terminate cable with appropriate PETK
termination kit. Refer to PETK installation instructions.| 8. Push excess
cable back through expediter. Tighten cap securely. Tape cable expansion loop
to pipe.
| |
9. Mount junction box base on expediter.
Make sure to align slots to properly orient junction box base. Tighten nut
with Terminator-LN-Tool. If mounting
horizontally, threaded gland holes must face downward.| 10. Install M25 power
gland (order separately) and M25 blind plug. For in-line splice, T-splice, or
end termination, install additional
M25 blind plug (order M25-B-EXE separately) instead of M25 power gland.| 11.
Install ambient temperature sensor.
| |
12. Install power cable.| 13. Install quick mount terminal blocks and
tighten screws (if necessary).| 14. Complete system wiring. Terminal set
screws shall be tightened to a torque value of 1.4 Nm (12.4 lb-in). See page 5
for wiring details.
| |
15. Install junction box lid and twist hand tight. Insert screwdriver into
ratchet slots located on side of junction box base.| 16. Use screwdriver to
ratchet on junction box lid. Lid will rotate 30 degrees. To remove lid, repeat
steps 15 and 16 but in the opposite direction.| 17. Install IEK insulation
entry kit to seal heating cable penetration through insulation cladding.
Wiring Details
In order to avoid EMI issues with a temperature controller, the shield of the control wire shall be connected to the instrumentation earth only. Do not connect the control wire shield in the junction box.
European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The
Netherlands • Phone: +31 (0) 15-36 15 370
Corporate Headquarters: 100 Thermon Dr • PO Box 609 San Marcos, TX
78667-0609 • Phone:512-396-5801 •
1-800-820-4328
For the Thermon office nearest you visit us at . .
.www.thermon.com
© Thermon, Inc. • Printed in U.S.A. • Information subject to change.
Form PN50852U-0222
Documents / Resources
|
THERMON PN50852U Terminator ZP-Ambient-WP Thermostat Connection
Kit
[pdf] Instruction Manual
PN50852U Terminator ZP-Ambient-WP Thermostat Connection Kit, PN50852U,
Terminator ZP-Ambient-WP Thermostat Connection Kit, ZP-Ambient-WP Thermostat
Connection Kit, Thermostat Connection Kit, Connection Kit, Kit
---|---