EXTECH DV690 High Voltage Detector User Manual

June 12, 2024
EXTECH

EXTECH DV690 High Voltage Detector

Product Overview

The Extech High Voltage Detector, Model DV690, senses the presence of AC voltage and alerts you (audibly and visibly) when you are in close proximity to live equipment and dangerous voltages. The non-contact sensor plate detects radiated electrical fields as it nears a live conductor.

Product Features

  • LED alert indicator
  • Audible buzzer
  • Buzzer mute switch
  • Function select switch
  • Slots for elastic arm strap or hot stick adaptor
  • Battery compartment
  • Belt/pocket clip
  • Neck-strap lanyard attachment slot

Product Description

Component Description
LED alert indicator Lights when voltage is detected
Buzzer mute switch Switch to mute the audible buzzer
Audible buzzer Sounds when voltage is detected
Function select switch Switch to select different functions
Slots for elastic arm strap or hot stick adaptor Slots to attach an elastic

arm strap or a hot stick
adaptor
Battery compartment| Compartment to hold batteries
Belt/pocket clip| Clip to attach the detector to a belt or pocket
Neck-strap lanyard attachment slot| Slot to attach a neck-strap lanyard

Battery Operation
To install the batteries, follow these steps:

  1. Open the battery compartment cover.
  2. Insert the batteries into the compartment, observing the correct polarity.
  3. Close the battery compartment cover securely.

Product Verification Tests
The product includes the following verification tests:

  1. Automatic Self-Test: This test is performed automatically by the product.
  2. Manual Verification Test: This test can be performed manually using the control switches.
  3. Ambient Noise Buzzer Test: This test checks the buzzer functionality in the presence of ambient noise.

Wearing the DV690
There are multiple options for wearing the detector. Choose one of the following:

  • Elastic arm strap
  • Hot stick adaptor

Using a ‘Hot Stick’
To attach the detector to a hot stick, follow these steps:

  1. Assemble the ‘Hot Stick’ attachment adaptor according to the provided instructions.
  2. Connect the adaptor to the detector.
  3. Attach the hot stick to the adaptor.

Basic Operating Steps
Refer to the user manual for detailed instructions on the basic operating steps.

Distance To Voltage Considerations
Refer to the user manual for information on distance to voltage considerations.

Specifications
Refer to the user manual for detailed product specifications.

Two-year Warranty
The product comes with a two-year warranty. Refer to the user manual for warranty terms and conditions.

Service and Support
For any service or support needs, refer to the user manual or contact our customer support team.

Introduction

Product Overview
The Extech High Voltage Detector, Model DV690, senses the presence of AC voltage and alerts you (audibly and visibly) when you are in close proximity to live equipment and dangerous voltages. The non-contact sensor plate detects radiated electrical fields as it nears a live conductor.

Product Features

  • Detects electrical fields from 100 V AC to 69 kV AC
  • Frequency bandwidth: 50 to 60 Hz
  • Bright LED alert indicator
  • Loud buzzer alarm (106 dB) with mute switch
  • Built-in safety self-test function
  • Can be held in hand or worn around the neck (supplied breakaway lanyard), clipped to a front pocket or belt, or strapped on an arm (supplied elastic strap)
  • Universal ‘hot stick’ option using the supplied adaptor
  • Detector can be placed in the supplied soft protective pouch during use
  • Durable product housing with rugged, textured hand grip
  • Battery operated
  • Supplied with a hard-shell carrying case, breakaway lanyard, arm strap, soft pouch, hot stick adaptor, clip for belt or pocket mounting, 3 x ‘AA’ batteries and instructions
  • Complies with EN 61326–1 safety standard

Product Description

Front and Back DescriptionsEXTECH-DV690-High-Voltage-Detector-
FIG-1

Figure 2.1 Product Description

  1. LED alert indicator: Lights when voltage is detected
  2. Buzzer mute switch
  3. Audible buzzer: Sounds when voltage is detected
  4. Function select switch
  5. Slots for elastic arm strap or hot stick adaptor
  6. Battery compartment screws
  7. Battery compartment cover
  8. Belt/pocket clip
  9. Neck-strap lanyard attachment slot

‘Hot Stick’ Attachment Adaptor

  1. Cylinder
  2. Cylinder screw
  3. Cylinder bracket
  4. Universal spline connector

For instructions on assembling the adaptor, connecting it to the detector, and attaching a hot stick, see Section 6, Using a Hot Stick.

Control Switches

  1. Buzzer enabled
  2. Buzzer muted
  3. Power OFF position
  4. Self-Test position
  5. NCV (non-contact voltage) detection mode

Battery Operation

The DV690 is battery powered and accepts three (3) 1.5 V ‘AA’ alkaline batteries in the rear compartment. If the detector does not audibly and visibly alert when you move the function switch to the TEST position, replace the batteries and try again. Do not use the detector if it does not power up normally.

CAUTION

  • Always install three new batteries of the same make and type.
  • Do not operate the detector if the batteries appear to be damaged, leaking, or otherwise abnormal in their appearance or odor.

Installing Batteries
The battery compartment is located on the back of the detector, as shown.

  1. Open the battery compartment by removing the two screws that secure the compartment cover.
  2. Install three (3) 1.5 V ‘AA’ alkaline batteries, observing correct polarity.
  3. Secure the battery compartment cover with the two screws.
  4. Do not operate the detector until the battery compartment is secured.

Product Verification Tests

WARNING
Before use, please perform all verification procedures, below, to ensure correct and safe operation. Failure to observe this warning can cause severe injury or death.

Automatic Self-Test

  1. Move the selector switch to the TEST position.
  2. If the detector is operating normally, the buzzer will sound and the alert LED will light.
  3. If the buzzer does not sound, or if the alert LED does not light, the detector is not operating normally. In this case, do not use the detector until you have had it evaluated and then either repaired or replaced.

Manual Verification Test

  1. Move the selector switch to the NCV position.

  2. Place a small gauge live wire (100 to 240 V AC) across the detector’s faceplate (between the LED and the buzzer speaker) and observe the behavior of the audible buzzer and visual LED alert. Placing the live wire at a slight angle on the detector’s faceplate can help the detection ability of the detector.

  3. If the buzzer sounds and the LED lights, the detector is operating normally.
    Note that the buzzer intensifies when the detected voltage increases.

  4. If either the buzzer or LED do not activate, then the detector is not functioning normally and should be evaluated and subsequently repaired or replaced.

Ambient Noise Buzzer Test
Verify that the detector’s audible buzzer is sufficient to be heard above the ambient noise in the test area. If you cannot hear the buzzer over the sound of machinery, etc. in the test area, the detector can not fully protect you. The LED will continue to visibly alert you when you are in close proximity to live voltage, however.

Wearing the DV690

The DV690 can be used by simply holding it in hand, but it may be more convenient to wear the detector so your hands are free. The detector can be worn around the neck, on an arm, or clipped to an exposed forward facing jacket pocket or belt during operation. Select the option below that is most appropriate for your application. For best results, the detector should be facing in the direction that you are facing or walking. In addition, use of the supplied protective soft pouch is recommended in dusty or wet conditions.

Options for Wearing the Detector
CAUTION
The detector should be worn on the outside of your clothing to minimize false alarm triggers from static electricity discharges.

  • Belt/Pocket clip. Attach the detector to your belt or pocket (forward-facing) using the clip on the back of the detector.
  • Neck-strap: Attach the supplied lanyard to the detector’s lanyard slot (see Section 2, Product Description) and wear it around the neck, keeping it outside of the clothing. The lanyard has a safety breakaway coupling mechanism that will detach the lanyard from the detector if it catches on a piece of machinery or other object.
  • Arm strap. Wear the detector around the arm using the supplied elastic strap. The strap feeds through the slots on the rear of the detector (see Section 2, Product Description).

Using a ‘Hot Stick’

Use of a hot stick (not supplied) allows you to safely reach into test areas with the detector that you either cannot reach or that are potentially dangerous to access. The supplied hot stick adaptor uses an industry standard ‘universal spline’ that allows the detector to attach to small or large hot sticks from a variety of manufacturers (for example, the Hastings Model HV3357).

How to Attach the Detector to a Hot Stick

  • Attach the cylinder (1) to the detector by connecting the cylinder bracket (2) to the slots on the back of the detector.
  • Remove the screw (4) from the spline neck (3), if it’s attached, and slide the universal spline neck (3) into the cylinder (1).
  • Attach the screw (4) to the cylinder (1) to secure the spline to the cylinder and then attach the hot stick to the universal spline connector (5) using a wing-bolt fastener that is typically supplied with the hot stick.

Basic Operating Steps

  1. Install batteries in the rear compartment as explained in Section 3, Battery Operation.

  2. Perform the product verification steps as described in Section 4, Product Verifications.

  3. Wear the detector, hold it in hand, or attach it to a hot stick as explained in Section 5, Wearing the DV690 and Section 6, Using a Hot Stick.

  4. Move the function switch to the NCV position to begin monitoring.

  5. Perform your normal tasks while the detector monitors your surroundings.

  6. The alert LED lights and the buzzer sounds when you are in close proximity to live conductors. Refer to Section 8, Distance to Voltage Considerations, for a guideline on approximately how close to the voltage source you’ll be when the visible and audible alarms trigger.
    CAUTION
    Static electricity can cause the DV690 to trigger; wearing the detector outside of clothing and avoiding contact with the detector will minimize false triggering.

  7. When you are finished using the detector, turn the function switch to the OFF position and store it in the supplied carry case. If the detector is to be stored for longer than 90 days, remove the batteries and store them separately

Distance To Voltage Considerations

The information provided below can help you better understand the behavior of the DV690’s alarms based on the distance you are from a variety of voltage sources.

CAUTION
This information is intended for general reference only and is not meant to replace protocols that you may have in place to ensure safety. Always proceed with caution and verify the operation of the DV690 before each use.
Refer to Figure 8.1, below, for the examples provided in this item list.

  • Residential meters (240 VAC): Distance between the DV690 and the residential meter is approximately 3.1 to 4 inches (8 to 10 cm) when the alarms trigger.
  • Medium voltage pad-mounted transformers (600 VAC): Distance between the DV690 and the transformer is approximately 10 inches (25 cm) when the alarms trigger.
  • Distribution pole (7.2 to 14.4 kV AC): Distance between the DV690 and the distribution pole is approximately 2.6 to 5 feet (0.8 to 1.5 m) when the alarms trigger.
  • Transmission pole (69 kV AC or higher): Distance between the DV690 and the transmission pole is approximately 10.8 feet (3.3 m) when the alarms trigger.

Distance To Voltage Considerations

EXTECH-DV690-High-Voltage-Detector-FIG-6

CAUTION
The illustration in Figure 8.1 is presented as a general guideline for reference purposes only. The distances are approximations and the voltages may vary by locale.

Specifications

EXTECH-DV690-High-Voltage-Detector-FIG-7

Two-year Warranty

FLIR Systems, Inc. warrants this Extech brand instrument to be free of defects in parts and workmanship for two years from date of shipment. To view the full warranty text, see the link below.
http://www.extech.com/support/warranties

Service and Support

Customer Support Telephone List: https://support.flir.com/contact
Calibration, Repair, and Returns e-mail: repair@extech.com
Technical Support: https://support.flir.com

Website
http://www.flir.com
Customer support
http://support.flir.com
Copyright
© 2021, FLIR Systems, Inc. All rights reserved worldwide.
Disclaimer
Specifications subject to change without further notice. Models and accessories subject to regional market considerations. License procedures may apply. Products described herein may be subject to US Export Regulations. Please refer to exportquestions@flir.com with any questions.

Publ. No.: NAS100064
Release: AA
Commit: 73965
Head: 73965
Language: en-US
Modified: 2021-02-22
Formatted: 2021-02-22

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals