DAIKIN BAF552AA160 High Performance Pre filter Instruction Manual

June 12, 2024
Daikin

Installation manual
High performance pre-filter DAIKIN BAF552AA160 High Performance Pre
filterInstallation manual
High performance pre-filter
BAF552AA160

About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:

  • General safety precautions:
  • Safety instructions that you must read before installing
  • Format: paper (in the box of the indoor unit)
  • Installation manual:
  • Installation instructions
  • Format: paper (supplied in the kit)

Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.

About the kit

NOTICE

  • Read this manual carefully before installation together with all documents from the documentation set, see “1 About this document” [4 2].
  • Be sure to use only the specified components delivered with the option kit when installing.
  • When the Daikin high performance pre-filter is installed, air volume, performance and operation sound of the indoor unit may be altered.
  • Only the Daikin high performance pre-filter is permitted for replacement.
  • Daikin high performance pre-filter CANNOT be used with other filters, chambers, fresh air intake kits or air discharge outlet sealing member kit (for selection of 2 or 3 way air blow).
  • Replace the filter when the filter sign is displayed on the remote controller.
  • Contact your dealer for instruction regarding installation or replacement of the filter.

2.1 Components
Make sure you have all the following part included in your kit:DAIKIN
BAF552AA160 High Performance Pre filter - partsa Daikin high performance pre-filter
b Screw
c Tie wrap
d Clamp
2.2 Compatibility
Combine the Daikin high performance pre-filter with the following indoor units:
2‒1 Model group

Group A Group B Group C Group D

FCAG35~60
FXFQ20~32
FXFA20~32| FCAG71
FCAHG71~140
FXFQ40~63
FXFA40~63| FCAG100~140
FXFQ80+100
FXFN50+112
FXFA80+100| FXFQ125
FXFA125
FXFN71

Refer to this table when performing “4.1 Field setting” [4 3].
For a full list of compatible units, refer to the option list.

Installation

3.1 Before installation
Check the “2.2 Compatibility” [4 2] before installation.
Refer to the installation and operation manual of the indoor unit and the decoration panel.
3.2 Installation site requirements of the uni

Do NOT install in places:

  • With mineral oil, or filled with oil vapour or spray, like in kitchens.
  • Where corrosive gas like sulphurous gas exists.
  • Where the humidity is ≥90% and the temperature is ≥65°C.
  • That require a high ceiling mode setting and 2/3 way blow mode setting of the indoor unit.

3.3 To install the pre-filter
Open the suction grille.

  1. Slowly lower the suction grille while pressing down on the two knobs. DAIKIN BAF552AA160 High Performance Pre filter - assembly

  2. Release the strap of the suction grille from the hook (2 locations). Open the suction grille in 45° angle.DAIKIN BAF552AA160 High Performance Pre filter - assembly 1 Remove the original air filter from suction grille.

  3. Pull the end of the original air filter diagonally down to unhook the air filter from the suction grille.

  4. Lift up the air filter and remove the original air filter from the hook on the suction grille.DAIKIN BAF552AA160 High Performance Pre filter - assembly 2 Attach Daikin high performance pre-filter.

  5. Attach 2 clamps (delivered with the kit). Do NOT overtight the screw to avoid damaging the suction grille.DAIKIN BAF552AA160 High Performance Pre filter - assembly 3

  6. Position the Daikin high performance pre-filter with airflow indicator on the high performance pre-filter frame. Point in the same direction of the airflow.DAIKIN BAF552AA160 High Performance Pre filter - assembly 4

  7. Install the Daikin high performance pre-filter securely and fix with tie wraps. The direction of the clamp should match the figure.DAIKIN BAF552AA160 High Performance Pre filter - assembly 5

  8. Cut of excess tie wraps.
    Re-install the suction grille.

  9. Perform steps 1 and 2 in reverse order to re-install the suction grille. Refer to the installation manual provided with the indoor unit and decoration panel.
    Finish the installation

  10. Perform the field setting, see “4.1 Field setting” [4 3].

  11. Perform the test run, see the installation manual of the indoor unit.
    Replacing the Daikin high performance pre-filter.

  12. Cut and remove the tie wraps and remove the Daikin high performance pre-filter.DAIKIN BAF552AA160 High Performance Pre filter - assembly 6

  13. Follow steps 6~8 to install new filter.

Configuration

4.1 Field setting
After installation of the Daikin high performance pre-filter make the following field settings:

  • Air volume setting
  • Filter sign setting

INFORMATION
Following setting are only applicable when using the BRC1H52* user interface. When using any other user interface, see the installation manual or service manual of the user interface.
Setting: Air volume setting

| Setting (1)
---|---
For model group (refer to ” 2‒1 Model group” [4 2])| M| SW| —
A| 13 (23)| 0| 03
1| 02
B| 0| 02
1| 02
C| 1| 02
D| 0| 03

Disposal

Prerequisite: Turn off the indoor unit before removing the pre-filter.

  1. While wearing protective glasses, mask and gloves open the suction grille and remove the pre-filter.
  2. Put the pre-filter in plastic bag and close tightly.

INFORMATION

  • Daikin high performance pre-filter CANNOT be renewed by washing.
  • Daikin high performance pre-filter can be used up to 12  months (2500  h). Pre-filter lifetime may vary depending on the room conditions. In rooms with lot of pollutants (smoke, pets, high traffic areas…) pre-filter may require more frequent changes.
  • When disposing the pre-filter, follow the local waste separation rules.

(1) Field settings are defined as follows:

  • M: Mode number – First number: for group of units – Number between brackets: for individual unit
  •  SW: Setting number
  • —: Value number

DAIKIN EUROPE N.V.
Zandvoordestraat 300, B-8400 Oostende, Belgium
BAF552AA160
High performance pre-filter
4P706412-1 – 2022.12
4P706412-1 2022.12
Copyright 2022 Daikin

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Daikin User Manuals

Related Manuals