Memopower 1-3KVA Uninterruptible Power Systems Instruction Manual

June 12, 2024
Memopower

Memopower 1-3KVA Uninterruptible Power Systems

Memopower-1-3KVA-Uninterruptible-Power-Systems

Product Information

The UPS system is a device that provides uninterrupted power supply to connected devices during power outages or fluctuations. It features an internal current source (batteries) and output sockets or terminals block that may be electrically live even if the system is not connected to the building wiring outlet. The UPS system operates with hazardous voltages and repairs should only be carried out by qualified maintenance personnel.

Important Safety Warning

Transportation

The UPS system should only be transported in its original package to protect against shock and impact.

Preparation

  • Condensation may occur if the UPS system is moved directly from a cold to warm environment. The system must be absolutely dry before being installed.
  • Avoid installing the UPS system near water or in moist environments, direct sunlight, or near heaters.
  • Do not block ventilation holes in the UPS housing.
  • Allow at least two hours for the UPS system to acclimate to the environment before installation.

Installation

  • Do not connect appliances or devices that would overload the UPS system (e.g. laser printers) to the UPS output sockets.
  • Avoid placing cables where people can step on or trip over them.
  • Do not connect domestic appliances such as hair dryers to the UPS output sockets.
  • The UPS system can be operated by any individual with no previous experience.
  • Connect the UPS system only to an earthed shockproof outlet that is easily accessible and close to the UPS system.
  • Use only VDE-tested, CE-marked mains cable to connect the UPS system to the building wiring outlet.
  • Use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
  • Ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA when installing the equipment.

Operation

  • Do not disconnect the mains cable on the UPS system or the building wiring outlet during operations as this would cancel the protective earthing of the system and all connected loads.
  • Before fully disconnecting the UPS system, press the OFF/Enter button to disconnect the mains.
  • Prevent fluids or foreign objects from entering the UPS system.

Maintenance, Service and Faults

  • The UPS system operates with hazardous voltages. Repairs should only be carried out by qualified maintenance personnel.
  • Before carrying out any service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
  • Only individuals who are adequately familiar with batteries and the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept away from the batteries.

All rights reserved. The information in this document is subject to change without notice.

Publish statement

Thank you for purchasing this series UPS. This series UPS is an intelligent, single phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS. With excellent electrical performance, perfect intelligent monitoring and network functions, smart appearance, complying with EMC and safety standards, The UPS meets the world’s advanced level. Read this manual carefully before installation This manual provides technical support to the operator of the equipment. Contact the nearest hazardous waste disposal station when the products or components are discarded

Important Safety Warning

Important safety instructions ­ Save these instructions Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully There exists dangerous voltage and high temperature inside the UPS. During the installation, operation and maintenance, please abide the local safety instructions and relative laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instructions. Our company will not assume the liability that caused by disobeyingsafety instructions.

Transportation
Please transport the UPS system only in the original package to protect against shock and impact.

Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or
near heater. Do not block ventilation holes in the UPS housing.

Installation
Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience. Connect the UPS system only to an earthed shockproof outlet which must be
easily accessible and close to the UPS system.
2

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.

Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.

Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the
3

ground. Before touching, please verify that no voltage is present! Batteries may cause electric shock and have a high short-circuit current. Please
take the precautionary measures specified below and any other measures necessary when working with batteries: remove wristwatches, rings and other metal objects use only tools with insulated grips and handles. When changing batteries, install the same number and same type of batteries. Do not attempt to dispose of batteries by burning them. This could cause battery explosion. Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic. Please replace the fuse only with the same type and amperage in order to avoid fire hazards. Do not dismantle the UPS system.

Symbols used in this guide
WARNING!
Riskofelectricshock
CAUTION!
Readthisinformationtoavoidequipmentdamage
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
2-1 Unpack checking
Don’t lean the UPS when moving it out from the packaging. Check the appearance to see if the UPS is damaged or not during the
4

transportation, do not switch on the UPS if any damage found. Please contact the dealer right away. Check the accessories according to the packing list and contact the dealer in case of missing parts. ` It includes: (1) UPS user’s guide (2) Software Suite CD (3) USB cable (4) Power cord (Input and output) (5) RS232 cable
2-2 Real panel view
1KVA / 1.5KVA(S/H):
2KVA(S/H):
5

3KVA(S/H):
1. Output receptacles(10A) 2. Battery Terminal 3. SNMP intelligent slot (option) 4. Network /Fax/Modem Surge Protection(option) 5. RS-232 communication port 6. AC input receptacle 7. Input circuit breaker 8. EPO(option) 9. USB(option) 10. Output receptacle(16A)
6

Installing the UPS
Rackmount installation
The Rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic Rackmount configuration with square and round mounting holes. The rail assemblies adjust to mount in 19″ racks with a distance from front to rear around 70~76 cm (27 to 30 inches) deep.
CAUTION The cabinet is heavy. Removing the cabinet from its carton
requires a minimum of two people. If installing optional EBP(S), make sure to install the EBP(S)
directly below the UPS so that all wiring between the cabinets is installed behind the front covers and inaccessible to users. NOTE Mounting rails are required for each individual cabinet
(1)To install the rail kit a) Assemble the left and right rails to the rear rails as shown in Figure1.Do not
tighten the screws. Adjust each rail size for the depth of your rack.
Figure 1 Securing the Rails
b) Select the proper size in the rack for positioning the UPS (see Figure 2). The rail occupies four positions on the front and rear of the rack.
c) Tighten four M5 Umbrella Nuts in the side of rail assembly (see Figure 1). d) Fix one rail assembly to the front of the rack with one M5×12 pan-head screw
and one M5 cage nut. Using two M5 cage nuts and two M5×12 pan-head screws, to fix the rail assembly to the rear of the rack.
7

Figure 2 Fixing the Rails
e) Repeat Steps 3 and 4 for the other rail assembly. f) Tighten the four butterfly nuts in the middle of each rail assembly. g) If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit. h) Place the UPS on a flat, stable surface with the front of the cabinet facing to
you. i) Align the mounting brackets with the screw holes on each side of the UPS and
fix with the supplied M4×8 flat-head screws(see Figure 3)
Figure 3 Installing the Mounting Brackets
j) If installing optional cabinets, repeat Step 8 and 9 for each cabinet. k) Slide the UPS and any other optional cabinets into the rack. l) Secure the front of the UPS to the rack using one M5×12 pan-head screws and
one M5 cage nuts on each side(see Figure 4).Install the bottom screw on each side through the bottom hole of mounting bracket and the bottom hole of the rail. Repeat for any optional cabinets.
Figure 4 Securing the Front of the Cabinet 8

m) Continue to the following section, “Rackmount Wiring Installation. (2)Rackmount Wiring Installation
a) Installing the UPS, including connecting the UPS internal batteries b) Connecting any Optional EBP(S)
To install the UPS
NOTE Do not make unauthorized changes to the ups; otherwise, damage may occur to your equipment and void your warranty. NOTE Do not connect the ups power cord to utility until after installation is completed. a) Remove the front cover of each UPS Press the cover side with LCD display, hold the other side and quickly extract it, then extract the other side with display. (see Fig.5) NOTE A ribbon cable connects the LCD control cover to the UPS. Do not pull on the cable or disconnect it. When remove the cover, Operate as the following right Figure shows instead of the left one. (see Fig.5)
Figure 5 Extract UPS front cover
CAUTION A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly
b) Connect the internal battery connector (see Figure6) Connect red to red, Press the connector tightly together to ensure a proper
9

connection. c) If you are installing EBPS, see the following section, “Connecting the EBP(s),” before continuing with the UPS installation.
Figure 6 Connecting the UPS Internal Batteries
d) Replace the UPS front cover. To replace the cover, verify that the ribbon cable is protected and (if EBPS are installed) the EBP cable is routed through the knockout on the bottom of the cover. Put the front cover hooks of side with display to the cover port, put another side to the other two ports, then press it until the cover and the chassis are combined tightly.
Figure 7
e) If you are installing power management software, connect your computer to one of the communication ports or optional connectivity card. For the
10

communication ports, use an appropriate cable. f) If your rack has conductors for grounding or bonding of ungrounded metal
parts, connect the ground cable (not supplied) to the ground bonding screw. See “Rear Covers” for the location of the ground bonding screw for each model. g) If an emergency power-off (disconnect) switch is required by local codes, see “Remote Emergency Power-off” (REPO) to install the REPO switch before powering on the UPS. h) Continue to “UPS Start up”.
Connecting the EBP(s)
(1) To install the optional EBP(s) for a UPS a) Remove the front cover of each EBP and UPS (see Figure 8).
It is the same with the installation of the front cover. (Refer” To install the UPS “)
Figure 8 Removing the EBP Front Cover
b) On the bottom of the UPS front cover, remove the EBP cable knockout (see Figure 9).
11

Figure 9 Removing the UPS Cable Knockout
c) For the bottom (or only) EBP, remove the EBP cable knockout on the top of the EBP front cover. See Figure 10 for the location of the top EBP cable knockout.
d) If you are installing more than one EBP, for each additional EBP remove the EBP cable knockout on the top and bottom of the EBP front cover. See Figure 10 for the location of the EBP cable knockouts.
CAUTION A small amount of arcing may occur when connecting an EBP to the UPS. This is normal and will not harm personnel. Insert the EBP cable into the UPS battery connector quickly and firmly.
e) Plug the EBP cable(s) into the battery connector(s) as shown in Figure 10. Up to four EBPS may be connected to the UPS. Connect black to black,. Press the connector tightly together to ensure a proper connection. To connect a second EBP, unclip the EBP connector on the first EBP and pull
gently to extend the wiring to the EBP connector on the second EBP. Repeat for any additional EBPs. f) Verify that the EBP connections are tight and the adequate bend radius and
strain relief exist for each cable.
12

Figure 10 Typical EBP Installation
g) Replace the EBP front cover.
To replace the cover, verify that the EBP cables are routed through the EBP cover knockouts, cover connects with the cover hook near the left side of the EBP cabinet. Repeat for each additional EBP.
It is the same with the installation of the front cover. (Refer” to install the UPS”)
h) Verify that all wires connected between the UPS and EBP(s) are installed behind the front covers and not accessible to users.
i) Return to Step4 to continue the UPS installation.
Rackmount converted to Tower Installation
1Rackmount converted to Tower plastic base installation Two plastic base brackets Flatten it after intercrossing
Intercross as following Figure:

Figure 11 plastic base installation
If an EBP is needed to be placed in the middle, the assembly of plastic base is similar (Figure 11 ).The difference is that two 1U plastic base extended boards are added in the middle.(as the following shows)

A

B
13

C

D

E

F

Figure 12 increase EBP plastic base installation

The installation between UPS and EBPS can be referred to Fig.13

14

Figure 13 The installation for UPS and battery box
Figure 14 Long backup external battery connection
a) Install the base, then place the RT UPS on the base one by one as Fig.13 shows. b) The cover installation and cable connection of the UPS and EBPS are the same as
RT. (To install the optional EBP(s) for a UPS)
2-4 UPS start up and turn off
Start up operation
(1) Turn on the UPS in line mode NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
a) Once mains power is plugged in, the UPS will charge the battery, at the moment, the LCD shows that the output voltage is 220, which means the UPS automatic ally tart the inverter. If it is expected to change to bypass model, you can Press “OFF” key.
15

b) Press and hold the ON key for more than half a second to start the UPS, then it will start the inverter.
c) Once started, the UPS will perform a self-test function, LED will light and go out circularly and orderly. When the self-test finishes, it will come to line mode, the corresponding LED lights, the UPS is working in line mode.
(2) Turn on the UPS by DC without mains power
a) When mains power is disconnected, press and hold the ON key for more than half a second to start UPS.
b) The operation of the UPS in the process of start is almost the same as that when mains power is in. After finishing the self-test, the corresponding LED lights and the UPS is working in battery mode.
Turn off operation
(1) Turn off the UPS in line mode
a) Press and hold the OFF key for more than half a second to turn off the UPS and inverter.
b) After the UPS shutdown, the LEDs go out and there is no output. If output is needed, you can set bps “ON” on the LCD setting menu.
(2) Turn off the UPS by DC without mains power
a) Press and hold the OFF key for more than half a second to turn off the UPS.
b) When turning off the UPS, it will do self-testing firstly. The LEDs light and go out circularly and orderly until there is no display on the cover.
2-5 Configuring Battery Setings
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime, configure the UPS for the correct number of EBPs, refer to Table 8 for the appropriate setting of battery numbers and type. Use the up and down scroll keys to select the number of battery strings according to your UPS configuration:

All UPS and EBP Cabinets

Number of BatteryStrings
16

UPS only (internal batteries)

1default

UPS+1EBP

3

UPS+2EBPs

5

UPS+3EBPs

7

UPS+4EBPs

9

NOTE The UPS contains one battery string; each EBP contains two battery strings.

2-6 LCD control panel

LCD control panel introduction
1LEDfrom top to bottom: “alarm”, “bypass”, “battery”, “inverter”); 2On-Line UPS LCD display;3Buttons-FUNC button/OFF button/On button.

Indicator

Status

Description

Red Yellow Yellow

On

The UPS has an active alarm or fault.

The UPS is in Bypass mode.

On

The UPS is operating normally on bypass

during High Efficiency operation.

On

The UPS is on Battery mode.

17

On

The UPS inverter is operating normally on

Green

Oline mode & Battery mode

NOTE When power on or startup , these indicators will turn on and off sequentially. NOTE On different operation modes , these indicators will indicate differently.

2-7 Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
Step 2: UPS output connection
For socket-type outputs, simply connect devices to the outlets. For terminal- type input or outputs, please follow below steps for the wiring
configuration: a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm2 power cords for 3KVA (220/230/240VAC
models). c) Upon completion of the wiring configuration, please check whether the
wires are securely affixed. d) Put the small cover back to the rear panel.
Step 3: Communication connection
Communication port:

To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When installing either SNMP or Relay card in the UPS, it will provide
18

advanced communication and monitoring options. NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software.
3. Operations

3-1 Button operation

Button ON Button
OFF Button

Function
Turn on the UPS: Press and hold ON button for at least 2 seconds to turn on the UPS.
Choosing different value: When the UPS enters the setting mode, press this button to choose the different value what you want.
Out off bypass modewhen the UPS enter to bypass mode, press and hold this button it will switch to normal mode.
Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS in battery mode. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
Down key: Press this button to display next selection in UPS setting mode.
Exit setting mode: Press this button to confirm selection and exit setting mode when LCD display the last selection in UPS setting mode.
Switch to bypass mode: When the main power is normal, press this button in 1 seconds. Then UPS will enter to bypass mode. This action will

19

be ineffective when the input voltage is out of

acceptable range.

Switch LCD message: Press this button to

change the LCD message for input voltage,

input frequency, battery voltage, output

voltage and output frequency etc.

Rotate Key:After the UPS turn on, continue to

press the button for 15 seconds and then the

LCD screen begin to rotate. Again and it will be

return!

FUNC/Rotate/Mute Button Mute the alarm: When the UPS is on battery

mode, press and hold this button for at least 5

seconds to disable or enable the alarm system.

But it’s not applied to the situations when

warnings or errors occur.

Up key: Press this button to display previous

selection in UPS setting mode.

Switch to UPS self-test mode: Press and hold

this button for 2 seconds to enter UPS self-

testing while in AC mode.

FUNC + OFF Button (+)

Setting mode: Press and hold these buttons in the same moment for 5 seconds to enter UPS setting mode.

3-2 LCD display

Part one: Rack display

There are 8 interfaces available in the LCD display.

Item

Interface Description

Content Displayed

Input voltage 01

20

Battery voltage 02

03

Output voltage

Load 04

Environment

05

Temperature

21

Firmware Version

06

& UPS model

CODE

07

(Operational status and

mode)

Alarm Code(Warming

Message)

All alarm codes are

08

present when abnormal

behavior(s) occur(s)

Part two: Tower display

After the UPS turn ON, continue to press the function key for 10 seconds , the LCD

screen begin to rotate.

LCD display with rotation function and after rotating display information content is

constant ,the LCD display information only display the direction and pattern of change.

LCD display after rotation, and then shut down, to boot, the LCD screen saved with

rotating state .

Item Interface Description

Content Displayed

22

01

Input voltage

02

Battery voltage

03

Output voltage

23

04

Load

Environment 05
Temperature

Firmware Version 06
& UPS model

CODE

07

(Operational status and

mode)

24

Alarm Code(Warming

Message)

08

All alarm codes are

present when abnormal

behavior(s) occur(s)

3-3 UPS setting
The UPS has setting functions. This user settings can be done under any kind of UPS working mode. The setting will take effect under certain condition. Below table describes how to set the UPS.
The setting function is controlled by 3 buttons (FUNC/Up ,OFF/Down, ON/Enter): FUNC/Up +OFF/Down—goes into the setting page, ON/Enter –value adjustment; FUNC/Up & OFF/Down —for choosing different pages.
After the UPS turn ON, press buttons “&” for 5 seconds and then goes into the setting interface page.
Setting saving method: After setting the project parameters, press the down button until you enter the last page of the setting, and then press the down button to automatically exit the current setting mode, and it will take effect after powering off and saving in battery mode.

Item

Settings

Content display

Mode setting

Press Enter button to change

the setting (NOR or ECO or CF).

01

Press UP button to select the

previous setting.

Press DOWN button to select

the next setting.

25

Output voltage setting

Press Enter button to change

02

the setting( 208220, 230, 240). Press UP button to select the

previous setting.

Press DOWN button to select

the next setting.

Frequency setting

Press Enter button to change

03

the setting (50 or 60Hz). Press UP button to select the

previous setting.

Press DOWN button to select

the next setting.

EOD point voltage setting (one

power-off set point)

Press the selection button P to

select different setting values

(1.75/1.84/1.92)

04

Default setting 184 (1.84V /cell)

Press the up button to select

the previous option;

Press the down button to select the next option;

EOD voltage setting

Press Func button to change the

setting(160/167/175/180.)

05

default setting 175(1.75V /cell)

Press UP button to select the
previous setting. Press DOWN button to select the next setting.
26

Bypass voltage upper limit setting

Press Enter button to change

the setting(The bypass voltage

06

upper limit range is 230-

264Vac ).

Press UP button to select the

previous setting.

Press DOWN button to select

the next setting.

Bypass voltage lower limit setting

Press Enter button to change

the setting(The bypass voltage

07

lower limit range is 176-220Vac).

Press UP button to select the

previous setting.

Press DOWN button to select

the next setting.

Mute setting

Press Enter button to change

08

the setting(ON or OFF). Press UP button to select the

previous setting.

Press DOWN button to save

and exit the setup.

BYPASS enable/disable setting

Press Enter button to change

09

the setting(ON or OFF). Press UP button to select the

previous setting.

Press DOWN button to save

and exit the setup.

27

Generator mode setting Press Enter button to change the setting(ON or OFF).
The factory default is: OFF, need

to be manually set after the

10

generator is manually connected;

Press the up button to select

the previous option;

Press DOWN button to save
and exit the setup.Pres
utton to select the
next option;

3-4 Operating Mode Description

Mode Line Mode Battery Mode
Bypass Mode

Description
The inverter green LED is on. When input AC mains is in line with the working conditions, UPS will work in line mode,charge the battery and protect the load. Both the inverter green LED and battery yellow LED is on,and the buzzer beeps once per 4 seconds. When the mains power down or instable, UPS will turn to Battery Mode at once. If the mains recovers,the UPS will transfer to line mode. If battery voltage low alarm activates, the indicator of battery LED flashes. If battery voltage reaches low limit, UPS will turn off to protect the battery. UPS will auto-restart when the mains recover.
NOTEThe back up time of Battery Mode is subject to the load and EBP numbers.
The bypass yellow LED is on.
Bypass tolerance can be set by Bypass voltage limit setting.
Under below conditions, the UPS will transfer to bypass mode:
BPS on set by user through Mode setting
, and set to ECO Mode.
Press the OFF button when on Line Mode .
Overload on Line Mode.
NOTEWhen in bypass mode , the load is not protected.

Indicator

28

ECO Mode

Both the inverter green LED and bypass yellow LED is on. When ECO enabled and the utility is in range, the UPS will work on ECO Mode. If the utility in out of ECO range but still in Line range, the UPS will transfer to Line Mode. Utility tolerance of ECO Mode can be set.

Standby mode

All LEDs turn off UPS is powered off and no output supply power, but still can charge batteries.

Fault Mode

When the UPS has fault. The warning red LED is on and the buzzer beeps. The UPS will turn to fault mode. If you turn on the UPS without the Fan and the LCD display fault codes. At the moment, you can press the OFF key to shut down the UPS when the mains power down. Confirm that there is no serious fault to turn on the UPS.

NOTE: As for corresponding information of the fault code, please refer to alarm or fault reference code.

3-5 Operational Status and Mode(s)

item

Content Displayed

2

Standby Mode

3

No Output

4

Bypass Mode

5

Utility Mode

6

Battery Mode

7

Battery Self-diagnostics

8

Inverter is starting up

9

ECO Mode

10

EPO Mode

11

Maintenance Bypass Mode

12

Fault Mode

13

Generator Mode

29

3-6 Alarm or Fault reference code

Event log

UPS Alarm Warning

Buzzer

LED

1

Rectifier Fault

Beep continuously Fault LED lit

2

Inverter fault(Including Inverter bridge is shorted)

Beep continuously

Fault LED lit

9

Fan fault

Beep continuously Fault LED lit

12

Selftest fault

Beep continuously Fault LED lit

13

Battery Charger fault

Beep continuously Fault LED lit

15

DC Bus over voltage

Beep continuously Fault LED lit

16

DC Bus below voltage

Beep continuously Fault LED lit

17

DC bus unbalance

Beep continuously Fault LED lit

18

Soft start failed

Beep continuously Fault LED lit

19

Rectification model Over Temperature

Twice per second

Fault LED lit

20

Inverter model Over Temperature

Twice per second

Fault LED lit

26

Battery over voltage

Once per second

Fault LED blinking

27

Mains Input reverse

Once per second

Fault LED blinking

28

Bypass Input reverse

Once per second

Fault LED blinking

29

Output Short-circuit

Once per second

Fault LED blinking

30

Input current limit

Once per second

Fault LED blinking

31

Bypass over current

32

Overload

33

No battery

Once per second Once per second Once per second

BPS LED blinking INV or BPS LED blinking Battery LED blinking

34

Battery under voltage

35

Battery low pre-warning

36

Over load time out

37

DC component over limit.

Once per second

Battery LED blinking

Once per second

Battery LED blinking

Once per 2 seconds Fault LED blinking

Once per 2 seconds INV LED blinking

39

Mains volt. Abnormal

40

Mains freq. abnormal

Once per 2 seconds Battery LED lit Once per 2 seconds Battery LED lit

41

Bypass Not Available

42

Bypass out of tracking range

BPS LED blinking BPS LED blinking

45

EPO Enable

Beep continuously Fault LED lit

30

4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below and the Trouble Shooting Chart.

Symptom

Possible cause

Remedy

No indication and alarm even though the mains is normal.

The AC input power is not connected well.
The AC input is connected to the UPS output.

Check if input power cord firmly connected to the mains.
Plug AC input power cord to AC input correctly.

Alarm code is shown as”33″ and battery led blinking.

The external or internal battery is incorrectly connected.

Check if all batteries are connected well.

Alarm code is shown as “26” and battery led blinking.

Battery voltage is too high or the charger is fault.

Contact your dealer.

Mains Input reverse& Bypass Alarm code is shown as “27&28″Input reverse
and FAULT led light.

Check input L/N wiring Reverse connection

Alarm code is shown as “34” and Battery voltage is too low or

battery led blinking

the charger is fault.

Contact your dealer.

Alarm code is shown as “32” and UPS is overload
INV or BYPASS led blinking.

Remove excess loads from UPS output.

Alarm code is shown as “29” and FAULT led light.

The UPS shut down automatically because short circuit occurs on the UPS output.

Check output wiring and if connected devices are in short circuit status.

Alarm code is shown as “9” and FAULT led light.

Fan fault.

Contact your dealer.

Alarm code is shown as “01,02, 15,16,17,18”

A UPS internal fault has occurred.

Battery backup time is shorter than nominal value

Batteries are not fully charged
Batteries defect

Contact your dealer.
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Contact your dealer to replace the battery.

31

Trouble Shooting Chart 32

5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.

Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

Storage

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage Temperature

Recharge Frequency

Charging Duration

-25°C – 40°C

Every 3 months

1-2 hours

40°C – 45°C

Every 2 months

1-2 hours

Options

SNMP card: internal SNMP(options)
Loosen the 2 torquescrews (on each side of thecard). Carefully insert the SNMP card and lock the screws The slot called SNMP supports the MEGAtec protocol.We advise that Net AgentII-3 port is also a tool to remotely monitorand manage any UPS system NetAgentII-3Ports supports the Modem Dial-in(PPP) function to enable the remote control via the internet when the network is unavailable. In addition to the features of a standard NetAgent Mini,NetAgent II has the option to add Net Feeler Lite to detect temperature,humidity,smoke andsecurity sensors.Thus,making NetAgent II aversatile management tool.NetAgent II also supports multiple languages and is set up for web-based auto languagedetection.

Typical topologyof the UPS NetworkManagement
33

Relaycard(options)
Mini dry contact card is used foproviding the interface for UPS peripheral monitoring. The contact signals canreflect UPS running status.The card is connected to peripheral monitoring devices via terminal board to facilitate the effective monitoring of the real-timestatus of UPS and timely feedback the statusto monitor when abnormal situation occurs(suchas UPS failure, mains interruption,UPS bypassand ect.). It is installed in the intelligent slotof the UPS.
The relay card includes 6 output ports and one input port.Please refer to thefollowing table for detail.

Pins definition of connecting terminal on the board

Relaycard electrical parameter

max

Relaycardcontact

(Max Switched Voltage) AC:120V DC:24V
(Max Switched Current) AC:1A DC:1A

34

Type AC:120V DC:5~12V
AC:1A DC:1A

Emergency Power-off (EPO) (options) EPO is used to shut down the UPS from a distance. This feature can be used for shutting down the load and the UPS by thermal relay, for instance in the event of room overtemperature. When EPO is activated, the UPS shuts down the output and all its power converters immediately. The UPS remains on to alarm the fault.
EPO Connections
NOTE Depending on user configuration, the pins must be shorted or opened to keep the UPS running. To restart the UPS, reconnect (re-open) the EPO connector pins and turn on the UPS manually. Maximum resistance in the shorted loop is 10 ohm. Always test the EPO function before applying your critical load to avoid accidental load loss.Leave the EPO connector installed onto the EPO port of the UPS even if the EPO function is not needed.
Load Segments(options) Load segments are sets of receptacles that can be controlled by power management software or through the display, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep critical equipment running while you turn off other equipment. This feature allows you to save battery power. Each UPS has two load segments:
Load Segment 1: The power shedding battery voltage of this segment can be set by LCD. Load Segment 1: The power shedding battery end of discharge(EOD).
35

Specification

MODEL PHASE

Capacity (VA/Watts)

INPUT Nominal voltage

Operating voltage range (Ambient Temp.
<40)

Low line transfer
Low line comeback
High line transfer
High line comeback

Operating frequency range** Power factor

Bypass voltage range

Generator input OUTPUT Output voltage* Power factor Voltage regulation

1KVA(S) 1KVA(H)
1000VA / 800W/900W/1000W

1.5KVA (S) 1.5KVA(H) 2KVA(S) 2KVA(H)

Single phase with ground

1500VA /

2000VA /

1200W/1350W/1500W 1600W/1800W/2000W

3KVA(S) 3KVA(H)
3000VA / 2400W/2700W/3000W

208/220/230/240VAC 176Vac±5% @100%-50% load;
110Vac±5% @50%-0% load;
186Vac±5% @100%-50% load; 120Vac±5% @50%-0% load;;
264Vac±5% @100%-50% load; 300Vac±5% @50%-0% load;
254Vac±5% @100%-50% load; 290Vac±5% @50%-0% load;
40-70Hz
0.99@100% load(Nominal Input Voltage)
Bypass high voltage point 230-264: setting the high voltage point in LCD from 230Vac to 264Vac. (Default: 264Vac)
Bypass low voltage point 176-220: setting the low voltage point in LCD from 176Vac to 220Vac. (Default: 176Vac)
Support

208/220/230/240Vac 0.8/0.9/1.0 ±1%

Line Mode (synchroni Frequency zed range)

46-54Hz or 56-64Hz

Bat. Mode

Crest factor

Harmonic distortion (THDv)

Waveform
Transfer time

AC mode <->Batt. mode
Inverter <-> bypass

Efficiency

BATTERY

Battery Type

88%(AC mode) 85%(DC mode)

12V9AH

depends on the capacity of external
batteries

(50/60±0.1)Hz 3:1
3% THDwith linear load 5% THD with non linear load
Pure Sinewave
Zero

4ms(Typical)

89%(AC mode) 86%(DC mode)

90%(AC mode) 86%(DC mode)

12V9AH 36

depends on the capacity of external
batteries

12V9AH

depends on the capacity of external
batteries

90%(AC mode) 87%(DC mode)

12V9AH

depends on the capacity of external
batteries

Numbers
Backup time Typical recharge time(standard modle)

Charging voltage

Charge current SYSTEM FEATURES

Overload

Line Mode

Batt. Mode
Short Circuit Overheat Low battery voltage EPO (optional) Audible & Visual alarms Comunication interface ENVIRONMENTAL Operating temperature Storage temperature Humidity range Altitude Noise level PHYSICAL
Dimension W×D×H (mm)

Net Weight (kg) STANDARDS Safety

EMC

2

2 3

3

3

4

4 8

6

Long run unit depends on the capacity of external batteries

4 hours recover to 90% capacity (Typical)

27.4 ±1%

1/2A

6/12A

41.0 ±1%

1/2A

6/12A

54.7±1%

1/2A

6/12A

82.1 ±1%
1/2A

6 8
109. 4±1 %
6/12A

105%~125%: UPS transfer to bypass after 1minute when the utility is normal 125%~130%: UPS transfer to bypass after 30 seconds when the utility is normal

130%: UPS transfer to bypass immediately when the utility is normal
105%~125%: UPS after 1minute shut down; 125%~130%: UPS after 10 seconds shut down;
130%: UPS immediately shut down; Hold Whole System
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately Alarm and Switch off
Shut down UPS immediately Line Failure, Battery Low, Overload, System Fault USB(or RS232), SNMPcard(optional), Relay card (optional)

040 -2555
20-90 % RH @ 0- 40°C (non-condensing)
< 1500m Less than 55dBA at 1 Meter

44032586.5

11.3

5.6

440460 86.5

1 440600 86.5

4 440460 86.5

16.5

8.1

19.5

8.5

44060086.5

26.2

8.8

IEC/EN62040-1,IEC/EN60950-1
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

  • Derate to 80% of capacity when the output voltage is adjusted to 208VAC
    ** Derate to 75% of capacity when the Input voltage frequency out of range(50/60±4Hz)
    *** Product specifications are subject to change without further notice.

37

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals