SUMMIT Tpi580 Air Velocity Meter User Guide

October 30, 2023
SUMMIT

Tpi580 Air Velocity Meter
User Guide

SUMMIT Tpi580 Air Velocity Meter -

Features

| Hot wire / Vane Combo unit.
---|---
| Smart probe : Interchangeable probe.
| Probe hot wire/vane auto recognition.
| CFM / CMM Measurement ( Volume calculate )
| Backlight
| Bluetooth LE / Apps for Android / iOS  ( Model : Tpi580BT Only )
| Auto power off ( 15 min )

Function and Accuracy

Function Description
**** Hotwire Air Range
Resolution 0.01 m/s

Accuracy

| ±( 5% + 1digit ) or
±( 1% + 1digit ) F.S
Unit| m/s, km/h, mph, fpm
Vane Air| Range| 1 m/s ~ 25 m/s
Resolution| 0.1 m/s
Accuracy| ±( 2% + 3digit )
Unit| m/s, km/h, mph, fpm
Temperature| Range| -20 °C ~ 60 °C ( -4 °F ~ 140 °F )
Resolution| 0.1 °C ( 0.1 °F)
Accuracy| ± 0.5 °C ( 0 °C ~ 45 °C )
± 1 °C ( -20 °C ~ 0°C, 45°C ~ 60°C )
± 1 °F ( 32 °F ~ 113 °F )
± 2 °F ( -4 °F ~ 32°F, 113°F ~ 140°F )
Others| Airflow(volume) calculate| CFM, CMM.
REC, HOLD| MIN, MAX, AVG, Data HOLD
Operation

environment

| -20 °C ~ 60 °C ( -4 °F ~ 140 °F ) at <75%RH
Communication| Bluetooth LE ( Tpi580BT only )
Battery| 4.5V ( AA size x 3)
Battery life time| Hot air probe : about. 30h      Vane air probe : about. 68h
Auto power off| 15 min ( if APO is active )

Key

: On / Off (Push it more than 2 sec.)
: Air Velocity unit ( m/s, km/h, fpm, mph, knots) ,Volume unit ( CMM,CFM), Temperature unit ( °C, °F ), Area unit ( in²,cm2 ,m,ft
: Record mode ( Time record mode, Point record mode ), MAX , MIN , AVG
: Backlight On / Off ( Backlight Auto off 60 Sec. ) ( Tpi580BT Only = Bluetooth Model – Bluetooth feature On / Off to push it more than 2 sec. )
: SET mode: Up feature. General mode: Data Hold
:SET mode: Down feature. General mode: Auto power On/Off enable / disable General mode: Save the air velocity and air volume between 0 ~ 299.
:SET mode: Left feature
: SET mode: Right feature. General mode: Display the saved value between 0 ~ 299.
: SET mode: Feature setting (Enter). General mode: Transfer from Air Velocity measurement to Volume (CMM,CFM) measurement. Push it again and transfer to Air Velocity measurement.
For key feature to work, hot wire probe or vane probe must be connected. Backlight and power Key always work.

LCD display

SUMMIT Tpi580 Air Velocity Meter - Fig

  • 1: Air velocity and air volume display.
    2: Enter the temperature and DUCT. Display time and Point when the Record feature started.

  • Auto Power Off feature on/off

  • Low Battery display

  • Bluetooth on – Blink. Bluetooth connect – Display continuously.

  • CMM or CFM measurement – Display x1, x10, x100. 9999900 CMM, 9999900 CFM

  • Record

  • DUCT: Round DUCT setting. Record: Point Record setting.

  • Hot wire probe

  • Vane probe

Measurement

  • Power on to push the Power key for more than 2 sec. ( Display All >Model#)

  • oPEn displays when the probe is not connected.

  • Only back light key and power key work in this condition.

  • Connect the Hot wire probe and display ‘H—d’.
    Main screen: Inverse counting for 5 sec > Hot wire warming up on Hot wire probeH — d : Hotwire warming up Delay

  • Vane Probe connect > Display the air velocity without delay.

  • Measure the air velocity.

UNIT setting

  •  Push the UNIT key.
  • SET display. Display the Air velocity unit. Change the unit to push the UP, Down key.
  • Push the Right key when the right unit blinks. CMM, CFM blink next and change to push the Up, Down key.
  • Push the Right key when the right unit blinks. The temperature unit blink next and change to push the Up, Down key.
  • Push the Right key when the right unit blinks. The area unit blink next and change to push the Up, Dow n key.
  • Push the Enter key and set the unit.

Record

  • Push the REC key.
  • SET display. Choose Point or Time to push the Up / Down key.
  • Choose Time , Point to push the Enter key.
  • Time: Push the Enter key and capture the measurement value at 1 sec interval. (Start / Stop the capture with the Enter key.)
  • Point: Capture with each Enter key.
  • Record mode: MAX > MIN > AVG with REC key.
  • Record data is cleared when your push the Left key on Record Stop.
  • Transfer from Record mode to General measurement mode to push the REC key more than 2 sec.

DUCT setting

  • Push the DUCT key.
  • Choose Free Area , Rectangle , Circular with the Up / Down key.
  • Set to push the Enter Key.
  • Choose the value with Up / Down , Left / Right key.
  • Set to push the Enter key.

** Push the Enter key on general air velocity measurement mode and it changes to air volume measurement.

  • Duct size max value
  • Unit cm : 9999
  • Unit m : 99.99
  • Unit ft : 99.99
  • Unit in : 999.9

** The max value is saved if the unit changed value is higher than max value.

Memory ( 0 ~ 299 )
Measure the air velocity and air volume on general mode or Record mode.

  • Push the MEM key.
    – CaptureTpi580 and Memory mode displays. (Data save mode)

  • Choose the address with the arrow key ( left, right, up, down ).

  • Push the Enter key.
    – Tpi580 saves the captured data to the selected address.
    – End the Memory mode. Now it is measurement mode.

When you save the measurement value on Record mode, it can be saved on Stop and saves the average value.

Memory All Clear
Push the MEM key more than 2 sec on Memory mode and Clear starts.
When Clear is done, the display changes to general measurement mode.

Escape / Cancel
The work is done with the UNIT key on Memory mode and Recall mode and now it is general measurement mode.
Memory mode is not working on “OPEN”.
It can’t recall when you recall the address without saved data.

RECALL ( 0 ~ 299 )

  • Push the RCL key.
  • Choose the Recall address with the left, right, up, down key.
  • Push the Enter key.
  • Display the saved value.

– Recall: “HOLD” and “ REC” display.
– Velocity / Volume display with Enter key.
– You can check the Duct size and type with Bluetooth.