AndyMark Lamprey2 Absolute Encoder Instructions

October 30, 2023
AndyMark

AndyMark Lamprey2 Absolute Encoder

AndyMark-Lamprey2-Absolute-Encoder-product-img

Product Lamprey2 Encoder Assembly Instructions

The Lamprey2 Encoder Assembly kit includes the following:

  • 1x 10-pin Cable
  • 1x Lamprey2 Absolute Encoder Board
  • 1x Lamprey Ring Magnet

Step 1 – Inventory your kit

Take care to keep the sensor magnet away from other strong fields. Exposure to Neodynium-style magnets can damage the target.

Step 2 – Mount The Sensor Board

The sensor should be as concentric as possible with the planned axis of rotation of the target magnet.

Use #10 socket or button head to mount the sensor board.

Step 3 – Install The Magnet

Install the magnet onto the device you wish to measure. Loctite 401 or similar quick-setting glue is recommended.

Apply glue to install the magnet.

Step 4 – Set The Air Gap

The magnet can be no closer than about 0.09 from the top surface of the board. The magnet may be placed on either side of the PCB and can be sensed through non-ferrous materials.

Step 5 – Install a 10-pin IDC cable

This sensor requires 3.3-5v DC. Power can be applied via the USB header, 5×2 header, JST header or the 0.100 header.

Connect the 10-pin IDC cable to the sensor board.

Product Lamprey2 Encoder Calibration Instructions

Step 6 – Basic Sensor Calibration

To use the sensor and receive quality measurements you must complete a calibration once the board and magnet are properly installed. There is a basic and advanced option.

6a – Hold Either Button As You Power Up

This will force the sensor into calibration mode. The sensor will flash all three status LEDs in an ascending pattern. Release the button after the light sequence completes.

6b – Rotate The Magnet Slowly

Slowly rotate the magnet through at least three complete rotations. The LEDs are now acting as a signal strength indication. They will turn solid as stronger signals are recorded…all three LEDs solid is a maximum signal. At least the red LED solid is required.

A flashing red LED indicates a failure and you should restart the procedure.

You have now finished the basic calibration…click either button once to finish. The sensor is now ready!

Step 7 – Advanced Sensor Calibration

To enter this mode do a double click at the end of step 6b.

Do an advanced calibration if you desire more precise angle outputs from the sensor. This step requires some careful inputs and is much easier if using the USB connection to view the debug messages from the sensor. During this step you’ll align the sensor to known angles. The more precisely you align the output during this step the better your result will be. A fixture or other means for locking each angle into place is highly recommended.

  1. Choose the number of calibration points desired. Each click of the button will cycle through the cal points menu. The LEDs will light to indicate the selected mode. Red = 8, Red+Green = 12, Red + Green + Blue = 24, Blue only = 36. More calibration points will yield a more linear and accurate angle measurement.
  2. Do a long press to select your desired calibration. The LEDs will begin flashing.

Lamprey2 Encoder Assembly Instructions

Step 1 — Inventory your kit

  • Take care to keep the sensor magnet away from other strong fields. Exposure to Neodynium style magnets can damage the target.

  • 1X Lamprey2 Absolute Encoder Board

  • 1X Lamprey Ring Magnet

Step 2 — Mount The Sensor Board

  • The sensor should be as concentric as possible with the planned axis of rotation of the target magnet.

Step 3 — Install The Magnet

  • Install the magnet onto the device you wish to measure. Loctite 401 or similar quick-setting glue is recommended.

Step 4 — Set The Air Gap

  • The magnet can be no closer than about 0.09” from the top surface of the board.
  • The magnet may be placed on either side of the PCB and can be sensed through non-ferrous materials.

Step 5 — Install a 10-pin IDC cable

  • This sensor requires 3.3-5v DC. Power can be applied via the
  • USB header, 5×2 header, JST header, or the 0.100” header.

Lamprey2 Encoder Calibration Instru

Step 6 — Basic Sensor Calibration

  • To use the sensor and receive quality measurements you must complete a calibration once the board and magnet are properly installed. There is a basic and advanced option.

6a — Hold Either Button As You Power Up

  • This will force the sensor into calibration mode. The sensor will flash all three status LEDs in an ascending pattern. Release the button after the light sequence completes.

6b — Rotate The Magnet Slowly

  • Slowly rotate the magnet through at least three complete rotations. The LEDs are now acting as a signal strength indication.
  • They will turn solid as stronger signals are recorded…all three LEDs solid is a maximum signal. At least the red LED solid is required.

A flashing red LED indicates a failure and you should restart the procedure

  • You have now finished the basic calibration…click either button once to finish. The sensor is now ready!

Step 7 — Advanced Sensor Calibration

  • To enter this mode do a double click at the end of step 6b.
  • Do an advanced calibration if you desire more precise angle outputs from the sensor. This step requires some careful inputs and is much easier if using the USB connection to view the debug messages from the sensor. During this step, you’ll align the sensor to known angles. The more precisely you align the output during this step the better your result will be. A fixture or other means for locking each angle into place is highly recommended.
  1. Choose the number of calibration points desired. Each click of the button will cycle through the cal points menu. The LEDs will light to indicate the selected mode. Red = 8, Red+Green = 12, Red + Green + Blue = 24, Blue only = 36. More calibration points will yield a more linear and accurate angle measurement.
  2. Do a long press to select your desired calibration. The LEDs will begin fishing.
  3. Align your sensor output to an arbitrary zero position and click either button. After each successful click during this stage, the LEDs will flash a sequence to acknowledge that the point has been recorded.
  4. Accurately rotate the sensor to your relative angle either CW or CCW, hold it in this position, and press either button. The relative angle equals (360 degrees)/(number of cal points). For an eight-position cal, your relative angle between points would be 45 degrees.
  5. Repeat step 4. for the total number of cal points chosen.
    • The sensor will only record points that are within a certain tolerance range…the sensor will quickly flash all the LEDs to indicate that you’ve attempted to select a point that is out of range.
  6. When complete the status LEDs will fill an ascending sequence and the sensor will wake into 3.3v analog output mode. You should see the always-on power LED and the blue LED illuminated. Any other LED indication means the calibration failed and you should restart.

Setting New Zero Positions

  • To set a new zero position during normal operation press and hold either user button for one second.
  • The LEDs will flash to indicate a new setting.
  • The red LED will flash when you cross the zero point to offer a visual check of the programmed location.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AndyMark User Manuals

Related Manuals