Luxpro PSPA711a PROGRAMMABLE THERMOSTAT Intallation Manual
- October 30, 2023
- LUXPRO
Table of Contents
Luxpro PSPA711a PROGRAMMABLE THERMOSTAT
View all LUXPRO thermostat manual
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only. Energizer® is a registered trademark of Eveready Battery Company, Inc. DURACELL® is a registered trademark of The Gillette Company, Inc.
COMPATIBILITY
Your PSPA711a is compatible with most 24-volt: 1-Heat / 1-Cool Gas, Oil, or Electric Heating and/or Cooling systems, including single-stage heat pumps. It cannot be used with 120-volt heating systems or 3-wire zone valves. Ask your dealer for other LUXPRO® thermostats to control those systems.
FEATURES
- PSPA711a controls a single stage of Heat and Cooling. Terminals: RH, RC, W, Y, G, B, O, C
- Large Display
- Electro-luminescent Display Backlight
- Clean Cycle® (Patent No. 6,988,671) IAQ Independently Programmable Fan
- 7-Day Programming
- 4 Periods Per Day
- Temporary Override 1-4hr (CAT24 Residential Compliant)
- Hold
- Optional Smart Recovery
- F/C Temperature Display
- 12/24 Hour Clock
- Easy Programming with LUX Speed Dial®
- Energy Usage Monitor
- Battery Free Nonvolatile Memory For All Programs And Settings
- Auto-Changeover
- Keyboard Lockout
- Temperature Offset (User Calibration)
- System or Battery Powered (or Both)
- Adjustable Temperature Differential / Cycle Rate
- Programmable Auto-Changeover Dead-Band
ELECTRICAL RATINGS
- 30V maximum (24VAC nominal)
- 1.5A maximum per terminal
- 2.0A terminal sum
CAUTION
Your thermostat is protected against normal static electric discharges. To
minimize the risk of damaging the unit in extremely dry weather, touch a
grounded metal object before touching your thermostat.
INSTALLATION
TOOLS REQUIRED
-
1 Phillips screwdriver (small)
- Drill with 3/16-in. (4.8mm) bit
- Wire stripper/cutter
LOCATION
On replacement installations, mount the new thermostat in place of the old
one, unless the conditions listed below suggest otherwise. On new
installations, follow the guidelines listed below.
- Locate the thermostat on an inside wall, about 5 ft. (1.5m) above the floor, in a room that is used often.
- Do not locate where air circulation is poor, such as in a corner or an alcove; or behind an open door.
- Do not install it where there are unusual heating conditions, such as: in direct sunlight; near a lamp, television, radiator, register, or fireplace; near hot water pipes in a wall; near a stove on the other side of a wall.
- Do not locate in unusual cooling conditions, such as: on a wall separating an unheated room; or in a draft from a stairwell, door, or window.
- Do not locate in a damp area. This can lead to corrosion that will shorten thermostat life.
- Do not install the unit until all construction work and painting have been completed.
WARNING
- Read instructions carefully before removing any wiring from an existing thermostat.
- Cabel wires before they are removed.
- Then removing wires from their terminals, ignore the color of the wires since they may not comply with any standard.
REMOVAL OF OLD UNIT
- Switch the electricity to the furnace and air conditioner OFF; then proceed with the following steps.
- Remove the cover from the old thermostat. Most are snap-on types and simply pull off. Some have locking screws on the side. These must be loosened.
- Note the letters printed near the terminals. Attach labels (enclosed) to each wire for identification. Label and remove wires one at a time. Make sure the wires do not fall back inside the wall.
- Loosen all screws on the old thermostat and remove it from the wall.
- Strip insulation 3/8 in. (9.5mm) from wire ends and clean off any corrosion.
- Fill the wall opening with non-combustible insulation to prevent drafts from affecting the thermostat.
- With each thumb on a release tab at the bottom of the body, and fingers over the top of the unit. Release the unit from its base plate by squeezing the tabs into the body.
- Separate the unit from its base plate by pulling the body outward at its bottom.
CAUTION
- Be careful not to drop the unit or disturb electronic parts.
- Leave the door closed while the body is removed from the base.
- Route the wires through the open areas in the base plate above the terminals. Hold the base against the wall, with the wires coming through. Position the base for the best appearance (to hide any marks from an old thermostat). Attach the base to the wall with the two screws provided
NOTE: If you are mounting the base to a soft material like plasterboard or if you are using the old mounting holes, the screws may not hold. Drill a 3/16-in. (4.8mm) hole at each screw location, and insert the plastic anchors provided. Then mount the base as described below.
WIRING
Using the terminal descriptions below, wiring diagrams on pages 10-11, and
your labels, determine the appropriate wiring for your system. If you are
unsure or need assistance, call the LUX
Technical Assistance Dept. (see TECHNICAL ASSISTANCE.)
TERMINAL DESCRIPTIONS
- RH: Provides power for heating terminals.
- RC: Provides power for cooling and fan terminals.
- B: Energized at any time the unit is in Heat mode.
- O: Energized at any time the unit is in Cool mode.
- W: Energized while the thermostat is calling for heat.
- Y: Energized while the thermostat is calling for cool.
- G: The fan terminal is energized at any time the thermostat attempts to turn the blower on.
- C: Usage of this terminal permits the thermostat to be powered by the system, instead of (or in addition to) batteries alone.
CONNECTING THE WIRES
Loosen wire clamp screws just enough to slide wire under the blacktop part of
the clamp. Connect stripped wire ends, by trapping it between its black clamp
and brass terminal. Then tighten its terminal screw. Tape the ends of any
unused wires.
COMPLETING YOUR INSTALLATION
Install two new Energizer® or DURACELL® “AA” size alkaline batteries at this
time. For instructions, refer to BATTERIES/MAINTENANCE. Configure your
thermostat at this time. Refer to SETUP OPTIONS. Install your thermostat on
its base. To do this hang the top of the unit by the tabs on the base, then
snap the bottom of the unit into place. Do not use unnecessary
force. If the body does not snap into place easily, remove the body, re-hang
it from the tabs, and try again. 18. Turn the power back on to your heating
and/or air conditioning system. Verify that the system and its fan are
operating properly. When set to a high temperature, the heating system should
provide warm air after a short time. Likewise, a cooling system should provide
cool air after a short time. Usually, sound from the furnace and air
conditioning units can be heard while they are running. The rush of moving air
should be heard within a short time after either has been started. Your
installation is now complete.
OPERATING BASICS
UP/DOWN CHANGE KEYS
These are the two upper keys just right of the unit’s display. They are used
to adjust set temperatures and make other setting changes.
- Pressing these keys once will adjust a setting one step in the associated direction.
- If there are many choices for a value, usually that setting will advance while holding one of these keys. Some settings though must be changed one press at a time.
SET DAY AND TIME
To set the correct time after the unit has been unpowered or after reset:
- Open the door on the front of the thermostat.
- Rotate the dial to SET DAY/TIME. The abbreviation for the day of the week will flash.
- Use the UP key to advance to the current day.
- Press NEXT to adjust the time. Time will flash.
- Use the UP/DOWN keys to set the time.
- Pressing NEXT again will toggle from Set Time to Set Day or vice versa.
- Return the dial to its RUN position.
TEMPERATURE CONTROL MODES
When a unit has first been powered up with the dial in the RUN position, your
thermostat will begin to control your heating and/or air conditioning system
according to its default program. There is a 4-position slide switch to change
temperature control modes. Slide the switch to the mode you would like to use.
HEAT
- Use HEAT mode to control your furnace and warm your home.
- In HEAT mode, HEAT is displayed right of the set temperature.
- While heating is active, HEAT will flash
COOL
- Use COOL mode to control your air conditioner, cooling your home.
- In COOL mode, COOL is displayed right of the set temperature.
- While cooling is active, COOL will flash
AUTO CHANGE (AUTO)
- Use AUTO CHANGE mode to allow your thermostat to switch between HEAT and COOL modes automatically. Slide the mode switch to AUTO and AUTO CHANGE will be displayed above the set temperature. You can determine whether your thermostat is in HEAT or COOL mode by whether HEAT or COOL is visible in the set temperature area of the unit’s display. Initially HEAT or COOL may not be active until a determination is made that HEAT or COOL is necessary.
- The programmed temperature for a given mode will be used as the set temperature for that mode.
- Pressing the UP/DOWN keys at the same time will force the unit to change modes and make the programmed set temperature the new set temperature.
OFF
- Slide the MODE switch to OFF when no heating or cooling is desired. Heating and cooling will be disabled, and the set temperature side of the display will be empty.
DEFAULT PROGRAM
As supplied by the factory, your thermostat will use its default program for
temperature control. This program and all other settings may be restored to
their default values via a SOFTWARE RESET. Please refer to the DEFAULT
TEMPERATURE PROGRAM for program times and temperatures.
HOLD
The hold is the simplest method to maintain fixed set temperatures.
- Press HOLD once to enter the permanent temperature HOLD while in RUN or OVERRIDE. HOLD will be displayed above the set temperature in the display.
- Pressing this button again will toggle HOLD off and return to RUN and the programmed set temperature.
- Changing system mode or rotating the SPEED DIAL® will also cancel a HOLD.
OVERRIDE
During RUN, set temperatures may be temporarily altered from their programmed values. Immediately after a set temperature has been altered, the 2-hour default duration may be adjusted within the range from 1 to 4 hours. The temporary set temperature(s) will be used for the duration of the OVERRIDE.
- Press either the UP or DOWN keys. In the current mode, the set temperature will begin to flash.
- Adjust the set temperature as desired.
- After a few seconds, the default 2-hour duration will flash in the time area of the display.
- Adjust the duration in 15-minute increments, from between 1 to 4 hours.
- When the duration stops flashing, the OVERRIDE has been initiated and the Set Temperature side of the display will show OVERRIDE
- The adjusted temperature will remain the set temperature in the current mode for the duration of the OVERRIDE. The temperature settings return to their program values.
- OVERRIDE may be canceled by initiating a HOLD and then canceling it, changing the position of the mode switch, or rotating the SPEED DIAL®
FAN MODES
The FAN switch controls which of three fan modes your thermostat is to use.
These modes are AUTO, CLEAN, and ON.
AUTO
AUTO mode runs the fan only to fulfill your heating and cooling requirements.
ON
ON mode runs your system fan continuously.
CLEAN CYCLE
LUX’s Clean Cycle® allows you to program a forced air system to flow air
through your system’s filter, cleaning the air in your home, even when heating
or cooling is not being utilized. In CLEAN mode the fan maintains the
programmed minimum run time; it may run additional time as required to
maintain temperature control. The algorithm used avoids additional fan time
when the minimum run time has been met over the last hour through temperature
control. Minimum fan run times are met by running one-third of the hourly
requirement at twenty-minute intervals. The default minimum fan run time is 15
minutes per hour.
DISPLAY ILLUMINATION
For visibility in the dark, your LUX thermostat incorporates an attractive
electro-luminescent display backlight.
- Press the light bulb button right of the display to illuminate it.
- Pressing this or other buttons will keep the display illuminated.
AUDIBLE BEEP
When a key is pressed, the thermostat will emit an audible beep. The beep will
terminate within 1/2 second while a button is held.
PROGRAMMING
DEFAULT TEMPERATURE PROGRAM
As supplied by the factory, the following program will be used for temperature
control in RUN MODE. This program and all other software settings may be
restored to their default values via a SOFTWARE RESET.
- Period Heat Mode Cool Mode
- Morning 6:00 AM 70°F (21°C) 6:00 AM 78°F (26°C)
- Day 8:00 AM 62°F (17°C) 8:00 AM 85°F (29°C)
- Evening 6:00 PM 70°F (21°C) 6:00 PM 78°F (26°C)
- Night 10:00 PM 62°F (17°C) 10:00 PM 82°F (29°C)
EDITING HEAT OR COOL PROGRAMS
You can change any preset times and/or temperatures to suit your schedule for
each day of the week. The four periods each day are named Morning (MORN), Day,
Evening (EVE), and Night (NITE).
WEEKDAY PROGRAMMING
To change the HEAT or COOL program:
- Set HEAT, COOL, or AUTO with the mode switch
- Rotate the dial to SET WEEKDAY PROGRAMS.
- PROGRAM, Mo, MORN, and START AT will be displayed, with the SET TIME flashing.
Programming is performed in the following order
- Mo Morn Start Time
- Mo Morn Heat Set Temperature
- Mo Morn Cool Set Temperature
- Mo Day Start Time
- Mo Day Heat Set Temperature
- …and so on until Fri Nite is fully programmed at which point pressing NEXT again will begin the list at Mo Morn Start Time. Use the UP/DOWN keys to change the start time for
this period. Press the UP/DOWN buttons to change the time in 15-minute increments. Hold the UP/DOWN button to change the time at a rate of 60 minutes/second.
One period ends at the start time of the next period. The end of one period
may not be any closer to the beginning of the next period than one 15-minute
increment. Moving a start time too close to the next start time results in the
latter time being pushed ahead too. Press NEXT to accept the displayed start
time and advance to the HEAT SET TEMPERATURE, it will flash to
show that it may be edited.
- The HEAT SET TEMPERATURE will be displayed on the right side of the display with the HEAT indicator visible.
- Edit the HEAT SET TEMPERATURE, then press NEXT to accept and advance to the COOL SET TEMPERATURE, it will flash to show that it may be edited.
- There is a minimum value that must be maintained between the HEAT SET TEMPERATURE and the COOL SET TEMPERATURE. That value is called the Dead band. Its default is 3°F. It is programmable and may be changed See ADVANCED FEATURES. If you move the heat set temperature to close to the cool set temperature the cool set temperature will move away from the heat set temperature to maintain the dead band. Conversely, the heat set temperature will move if you adjust the cool set temperature too close.
- Edit the COOL SET TEMPERATURE, then press NEXT to accept and advance to the next period
- When you have changed the Cool set temperature to your desired temperature, press NEXT to advance to the next period. Its start time will be flashing indicating that it is under edit.
- When all the periods for a day have been set, the start time for the next weekday Morning period will be displayed to begin editing the settings for that day.
- Complete programming for all weekdays and rotate the dial back to RUN to accept all current values and end the programming session.
WEEKEND PROGRAMMING
Weekend programming is identical to weekday programming except that you must
rotate the dial to SET WEEKEND PROGRAMS and the sequence of days that you may
program is Sa and Su, then repeat this two-day sequence.
CLEAN CYCLE® (IAQ FAN PROGRAMMING)
Clean Cycle® programming is similar to temperature programming. It has four
consecutive periods, which are independent of the four temperature periods.
The default setting for your systems fans CLEAN CYCLE® program requires it to
run at least 15 minutes per hour. Default Program periods are:
- Default Periods Time
- MORN 6:00 AM (6:00)
- DAY 8:00 AM (8:00)
- EVE 6:00 PM (18:00)
- NIGHT 10:00 PM (22:00)
To edit the CLEAN CYCLE® program
- Move the Fan switch to CLEAN.
- Rotate the dial to AIR FILTER
- Press HOLD for 2 seconds.
- PROGRAM, FAN, START AT, MO (day), and MORN (period) will all be visible. The current start time will flash in the time area.
Programming is performed in the following order
- Mo Morn Start Time
- Mo Morn Minimum ON Time
- Mo Day Start Time
- Mo Day Minimum ON Time
- …and so on until Sun Night is fully programmed at which point pressing NEXT again will begin the list at Mo Morn Start Time.
- Press UP/DOWN to change the start time for this period in 15-minute increments. Hold the UP/DOWN button to change the time at a rate of 60 minutes/second
- Press the NEXT to accept the start time, and advance to set the minimum fan on time per hour. The current minimum fan run time will flash with MIN/HR.
- Press UP/DOWN to alter the minimum ON Time setting by 3 minutes. Time can be adjusted from 0 to minutes to 60 minutes in increments of 3 minutes. Set 0 MIN/HR to allow AUTO control for particular periods while CLEAN is used in others. Set the fan duration to 60 MIN/HR to run the fan continuously for this period.
- Press NEXT to advance to the next period. After the four program periods of day have been programmed,, pressing NEXT will advance to the following day’s MORN period.
- One period ends at the start time of the next period. The end of one period may not be any closer to the beginning of the next period than one 15-minute increment. Moving a start time to close to the next start time results in the latter time being pushed ahead too.
- Rotate the dial away from the SET FAN PROGRAMS/AIR FILTER position to exit fan programming.
COPY
Pressing COPY will copy the previous day’s temperature or fan program into the
current day and advance the thermostat to the beginning of the next day.
KEYBOARD LOCK
To prevent tampering Press NEXT, NEXT, NEXT, HOLD This sequence of keys will
lock and unlock all settings and programs. When locked, a padlock icon will be
visible above the time/temperature area of the display.
FILTER MONITOR
Your thermostat can alert you that your system’s air filter should be changed,
by displaying FILTER in the time-temperature display area once the system’s
fan has run the number of hours specified by this setting’s limit. The
presence of the word FILTER on the screen will not affect the operation of the
thermostat. If equipped, the filter is located in your heating/cooling
equipment.
FILTER USAGE
To view the number of hours the thermostat has activated the fan since the
last timer reset:
- Rotate the dial to the AIR FILTER position. The current filter usage will be shown with HRS FILTER
- To reset the timer to 0. press UP or DOWN once. Pressing UP or DOWN again will toggle between 0 and the current value. The value in the display when you exit this mode will be the value retained in memory. Leave the value at 0 to reset the timer.
- To exit the AIR FILTER mode, rotate the dial to another position.
FILTER LIMIT
This general rule will provide you with a good estimate of your filter’s life
in hours. Assume that the fan will run at 1/3 duty cycle or 8 hours per day.
Common 90-day filters are then good for 90*24/3=720 hours of use. This is the
default limit value. Setting the filter counter limit to 0000 will disable the
change filter indicator. Valid entries are from 0 to 2000hrs. To set the
number of hours of filter use before replacement is indicated:
- Rotate the dial to the AIR FILTER position. The current filter usage will be shown with HRS FILTER
- Hold NEXT for 2 seconds. The Filter limit will be displayed.
- Refer to your Air Filter package to determine your filter’s recommended life. If given in days, multiply by 8 to find the recommended setting in hours of filter usage.
- Use UP/DOWN keys to adjust the filter limit in 10-hour increments to the recommended value.
- Rotate the dial to RUN to finish this setting.
ENERGY USAGE
Your thermostat records the total number of hours the thermostat has activated
heating and cooling with six separate timers. They measure:
- Today’s cumulative heating time
- Yesterday’s cumulative heating time
- Total cumulative heating time
- Today’s cumulative cooling time
- Yesterday’s cumulative cooling time
- Total cumulative cooling time
To view HEAT or COOL energy usage
- Slide the mode switch to HEAT or COOL.
- Rotate the dial to the ENERGY USAGE position, to review today’s usage. HRS USAGE, Mode, and Current Days are all shown along with the usage value.
- Press NEXT to review yesterday’s usage.
- Press NEXT again to review Total usage. The Total timer may be changed to zero by pressing UP or DOWN while the Total time is displayed. To restore the count, press UP or DOWN again.
- To finish the review and/or reset of this mode’s energy monitor, rotate the dial to another mode, the current values will be the values retained in memory. Leave the value at 0 to reset the cumulative timer.
CALIBRATION OFFSET
Your thermostat is accurately calibrated at the factory to within ±1°F An
offset value up to ±5°F may be added to the temperature value that the
thermostat measures. This may allow you to match this thermostat to another.
To change this offset from its default value of 0:
- Open the door on the front of the thermostat.
- Rotate the dial to SET DAY/TIME.
- Simultaneously press NEXT and HOLD. The temperature Offset value will flash.
- Use the UP/DOWN keys to adjust the offset value.
- Return the dial to its RUN position to accept the new value.
RESET
Your thermostat has two RESET buttons. The Software RESET is on the front of
the thermostat behind the door. It is labeled RESET. HARDWARE RESET is on the
rear of the circuit board.
HARDWARE RESET
Use this small white button labeled H_RST after changing the Setup Option
Jumper positions to effect the changes. The Hardware RESET turns Heat, Air,
and Fan off, resets the units’ clock, and reads the Setup Option jumper
positions, before initiating normal operation.
SOFTWARE RESET
Use this feature to make all settings and programs their default values The
Software RESET button turns Heat, Air and Fan off, resets the units’ clock and
reads the Setup Option jumper positions. It then makes all settings and
programs their default values before initiating normal
operation.
NO T E : Pressing this button will overwrite your program and install the
default values of all temperature programs and setup values into the unit’s
nonvolatile memory. To ease reprogramming later, record your thermostat’s
programs and settings in the table provided before using this button. (See
Page 12.)
TEMPERATURE VARIATION / SWING
Your thermostat works by turning your heating or cooling system on and off
whenever the room temperature varies a certain number of degrees from the set-
point temperature. This variation is the “swing.” Your system should cycle on
about 3 to 6 times per hour. A smaller swing number increases the number of
cycles, so room temperature is more constant. A larger swing number decreases
the number of cycles, saving energy in most cases.
SWING 1 – 1st STAGE
This setting controls when the heating or cooling turns on and off.
- Swing 1 sets the temperature variation that the system allows above and below the set temperature before switching the heating or cooling unit on and off. To change this value:
- Rotate the SPEED DIAL® to ENERGY USAGE
- Press NEXT and HOLD simultaneously. The temperature section of the display shows SET TEMP SWING and 1 denoting that you are setting SWING 1. The Time section flashes the current setting.
- Select one of the 9 values from 025 to 225 with the UP/DOWN buttons. The smallest setting of 025 provides the most accurate temperature control, and the system will cycle on/off the most frequently. The largest setting of 225 provides the widest temperature differential, and the system will cycle on/off less frequently.
- Return the SPEED DIAL® to RUN
DEAD BAND
When using Auto-Changeover, the dead band provides a disallowed temperature
range between the maximum heat set temperature and the minimum cool set
temperature. the dead band may be set from 1 to 6 degrees. With auto
changeover active, the dead band set to 3°F and heat set to 70°F the minimum
allowed cool set temperature will be 73°F. If the cool set temperature is
lowered, then the heat set temperature will be lowered by the same amount
maintaining the 3°F dead band.
To change this setting:
- Set SPEED DIAL® to RUN
- Set MODE to AUTO
- Press NEXT and COPY simultaneously for 2 seconds.
- The display shows SET DEAD BAND, while the
- The time/Temperature section flashes the current setting.
- Use UP/DOWN keys to adjust the DEAD BAND in 1 degree increments.
- Press and release NEXT to return to RUN. Or, after 30 seconds the unit will automatically revert to RUN mode.
SETUP OPTIONS
There are five jumpers; each controls a setting depending on its position.
Jumpers are located on the rear of the thermostat’s circuit board. For
reference, there a table of settings and jumper positions printed there as
well. They are described here from J3, the rightmost jumper, to J7, the
leftmost jumper.
MINIMUM RUN TIME J3
The position of J3 sets the minimum length of time that the thermostat must
remain with HEAT or COOL either On or Off, before it will automatically switch
to the alternate On or Off state. This Delay prevents rapid cycling of your
system and provides equipment protection for cooling units. Switch position
OFF is a 5 minute delay, and ON is a 2-minute delay. 5 minutes is the default
setting and is good for most applications. If you feel that your system is
trying to cycle more rapidly than every 5 minutes, you may try the 2-minute
set.
CLOCK FORMAT J4
The time shown on the thermostat’s clock may be displayed in 12 or
24-hour format. Set this option to your preference.
TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) J5
The temperature may be displayed in Fahrenheit or Celsius with this option.
SMART RECOVERY J6
Smart Recovery allows your HVAC system to attempt to recover from a setback
period and reach your desired comfort temperature by the beginning of your
programmed comfort period. This jumper allows you to choose whether to use
Smart Recovery.
- An initial Smart Recovery will start 1/2 hour before the programmed comfort temperature.
- Maximum Smart recovery time is one hour.
- If enabled, Smart Recovery will initiate if:
- Recovery is valid, from an evening setback to a morning comfort or day setback to an evening comfort period
- In Heat mode, the set temperature of the comfort period must be higher than the setback period
- In Cool mode, the set temperature of the comfort period must be lower than the setback period
GAS/ELECTRIC MODE J7
This setting changes how the system’s blower fan (if applicable) is controlled
while in HEAT mode, and with the Fan switch in the AUTO position. This setting
does not affect fan operation while in COOL mode. When set to “Gas”, the fan
is controlled solely by the heating system itself. When set to “Electric”, the
fan is controlled directly by the thermostat. NOTE: If your blower fan does
not operate properly after installation, move the Gas / Electric option to the
“Electric” setting.
REPOSITIONING JUMPERS
Use the table on Page 12 to determine the jumper position corresponding to the
option you desire. Th table is also printed on the circuit board. If necessary
change the jumper position by pulling it straight off the pins it covers.
Replace the jumper over one pin for OPEN, or both pins for CLOSED. When all
changes have been made, press the Hardware Reset Button. See
HARDWARE RESET. These jumpers are located inside the thermostat on the the
rear of its circuit board. To access them remove the unit from the wall by
pressing up on the thumb latch at the bottom of the thermostat, and swinging
the body up and away to separate them. To change a setting, the jumper must be
repositioned and a Hardware reset must be performed. See HARDWARE RESET.
BATTERIES/MAINTENANCE
Depending on your installation, your unit may require batteries to control
your HVAC system. Replace your thermostat batteries at least once a year or
when the battery symbol appears in the display.
BATTERY INSTALLATION
-
Remove fresh batteries from their carton.
-
Remove the body of the thermostat from the wall as described in the installation.
-
Remove the used batteries if present and replace them within 90 seconds to avoid having to reset the day and time.
-
Install two new “AA” size Energizer® or Duracell® alkaline batteries. Observe the polarity marking shown in the battery compartment.
W A R N I N G: Replace your thermostat’s batteries with new Energizer or Duracell alkaline batteries at least once a year or when the battery symbol appears in the display. Use of high-quality alkaline batteries is absolutely required for your thermostat to operate properly. -
Re-hang on its base plate as described in the installation.
TECHNICAL ASSISTANCE
If you have any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. If you require assistance, please contact our Technical Assistance Department at 856-234-8803 during regular business hours between 8:00 AM and 4:30 PM Eastern Standard Time, Monday through Friday. You can also, receive technical assistance online anytime day or night at http://www.luxproproducts.com. Our website offers you answers to the most common technical questions, and also permits you to email your questions to our technical support staff at your convenience.
WARRANTY
Limited Warranty: If this unit fails because of defects in materials or
workmanship within three years of the date of original purchase, LUX will, at
its option, repair or replace it. This warranty does not cover damage by
accident, misuse, or failure to follow installation instructions. Implied
warranties are limited in duration to three years from the date of the
original purchase. Some states do not allow limitations on how long an implied
warranty lasts, so the above limitation may not apply to you. Please return
malfunctioning or defective units to the location from which the purchase was
made, along with proof of purchase. Please refer to “TECHNICAL ASSISTANCE”
before returning the thermostat. Purchaser assumes all risks and liability for
incidental and consequential damage resulting from the installation and use of
this unit. Some states do not allow the exclusion of incidental or
consequential damages, so the
above exclusion may not apply to you. This warranty gives you specific legal
rights and you may also have other rights which vary from state to state.
Applicable in the U.S.A. and Canada only
12 WIRING DIAGRAMS
WIRING DIAGRAM NOTES
- Dashed lines are optional.
- An optional common wire allows the system to power the thermostat.
- Use “B” or “O” wire – but not both in heat pump systems. Generally, neither is required in a conventional system.
- If “Y” and “C” wires are both present, then “C” is a common wire.
- If a “B” wire in your system is a common wire then connecting it to the B terminal may cause damage to your system.
WARNING: THIS IS A LOW-VOLTAGE THERMOSTAT (24 volts). A SERIOUS RISK OF FIRE EXISTS IF YOU CONNECT THIS THERMOSTAT TO A LINE VOLTAGE APPLICATION (typically 115 or 230 volts). IF UNCERTAIN ABOUT THE VOLTAGE CONSULT A PROFESSIONAL ELECTRICIAN.
WIRING DIAGRAM NOTES
- Dashed lines are optional.
- An optional common wire allows the system to power the thermostat.
- Use “B” or “O” wire – but not both in heat pump systems. Generally neither are required in a conventional system.
- If “Y” and “C” wires are both present, then “C” is a common wire.
- If a “B” wire in your system is a common wire then connecting it to the B terminal may cause damage to your system.
WARNING: THIS IS A LOW-VOLTAGE THERMOSTAT (24 volts). A SERIOUS RISK OF FIRE EXISTS IF YOU CONNECT THIS THERMOSTAT TO A LINE VOLTAGE APPLICATION (typically 115 or 230 volts). IF UNCERTAIN ABOUT THE VOLTAGE CONSULT A PROFESSIONAL ELECTRICIAN.
USER PROGRAM TABLE
To ease reprogramming later, record your thermostat’s programs and settings in
the table provided below.| DAY| PERIOD| HEAT| COOL
---|---|---|---|---
TIME| TEMP.| TIME| TEMP.
** THURS| MORN| | | |
DAY| | | |
DAY| PERIOD| HEAT| COOL| EVE| | | |
TIME| TEMP.| TIME| TEMP.| NIGHT| | | |
** MON| MORN| | | | | FRI| MORN| | | |
DAY| | | | | DAY| | | |
EVE| | | | | EVE| | | |
NIGHT| | | | | NIGHT| | | |
TUES| MORN| | | | | SAT| MORN| | | |
DAY| | | | | DAY| | | |
EVE| | | | | EVE| | | |
NIGHT| | | | | NIGHT| | | |
WED| MORN| | | | | **** SUN| MORN| | | |
DAY| | | | | DAY| | | |
EVE| | | | | EVE| | | |
NIGHT| | | | | NIGHT| | | |
JUMPER TABLE
MERCURY WARNING AND RECYCLING NOTICE
Mercury is considered to be a hazardous material. If this product is replacing
a thermostat that contains mercury in a sealed tube, contact your local waste
management authority for instructions regarding recycling and proper disposal.
It may be unlawful in your state to place it in the trash.
Luxpro PSPA711a PROGRAMMABLE THERMOSTAT Intallation Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>