Lenovo RT11kVA 6U Rack or Tower Uninterruptible Power Supplies G2 User Guide

October 30, 2023
Lenovo

Lenovo RT11kVA 6U Rack or Tower Uninterruptible Power Supplies G2

Lenovo-RT11kVA-6U-Rack-or-Tower-Uninterruptible-Power-
Supplies-G2-product

Product Information

The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 is a compact and efficient power protection system designed to safeguard the high availability of Lenovo server environments. It offers extended power protection with increased efficiency and simplified power management, with efficiency ratings of up to 98%. The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required. The 6U Rack or Tower UPS-G2 units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique to significantly extend battery service life and optimizes recharge time, compared to traditional charging methods. They also come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades. Additionally, the UPS Manager software integrates seamlessly with major virtualization platforms, enabling you to view and manage your entire power system from your current dashboard.

Product Usage Instructions

The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 can be installed in a data center rack cabinet or can be used as a tower UPS unit in an office or distributed IT environment where extended power protection is required. The UPS unit ships with a power module, a battery module, a Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired power cables for connections to the power module’s terminal block. The accessory kit that comes with the UPS unit includes the following items: Power Module, Extended battery module (EBM), Network Management Card (2) brackets for 19′ mounting (2), Rack-mounting kit, Serial cable, USB cable (2), Supports for tower mounting, Link plate, Safety instructions, and Quickstart guide.  The Extended Battery Modules are shipped with an accessory kit that contains the following items: Rack-mount kit, Tower kit, EBM power cable, and EBM detection cable. For more information on ordering feature codes, CTO, LFO, and part number codes for the 6U Rack or Tower UPS-G2 models and options, please refer to Table 1 and Table 2 in the product manual.

RT11kVA 6U Rack or Tower Uninterruptible PowerSupplies-G2

Product Guide

The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 offerings provide extended power protection with increased efficiency and simplified power management to safeguard high-availability of Lenovo server environments. With efficiency ratings of up to 98%, these compact 6U rack or tower designs can help reduce energy usage without compromising performance or reliability. The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required. The 6U Rack UPS-G2 unit (RT11kVA) is shown in Figure 1 Figure 1. RT11kVA 6U Rack UPS-G2 unit (Power module (top) and Battery module (bottom)) Did you know? 6U Rack or Tower UPS-G2 units feature Advanced Battery Management (ABM) technology that uses a unique three- stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging methods. 6U Rack or Tower UPS-G2 units come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades. 6U Rack or Tower UPS-G2 units come standard with UPS Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.

Ordering information

The following tables show the orderable feature code, CTO, LFO and part number codes for the 6U Rack or Tower UPS-G2 models and options.
Table 1. Ordering feature code, CTO and LFO model

Description Feature code CTO LFO

UPS unit
IBM RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)| BV3E| 7DD5CTO4WW| 7DD5A00AWW
Extended Battery Modules (EBM)
8kVA/11kVA 3U Rack or Tower Extended Battery Module-G2| BV3F| 7DD5CTO4WW| 7DD5A00BWW

Table 2. Ordering feature code and Part number option

Description Feature code Part number
Environmental Monitoring Probe-G2 BV3H 4XF7A87625
  • The RT11kVA 6U Rack or Tower UPS-G2 model ships standard with the Network Management Card (NMC), software license for IPM and EMP.

The RT11kVA 6U Rack or Tower UPS-G2 model includes the following items:

  • A power module
  • A battery module
  • A Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired
  • power cables for connections to the power module’s terminal block
  • An accessory kit that contains the following items:
    • Power Module
    • Extended battery module (EBM)
    • Network Management Card
    • (2) brackets for 19’ mounting
    • (2) Rack-mounting kit
    • Serial cable
    • USB cable
    • (2) Supports for tower mounting
    • Link plate
    • Safety instructions
  • Quickstart guide

The Extended Battery Modules are shipped with the following items:

  • An accessory kit that contains the following items:
    • Rack-mount kit
    • Tower kit
    • EBM power cable
    • EBM detection cable
  • Documentation package

The RT11kVA 6U Rack or Tower UPS-G2 units have a hardwired terminal block connector for AC input power.

  • All 6U Rack or Tower UPS-G2 models come standard with a NMC included with the models.

Network Management Card (NMC)
The NMC provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPS Power Manager UPM software. Figure below shows the UPS NMC.

Figure 2. UPS Network Management Card
The NMC includes the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH

  • Simultaneous shutdown of protected servers
  • Configuration of automatic email messages in response to UPS alarms and to transmit reports
  • Customizable actions, including automatic shutdown if there is an extended power failure with
  • standard UPS Power Protector software
  • Control of UPS on/off switching with a web browser
  • Adjustment and control of load segments through the HTML interface, including sequential starting of
  • the installation and optimization of backup time by shutting down non-priority systems
  • Automatic date and time adjustment through an NTP server
  • Dual stack IP v4/IP v6
  • Recording of events and measurements in the card log
  • Data and event logging in the nonvolatile memory
  • Card firmware update through the network 10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
  • Measurement of humidity and temperature with the Environmental Monitoring Probe (EMP)

Environmental Monitoring Probe (EMP)

EMP (part number 4XF7A87625) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown below.

Figure 3. Environmental Monitoring Probe
The Environmental Monitoring Probe has the following features:

  • Monitors temperature, humidity, and status of two user-provided contact devices or sensors
  • Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable that is included with the EMP)
  • Can be located up to 20 m (65.6 ft) from the UPS
  • Measures ambient temperatures between 0 – 80 °C (32 – 176 °F), with an accuracy of ±1 °C (33.8° F)
  • Measures relative humidity between 10 – 90%, with an accuracy of ±5%
  • Displays temperature, humidity, and contact closure status through a Web browser
  • Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
  • Stores events in the NMC’s event log
  • Sends SNMP alarms to network management systems
  • Sends email notifications through SMTP

Features

A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure. In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on all sized businesses. The typical utility power is 99.9% available but that means that there can be almost 9 hours of downtime a year, not to mention brownouts and otherpower quality problems. Selecting the right UPS can help protect against these potentially costly issues. The RT11kVA 6U Rack or Tower UPS-G2 units protect against the following power problems: power failures, power sags, power surges, under-voltage, electrical line noise, over-voltage, frequency variation, switching transients, and harmonic distortion.
The RT11kVA 6U Rack or Tower UPS-G2 models offer the following features:

  • High-efficiency protection delivers more real power (Watts) in a compact tower or 6U rack design, which lowers power and cooling consumption
  • Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
    • English
    • French
    • German
    • Spanish
    • Russian
    • Portuguese
    • Italian
  • Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
  • Standard UPS Power Manager software provides effective local or remote power monitoring and
  • management for servers and virtual machines, and allows for graceful remote system shutdown
  • ABM technology significantly extends battery service life and optimizes recharge time
  • Optional external battery modules (EBMs) provide extra run time to critical systems during a prolonged power outage
  • Standard NMC provides enhanced UPS monitoring and control over the network through a standard web browser
  • Environmental Monitoring Probe provides thermal management requirements (temperature and humidity)
  • Standard Maintenance Bypass enhances availability by providing service continuity during UPS maintenance and upgrades
  • Provides dual channel communication through the USB or RS-232 port and an NMC at the same time to maximize communications flexibility
  • Flash upgrades firmware for both the UPS and the NMC, which makes it an ideal solution for remote locations
  • Includes ROO and RPO connectors to control the power of the UPS unit through a wired remote switch

Technical specifications

Table 2 lists the technical specifications for the 11kVA 6U Rack or Tower UPS-G2 models.
Table 3. Technical specifications

Specification RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)

General
Part number| 7DD5CTO4WW
Form factor| 6U Rack or Tower
Topology| Online, double conversion, sinewave output
VA/Watts rating| 11000 VA

10000 W

Efficiency (on utility power)| Online mode: Up to 94.5%

High efficiency mode: Up to 98%

Transfer time| Online mode: 0 ms (no break)

High efficiency mode: 10 ms maximum (due to loss of utility power)

Energy Star compliant| Yes
Electrical input
Input voltage| 200 – 240 V AC, 1-Phase
Specification| RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)
---|---
Input frequency| 50/60 Hz
Max input amperage| 50 A
Input connector| Hardwired terminal block
Input line cord| Onsite electrician and wiring required
Electrical output
Output voltage settings| 200/208/220/230/240 V AC
Output frequency| 50/60 Hz
Output power capacity| 200-208 V AC: 10000 VA/9000 W

220 V AC: 11000 VA/9900 W

230-240 V AC: 11000 VA/10000 W

Output connectors| 4x IEC 320-C19 (16 A) (on the MBP)
Batteries
Battery type| Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
Battery management| ABM technology or temperature-compensated charging method (user selectable), automatic battery test and deep discharge protection, and automatic recognition of external battery units
Battery replacement| Hot-swap standard and extended battery modules
External battery support| Up to 8 (PN 7DD5CTO4WW)
Typical backup times| See Table below
Communications and management
USB port (Type B)| Yes
RS-232 serial port (RJ-45)| Yes
10/100 Mbps Ethernet port (RJ-45)| Yes (on the Network Management Card)
Environmental monitoring| Environmental Monitoring Probe-G2 (4XF7A87625) connects to the Network Management Card-G2 (4C57A87624)
Management software| UPS Power Manager and UPS Power Protector
Control panel| Intelligent 5-button graphical LCD
LED indicators| Online, On Battery, Bypass, and Fault
Remote On/Off and Power Off| Remote On/Off and Remote Power Off terminal block connectors

Following table lists the expected period that the 6U Rack or Tower UPS-G2 models operates only on batteries, depending on the load.
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, andtemperature.
Table 4. 6U Rack or Tower UPS-G2 runtime chart

Load Run time, Minutes
Percentage Watts
EBMs 3x EBMs
EBMs 7x EBMs

RT11kVA 6U Rack or Tower UPS-G2 (1-phase)
25%| 2500 W| NA| 25| 60| 97| 136| 163| 184| 223| 261
50%| 5000 W| NA| 10| 25| 42| 61| 79.7| 98| 120| 139
75%| 7500 W| NA| 5.5| 15| 25| 37| 48| 61| 73| 86
100%| 10000 W| NA| 3| 10| 18| 25| 34| 42| 51| 61

Connectors and controls

The 6U Rack or Tower UPS-G2 units have a 5-button graphical LCD on the front. It provides useful information about the UPS itself, load status, events, measurements, and settings. Figure 4 shows the control panel on the front of the 6U Rack or Tower UPS-G2.Lenovo-RT11kVA-6U-Rack-or-Tower-Uninterruptible-
Power-Supplies-G2-fig-3

Figure 4. Control panel on the front of the 6U Rack or Tower UPS-G2
The following functions are available on the control panel:

  • Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
  • Measurements: Displays the output Watts/VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
  • Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
  • Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
  • Event log: Displays the stored events, selects faults, alarms and events to display, and clears events.
  • Fault log: Displays the event log and alarm history.
  • Identification: Displays the machine type, model, and serial number of the unit, and the firmware level of the UPS, including the NMC’s firmware level and IP address.

Figure below shows the rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)Lenovo-RT11kVA-6U-Rack-or-Tower-Uninterruptible-Power-
Supplies-G2-fig-4 Figure 5. Rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC) Figure below shows the rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2Lenovo-RT11kVA-6U-Rack-or-Tower-Uninterruptible-Power-
Supplies-G2-fig-5

Figure 6. Rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2

Physical specifications

The RT11kVA 6U Rack or Tower UPS-G2 Power Module has the following physical specifications (approximate):

  • Height: 260 mm (10.2 in.)
  • Width: 440 mm (17.3 in.)
  • Depth: 700 mm (27.6 in.)
  • Weight: 11kVA 86 kg (189.6 lb) The 11kVA 3U Rack or Tower Extended Battery Module has the following physical specifications
  • (approximate):
  • Height: 440 mm (17.3 in.)
  • Width: 680 mm (26.8 in.)
  • Depth: 130 mm (5.1 in.)
  • Weight: 65 kg (143 lb)

Operating environment

The RT11kVA 6U Rack or Tower UPS-G2 unit is supported in the following environments:

  • Temperature (operation): 0 – 40 °C (32 – 104 °F), with linear derating for altitude
  • Relative humidity: 0 – 95%
  • Maximum altitude (operation): 3,000 m (9,843 ft)

Agency approvals

The RT11kVA 6U Rack or Tower UPS-G2 units conform to the following regulations:

  • RoHS Compliant
  • BESC
  • CBSA
  • CE
  • cUL/CSA
  • Pvoc
  • SGS
  • UKCA
  • UL

Warranty
The 11kVA 6U Rack or Tower UPS-G2 models and the Extended Battery Module (EBM), including batteries has a 2-year limited warranty.
Management Software
Eaton’s Intelligent Power Manager (IPM2) software for disaster-avoidance applications provides the tools
you need to monitor and manage power equipment in physical or virtual environments to keep IT devices
running during a power or environmental event.
This innovative software ensures system uptime and data integrity by allowing you to remotely monitor,
manage and control devices on your network. IPM2 provides a solution that is easy to use, maintains
business continuity, and allows you to do more with less.
Intelligent Power Manager (IPM)
IPM is an easy-to-use disaster avoidance platform with sophisticated capabilities that include triggering
alerts and automating resolutions to keep applications running. IPM enables you to:

  • Leverage Eaton’s integrations with industry leaders to keep critical applications running and automate resolutions for your entire network risking potential downtime.
  • Migrate workloads to increase system uptime and minimize generator load by suspending non-critical virtual machines.
  • Power cap servers to keep critical loads running longer by limiting server power consumption.
  • Support for up to 600 devices.

The Intelligent Power Manager (IPM) offers three levels of licenses Monitor, manage and optimize. IPM Optimize is a premium offering and provides the most complete set of capabilities.
Table 5. Levels of licenses

Monitor Edition Manage Edition Optimize Edition
Choose this option if your key objective is to monitor an IT room Choose this

option if your key objective is to manage a number of UPSs and/or you are looking for basic graceful shutdown| Choose this option if you need virtualization load-shedding
Contextual visibility of power metrics and constraints| Contextual visibility of power metrics and constraints

Monitor Eaton and third-party power devices

| Contextual visibility of power metrics and constraints

Monitor Eaton and third-party power devices

Monitor Eaton and third-party power devices|  | Manage and update Eaton power devices

Define basic business continuity automation configurations with host-level actions

 |  | Simple wizard-based automation configuration
 |  | Define advanced business continuity automation configurations with VM and cluster-level actions

Maintain business continuity: Minimize operating expenses

  • Intelligent load-shedding: Increase system uptime while extending battery runtime and minimizing generator load by suspending non-critical virtual machines.
  • Site Recovery Manager failover: Reduce data recovery expenses by syncing primary and disaster-recovery sites prior to power failures.
  • Power capping on demand: Keep critical workloads running longer during a power outage by limiting server power consumption.

Eaton’s strategic alliances: integration with industry leaders
Eaton understands that power protection is only one aspect of IT environments. By partnering with the industry’s leading global IT providers, Eaton helps you harness the full power of your data center. Together with our alliance partners, Eaton aims to solve even the most complex IT challenges while continuing to provide the ultimate in-power protection.

Eaton’s Intelligent Power Manager resources:
Refer to the following resources:

  • Setup guide
  • IPM User guide
  • Intelligent Power Manager (IPM) FAQ
  • Supported

Supported servers

The RT11kVA 6U Rack or Tower UPS-G2 offerings are compatible with all ThinkSystem, System x and
ThinkServer systems and other devices that require AC power.
To determine the best fit UPS for a particular configuration, the following needs to be considered:

  • Total power load of the hardware that will be connected to the UPS
  • Number and type of outlets required
  • UPS outlet and group limitations for connecting the hardware to the UPS

To determine chassis, node and server overall power capacities, use the Power Configurator tool. The tool can be downloaded from http://support.lenovo.com/documents/LNVO-PWRCONF To determine the power draw of other devices such as storage and switching that will be attached to the UPS, refer to the products user manual for the maximum power draw. For additional technical information on the UPS line cords, outlets and grouping refer to the UPS Technical Reference, https://support.lenovo.com/docs/UM104477.
Supported rack cabinets
The RT11kVA 6U Rack or Tower UPS-G2 units can be installed in the compatible rack cabinets that are listed in Table 4.
Table 6. Rack cabinets

Part number Description
93072RX 25U Standard Rack
93072PX 25U Static S2 Standard Rack
93634PX 42U 1100mm Dynamic Rack
93634EX 42U 1100mm Dynamic Expansion Rack
93604PX 42U 1200mm Deep Dynamic Rack
93614PX 42U 1200mm Deep Static Rack
93074RX 42U Standard Rack

Related publications and links
For more information about this topic, see the following resources:

Related product families
Product families related to this document are the following:

  • Uninterruptible Power Supplies

Notices
Lenovo may not offer the products, services, or features discussed in this document in all countries. Consult your
local Lenovo representative for information on the products and services currently available in your area. Any
reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product,
program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any
Lenovo intellectual property right may be used instead. However, it is the user’s responsibility to evaluate and verify
the operation of any other product, program, or service. Lenovo may have patents or pending patent applications
covering subject matter described in this document. The furnishing of this document does not give you any license to
these patents. You can send license inquiries, in writing, to:

  • Lenovo (United States), Inc.
  • 8001 Development Drive
  • Morrisville, NC 27560
  • U.S.A.

Attention: Lenovo Director of Licensing
LENOVO PROVIDES THIS PUBLICATION ”AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some jurisdictions do not allow disclaimers of express or implied warranties in certain transactions, therefore, this statement may not apply to you. This information could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new editions of the publication. Lenovo may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time without notice. The products described in this document are not intended for use in implantation or other life support applications where malfunction may result in injury or death to persons. The information contained in this document does not affect or change Lenovo product specifications or warranties. Nothing in this document shall operate as an express or implied license or indemnity under the intellectual property rights of Lenovo or third parties. All information contained in this document was obtained in specific environments and is presented as an illustration. The result obtained in other operating environments may vary. Lenovo may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you. Any references in this publication to non-Lenovo Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this Lenovo product, and use of those Web sites is at your own risk. Any performance data contained herein was determined in a controlled environment. Therefore, the result obtained in other operating environments may vary significantly. Some measurements may have been made on development-level systems and there is no guarantee that these measurements will be the same on generally available systems. Furthermore, some measurements may have been estimated through extrapolation. Actual results may vary. Users of this document should verify the applicable data for their specific environment. © Copyright Lenovo 2023. All rights reserved.
This document, LP1723, was created or updated on May 25, 2023.
Send us your comments in one of the following ways:

This document is available online at https://lenovopress.lenovo.com/LP1723.

Trademarks

Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo in the United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at https://www.lenovo.com/us/en/legal/copytrade/.
The following terms are trademarks of Lenovo in the United States, other countries, or both:

  • Lenovo®
  • System x®
  • ThinkServer®
  • ThinkSystem®

Other company, product, or service names may be trademarks or service marks of others. RT11kVA 6U Rack or Tower Uninterruptible Power Supplies-G2

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Lenovo User Manuals

Related Manuals