Lenovo RT11kVA 6U Rack or Tower Uninterruptible Power Supplies G2 User Guide
- October 30, 2023
- Lenovo
Table of Contents
- Lenovo RT11kVA 6U Rack or Tower Uninterruptible Power Supplies G2
- Product Information
- Product Usage Instructions
- Product Guide
- Ordering information
- Features
- Technical specifications
- Connectors and controls
- Physical specifications
- Operating environment
- Agency approvals
- Supported servers
- Trademarks
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Lenovo RT11kVA 6U Rack or Tower Uninterruptible Power Supplies G2
Product Information
The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 is a compact and efficient power protection system designed to safeguard the high availability of Lenovo server environments. It offers extended power protection with increased efficiency and simplified power management, with efficiency ratings of up to 98%. The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required. The 6U Rack or Tower UPS-G2 units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique to significantly extend battery service life and optimizes recharge time, compared to traditional charging methods. They also come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades. Additionally, the UPS Manager software integrates seamlessly with major virtualization platforms, enabling you to view and manage your entire power system from your current dashboard.
Product Usage Instructions
The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 can be installed in a data center rack cabinet or can be used as a tower UPS unit in an office or distributed IT environment where extended power protection is required. The UPS unit ships with a power module, a battery module, a Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired power cables for connections to the power module’s terminal block. The accessory kit that comes with the UPS unit includes the following items: Power Module, Extended battery module (EBM), Network Management Card (2) brackets for 19′ mounting (2), Rack-mounting kit, Serial cable, USB cable (2), Supports for tower mounting, Link plate, Safety instructions, and Quickstart guide. The Extended Battery Modules are shipped with an accessory kit that contains the following items: Rack-mount kit, Tower kit, EBM power cable, and EBM detection cable. For more information on ordering feature codes, CTO, LFO, and part number codes for the 6U Rack or Tower UPS-G2 models and options, please refer to Table 1 and Table 2 in the product manual.
RT11kVA 6U Rack or Tower Uninterruptible PowerSupplies-G2
Product Guide
The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 offerings provide extended power protection with increased efficiency and simplified power management to safeguard high-availability of Lenovo server environments. With efficiency ratings of up to 98%, these compact 6U rack or tower designs can help reduce energy usage without compromising performance or reliability. The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required. The 6U Rack UPS-G2 unit (RT11kVA) is shown in Figure 1 Figure 1. RT11kVA 6U Rack UPS-G2 unit (Power module (top) and Battery module (bottom)) Did you know? 6U Rack or Tower UPS-G2 units feature Advanced Battery Management (ABM) technology that uses a unique three- stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging methods. 6U Rack or Tower UPS-G2 units come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades. 6U Rack or Tower UPS-G2 units come standard with UPS Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
Ordering information
The following tables show the orderable feature code, CTO, LFO and part number
codes for the 6U Rack or Tower UPS-G2 models and options.
Table 1. Ordering feature code, CTO and LFO model
Description | Feature code | CTO | LFO |
---|
UPS unit
IBM RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)| BV3E| 7DD5CTO4WW| 7DD5A00AWW
Extended Battery Modules (EBM)
8kVA/11kVA 3U Rack or Tower Extended Battery Module-G2| BV3F| 7DD5CTO4WW|
7DD5A00BWW
Table 2. Ordering feature code and Part number option
Description | Feature code | Part number |
---|---|---|
Environmental Monitoring Probe-G2 | BV3H | 4XF7A87625 |
- The RT11kVA 6U Rack or Tower UPS-G2 model ships standard with the Network Management Card (NMC), software license for IPM and EMP.
The RT11kVA 6U Rack or Tower UPS-G2 model includes the following items:
- A power module
- A battery module
- A Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired
- power cables for connections to the power module’s terminal block
- An accessory kit that contains the following items:
- Power Module
- Extended battery module (EBM)
- Network Management Card
- (2) brackets for 19’ mounting
- (2) Rack-mounting kit
- Serial cable
- USB cable
- (2) Supports for tower mounting
- Link plate
- Safety instructions
- Quickstart guide
The Extended Battery Modules are shipped with the following items:
- An accessory kit that contains the following items:
- Rack-mount kit
- Tower kit
- EBM power cable
- EBM detection cable
- Documentation package
The RT11kVA 6U Rack or Tower UPS-G2 units have a hardwired terminal block connector for AC input power.
- All 6U Rack or Tower UPS-G2 models come standard with a NMC included with the models.
Network Management Card (NMC)
The NMC provides convenient, over-the-network UPS remote monitoring and
management through a standard web browser or UPS Power Manager UPM software.
Figure below shows the UPS NMC.
Figure 2. UPS Network Management Card
The NMC includes the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
- Simultaneous shutdown of protected servers
- Configuration of automatic email messages in response to UPS alarms and to transmit reports
- Customizable actions, including automatic shutdown if there is an extended power failure with
- standard UPS Power Protector software
- Control of UPS on/off switching with a web browser
- Adjustment and control of load segments through the HTML interface, including sequential starting of
- the installation and optimization of backup time by shutting down non-priority systems
- Automatic date and time adjustment through an NTP server
- Dual stack IP v4/IP v6
- Recording of events and measurements in the card log
- Data and event logging in the nonvolatile memory
- Card firmware update through the network 10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
- Measurement of humidity and temperature with the Environmental Monitoring Probe (EMP)
Environmental Monitoring Probe (EMP)
EMP (part number 4XF7A87625) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown below.
Figure 3. Environmental Monitoring Probe
The Environmental Monitoring Probe has the following features:
- Monitors temperature, humidity, and status of two user-provided contact devices or sensors
- Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable that is included with the EMP)
- Can be located up to 20 m (65.6 ft) from the UPS
- Measures ambient temperatures between 0 – 80 °C (32 – 176 °F), with an accuracy of ±1 °C (33.8° F)
- Measures relative humidity between 10 – 90%, with an accuracy of ±5%
- Displays temperature, humidity, and contact closure status through a Web browser
- Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
- Stores events in the NMC’s event log
- Sends SNMP alarms to network management systems
- Sends email notifications through SMTP
Features
A UPS is a device that acts as a defensive barrier between electronic
equipment and incoming power problems. It conditions, regulates, and filters
out power disturbances to ensure a clean power source for IT equipment. A UPS
also provides battery backup if there is a power failure. In today’s high
availability server environments, unplanned power outages or line quality
irregularities can have a considerable financial impact on all sized
businesses. The typical utility power is 99.9% available but that means that
there can be almost 9 hours of downtime a year, not to mention brownouts and
otherpower quality problems. Selecting the right UPS can help protect against
these potentially costly issues. The RT11kVA 6U Rack or Tower UPS-G2 units
protect against the following power problems: power failures, power sags,
power surges, under-voltage, electrical line noise, over-voltage, frequency
variation, switching transients, and harmonic distortion.
The RT11kVA 6U Rack or Tower UPS-G2 models offer the following features:
- High-efficiency protection delivers more real power (Watts) in a compact tower or 6U rack design, which lowers power and cooling consumption
- Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
- English
- French
- German
- Spanish
- Russian
- Portuguese
- Italian
- Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
- Standard UPS Power Manager software provides effective local or remote power monitoring and
- management for servers and virtual machines, and allows for graceful remote system shutdown
- ABM technology significantly extends battery service life and optimizes recharge time
- Optional external battery modules (EBMs) provide extra run time to critical systems during a prolonged power outage
- Standard NMC provides enhanced UPS monitoring and control over the network through a standard web browser
- Environmental Monitoring Probe provides thermal management requirements (temperature and humidity)
- Standard Maintenance Bypass enhances availability by providing service continuity during UPS maintenance and upgrades
- Provides dual channel communication through the USB or RS-232 port and an NMC at the same time to maximize communications flexibility
- Flash upgrades firmware for both the UPS and the NMC, which makes it an ideal solution for remote locations
- Includes ROO and RPO connectors to control the power of the UPS unit through a wired remote switch
Technical specifications
Table 2 lists the technical specifications for the 11kVA 6U Rack or Tower
UPS-G2 models.
Table 3. Technical specifications
Specification | RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC) |
---|
General
Part number| 7DD5CTO4WW
Form factor| 6U Rack or Tower
Topology| Online, double conversion, sinewave output
VA/Watts rating| 11000 VA
10000 W
Efficiency (on utility power)| Online mode: Up to 94.5%
High efficiency mode: Up to 98%
Transfer time| Online mode: 0 ms (no break)
High efficiency mode: 10 ms maximum (due to loss of utility power)
Energy Star compliant| Yes
Electrical input
Input voltage| 200 – 240 V AC, 1-Phase
Specification| RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)
---|---
Input frequency| 50/60 Hz
Max input amperage| 50 A
Input connector| Hardwired terminal block
Input line cord| Onsite electrician and wiring required
Electrical output
Output voltage settings| 200/208/220/230/240 V AC
Output frequency| 50/60 Hz
Output power capacity| 200-208 V AC: 10000 VA/9000 W
220 V AC: 11000 VA/9900 W
230-240 V AC: 11000 VA/10000 W
Output connectors| 4x IEC 320-C19 (16 A) (on the MBP)
Batteries
Battery type| Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed,
leak-proof
Battery management| ABM technology or temperature-compensated charging method
(user selectable), automatic battery test and deep discharge protection, and
automatic recognition of external battery units
Battery replacement| Hot-swap standard and extended battery modules
External battery support| Up to 8 (PN 7DD5CTO4WW)
Typical backup times| See Table below
Communications and management
USB port (Type B)| Yes
RS-232 serial port (RJ-45)| Yes
10/100 Mbps Ethernet port (RJ-45)| Yes (on the Network Management Card)
Environmental monitoring| Environmental Monitoring Probe-G2 (4XF7A87625)
connects to the Network Management Card-G2 (4C57A87624)
Management software| UPS Power Manager and UPS Power Protector
Control panel| Intelligent 5-button graphical LCD
LED indicators| Online, On Battery, Bypass, and Fault
Remote On/Off and Power Off| Remote On/Off and Remote Power Off terminal block
connectors
Following table lists the expected period that the 6U Rack or Tower UPS-G2
models operates only on batteries, depending on the load.
Note: Battery backup times are approximate and can vary with equipment,
configuration, battery age, andtemperature.
Table 4. 6U Rack or Tower UPS-G2 runtime chart
Load | Run time, Minutes |
---|---|
Percentage | Watts |
EBMs | 3x EBMs |
EBMs | 7x EBMs |
RT11kVA 6U Rack or Tower UPS-G2 (1-phase)
25%| 2500 W| NA| 25| 60| 97| 136| 163| 184| 223| 261
50%| 5000 W| NA| 10| 25| 42| 61| 79.7| 98| 120| 139
75%| 7500 W| NA| 5.5| 15| 25| 37| 48| 61| 73| 86
100%| 10000 W| NA| 3| 10| 18| 25| 34| 42| 51| 61
Connectors and controls
The 6U Rack or Tower UPS-G2 units have a 5-button graphical LCD on the front. It provides useful information about the UPS itself, load status, events, measurements, and settings. Figure 4 shows the control panel on the front of the 6U Rack or Tower UPS-G2.
Figure 4. Control panel on the front of the 6U Rack or Tower UPS-G2
The following functions are available on the control panel:
- Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
- Measurements: Displays the output Watts/VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
- Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
- Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
- Event log: Displays the stored events, selects faults, alarms and events to display, and clears events.
- Fault log: Displays the event log and alarm history.
- Identification: Displays the machine type, model, and serial number of the unit, and the firmware level of the UPS, including the NMC’s firmware level and IP address.
Figure below shows the rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC) Figure 5. Rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC) Figure below shows the rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2
Figure 6. Rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2
Physical specifications
The RT11kVA 6U Rack or Tower UPS-G2 Power Module has the following physical specifications (approximate):
- Height: 260 mm (10.2 in.)
- Width: 440 mm (17.3 in.)
- Depth: 700 mm (27.6 in.)
- Weight: 11kVA 86 kg (189.6 lb) The 11kVA 3U Rack or Tower Extended Battery Module has the following physical specifications
- (approximate):
- Height: 440 mm (17.3 in.)
- Width: 680 mm (26.8 in.)
- Depth: 130 mm (5.1 in.)
- Weight: 65 kg (143 lb)
Operating environment
The RT11kVA 6U Rack or Tower UPS-G2 unit is supported in the following environments:
- Temperature (operation): 0 – 40 °C (32 – 104 °F), with linear derating for altitude
- Relative humidity: 0 – 95%
- Maximum altitude (operation): 3,000 m (9,843 ft)
Agency approvals
The RT11kVA 6U Rack or Tower UPS-G2 units conform to the following regulations:
- RoHS Compliant
- BESC
- CBSA
- CE
- cUL/CSA
- Pvoc
- SGS
- UKCA
- UL
Warranty
The 11kVA 6U Rack or Tower UPS-G2 models and the Extended Battery Module
(EBM), including batteries has a 2-year limited warranty.
Management Software
Eaton’s Intelligent Power Manager (IPM2) software for disaster-avoidance
applications provides the tools
you need to monitor and manage power equipment in physical or virtual
environments to keep IT devices
running during a power or environmental event.
This innovative software ensures system uptime and data integrity by allowing
you to remotely monitor,
manage and control devices on your network. IPM2 provides a solution that is
easy to use, maintains
business continuity, and allows you to do more with less.
Intelligent Power Manager (IPM)
IPM is an easy-to-use disaster avoidance platform with sophisticated
capabilities that include triggering
alerts and automating resolutions to keep applications running. IPM enables
you to:
- Leverage Eaton’s integrations with industry leaders to keep critical applications running and automate resolutions for your entire network risking potential downtime.
- Migrate workloads to increase system uptime and minimize generator load by suspending non-critical virtual machines.
- Power cap servers to keep critical loads running longer by limiting server power consumption.
- Support for up to 600 devices.
The Intelligent Power Manager (IPM) offers three levels of licenses Monitor,
manage and optimize. IPM Optimize is a premium offering and provides the most
complete set of capabilities.
Table 5. Levels of licenses
Monitor Edition | Manage Edition | Optimize Edition |
---|---|---|
Choose this option if your key objective is to monitor an IT room | Choose this |
option if your key objective is to manage a number of UPSs and/or you are
looking for basic graceful shutdown| Choose this option if you need
virtualization load-shedding
Contextual visibility of power metrics and constraints| Contextual visibility
of power metrics and constraints
Monitor Eaton and third-party power devices
| Contextual visibility of power metrics and constraints
Monitor Eaton and third-party power devices
Monitor Eaton and third-party power devices| | Manage and update Eaton power devices
Define basic business continuity automation configurations with host-level actions
| | Simple wizard-based automation configuration
| | Define advanced business continuity automation configurations with VM
and cluster-level actions
Maintain business continuity: Minimize operating expenses
- Intelligent load-shedding: Increase system uptime while extending battery runtime and minimizing generator load by suspending non-critical virtual machines.
- Site Recovery Manager failover: Reduce data recovery expenses by syncing primary and disaster-recovery sites prior to power failures.
- Power capping on demand: Keep critical workloads running longer during a power outage by limiting server power consumption.
Eaton’s strategic alliances: integration with industry leaders
Eaton understands that power protection is only one aspect of IT environments.
By partnering with the industry’s leading global IT providers, Eaton helps you
harness the full power of your data center. Together with our alliance
partners, Eaton aims to solve even the most complex IT challenges while
continuing to provide the ultimate in-power protection.
Eaton’s Intelligent Power Manager resources:
Refer to the following resources:
- Setup guide
- IPM User guide
- Intelligent Power Manager (IPM) FAQ
- Supported
Supported servers
The RT11kVA 6U Rack or Tower UPS-G2 offerings are compatible with all
ThinkSystem, System x and
ThinkServer systems and other devices that require AC power.
To determine the best fit UPS for a particular configuration, the following
needs to be considered:
- Total power load of the hardware that will be connected to the UPS
- Number and type of outlets required
- UPS outlet and group limitations for connecting the hardware to the UPS
To determine chassis, node and server overall power capacities, use the Power
Configurator tool. The tool can be downloaded from
http://support.lenovo.com/documents/LNVO-PWRCONF To determine the power draw
of other devices such as storage and switching that will be attached to the
UPS, refer to the products user manual for the maximum power draw. For
additional technical information on the UPS line cords, outlets and grouping
refer to the UPS Technical Reference,
https://support.lenovo.com/docs/UM104477.
Supported rack cabinets
The RT11kVA 6U Rack or Tower UPS-G2 units can be installed in the compatible
rack cabinets that are listed in Table 4.
Table 6. Rack cabinets
Part number | Description |
---|---|
93072RX | 25U Standard Rack |
93072PX | 25U Static S2 Standard Rack |
93634PX | 42U 1100mm Dynamic Rack |
93634EX | 42U 1100mm Dynamic Expansion Rack |
93604PX | 42U 1200mm Deep Dynamic Rack |
93614PX | 42U 1200mm Deep Static Rack |
93074RX | 42U Standard Rack |
Related publications and links
For more information about this topic, see the following resources:
- Rack & Power Infrastructure Options page
- Power and Cooling Technical References:
- Product specifications and resources – RT11kVA 6U UPS-G2 (200-240VAC):
- Installation and User’s Manual – RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC):
- 9PX11KiRTNBP (RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC))
- Network Management Card
- Network Management Card User Guide
Related product families
Product families related to this document are the following:
- Uninterruptible Power Supplies
Notices
Lenovo may not offer the products, services, or features discussed in this
document in all countries. Consult your
local Lenovo representative for information on the products and services
currently available in your area. Any
reference to a Lenovo product, program, or service is not intended to state or
imply that only that Lenovo product,
program, or service may be used. Any functionally equivalent product, program,
or service that does not infringe any
Lenovo intellectual property right may be used instead. However, it is the
user’s responsibility to evaluate and verify
the operation of any other product, program, or service. Lenovo may have
patents or pending patent applications
covering subject matter described in this document. The furnishing of this
document does not give you any license to
these patents. You can send license inquiries, in writing, to:
- Lenovo (United States), Inc.
- 8001 Development Drive
- Morrisville, NC 27560
- U.S.A.
Attention: Lenovo Director of Licensing
LENOVO PROVIDES THIS PUBLICATION ”AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER
EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some
jurisdictions do not allow disclaimers of express or implied warranties in
certain transactions, therefore, this statement may not apply to you. This
information could include technical inaccuracies or typographical errors.
Changes are periodically made to the information herein; these changes will be
incorporated in new editions of the publication. Lenovo may make improvements
and/or changes in the product(s) and/or the program(s) described in this
publication at any time without notice. The products described in this
document are not intended for use in implantation or other life support
applications where malfunction may result in injury or death to persons. The
information contained in this document does not affect or change Lenovo
product specifications or warranties. Nothing in this document shall operate
as an express or implied license or indemnity under the intellectual property
rights of Lenovo or third parties. All information contained in this document
was obtained in specific environments and is presented as an illustration. The
result obtained in other operating environments may vary. Lenovo may use or
distribute any of the information you supply in any way it believes
appropriate without incurring any obligation to you. Any references in this
publication to non-Lenovo Web sites are provided for convenience only and do
not in any manner serve as an endorsement of those Web sites. The materials at
those Web sites are not part of the materials for this Lenovo product, and use
of those Web sites is at your own risk. Any performance data contained herein
was determined in a controlled environment. Therefore, the result obtained in
other operating environments may vary significantly. Some measurements may
have been made on development-level systems and there is no guarantee that
these measurements will be the same on generally available systems.
Furthermore, some measurements may have been estimated through extrapolation.
Actual results may vary. Users of this document should verify the applicable
data for their specific environment. © Copyright Lenovo 2023. All rights
reserved.
This document, LP1723, was created or updated on May 25, 2023.
Send us your comments in one of the following ways:
-
Use the online Contact us review form found at:
https://lenovopress.lenovo.com/LP1723. -
Send your comments in an e-mail to:
comments@lenovopress.com.
This document is available online at https://lenovopress.lenovo.com/LP1723.
Trademarks
Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo
in the United States, other countries, or both. A current list of Lenovo
trademarks is available on the Web at
https://www.lenovo.com/us/en/legal/copytrade/.
The following terms are trademarks of Lenovo in the United States, other
countries, or both:
- Lenovo®
- System x®
- ThinkServer®
- ThinkSystem®
Other company, product, or service names may be trademarks or service marks of others. RT11kVA 6U Rack or Tower Uninterruptible Power Supplies-G2
References
- Lenovo Enterprise Systems Data Center Planning Portal - Lenovo Support US
- Rack & Power Infrastructure Options > Lenovo Press
- Eaton Gigabit Network Card
- lenovopress.lenovo.com/assets/images/LP1723/6U-9PX-11kVA_rackUPS_RA.png
- lenovopress.lenovo.com/assets/images/LP1723/EMP_v1.png
- RT11kVA 6U Rack or Tower Uninterruptible Power Supplies-G2 Product Guide > Lenovo Press
- Uninterruptible Power Supplies > Lenovo Press
- RT11kVA 6U Rack or Tower Uninterruptible Power Supplies-G2 > Lenovo Press
- Lenovo System x UPS Technical Reference v5.0.0 - Lenovo Support US
- Lenovo Enterprise Systems Data Center Planning Portal - Lenovo Support US
- Intelligent Power Manager Software | Remote Monitor | Eaton
- Intelligent Power Manager FAQ | IPM | Eaton | EMEA
- 9PX11KIRTNBP | Eaton 9PX UPS | Specifications | Eaton
- Copyright and Trademark Information | Lenovo US | Lenovo US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>