Operation Manual of Solar Controller SR658 for Split Solar System
Thank you for purchasing the Solar Controller SR658 for your Split Solar System. Please read the following instructions carefully before operating the product.

Safety Information

Installation and Commissioning:

  • Ensure that no damage occurs to any of the constructional fire safety measures presented in the building when laying wires.
  • Do not install the controller in rooms where easily inflammable gas mixtures are present or may occur.
  • Make sure that the permissible environmental conditions cannot be exceeded at the site of installation.
  • Before connecting the device, ensure that the power supply matches the specifications that controller requires.
  • All devices connected to the controller must conform to the technical specifications of the controller.
  • All operations on an open controller are only to be conducted cleared from the power supply. All safety regulations for working on the power supply are valid.
  • Connecting and/or all operation that require opening the controller (e.g. changing the fuse) are only conducted by specialists.

Operation

The Solar Controller SR658 is operated using the 5 buttons besides the screen:

  • Holiday button
  • SET button: confirm/selection
  • Upwards button: increase the value
  • Downwards button: reduce the value
  • ESC button return/exit: return to the previous menu

Important Information

Please note that while we have carefully checked the text and pictures of this manual and provided the best of our knowledge and ideas, there may be inevitable errors. We cannot guarantee that this manual is given in the integrity of image and text, they are just some examples, and they apply only to our own system. Incorrect, incomplete and erroneous information and the resulting damage we do not take responsibility.

Signal Description
Safety instructions in the text are marked with a warning triangle. They indicate measures which can lead to injury of person or safety risks. Small triangles are used to indicate operation steps. Notes contain important information about operation or functions.

Meaning of Icons Appeared on the Screen

  • Exceed the maximum temperature of tank
  • Running of tank emergency shutdown function
  • Running of collector emergency shutdown function
  • Running of collector cooling function
  • Running of tank cooling function
  • Running of system cooling function
  • Activating of anti-freezing function

Operation Manual of Solar Controller SR658for Split Solar System

Read the instruction carefully please before operation!
Downloaded from www.Manualslib.com manuals search engine

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Safety information

Installation and commissioning When laying wires, please ensure that no damage occurs to any of the constructional fire
safety measures presented in the building. The controller should not be installed in rooms where easily inflammable gas mixtures are
present or may occur. The permissible environmental conditions can’t be exceeded at the site of installation. Before connecting the device, please make sure that the power supply matches the
specifications that controller requires. All devices connected to the controller must conform to the technical specifications of the
controller. All operations on an open controller are only to be conducted cleared from the power
supply. All safety regulations for working on the power supply are valid. Connecting and / or all operation that require opening the controller (e.g. changing the
fuse) are only conducted by specialists.
1.2 About this manual This manual describes the installation, functions and operation of a solar controller. When installing the remaining components e.g. the solar collectors and the tank unit, please ensure to observe the appropriate installation instructions provided by each manufacturer. Installation, electrical connection, commissioning and maintenance of the device may only be performed by trained professional person. The professional person must be familiar with this manual and follow the instructions contained herein.
1.3 Liability waiver The manufacturer can’t monitor the compliance with these instructions or the circumstances and methods used for installation, operation, utilization and maintenance of this controller. Improper installation can cause damages to material and person. This is the reason why we do not take over responsibility and liability for losses, damages or cost that might arise due to improper installation, operation or wrong utilization and maintenance or that occurs in some connection with the above-mentioned. Moreover, we do not take over liability for patent infringements or infringements ­ occurring relating to the use of this controller on the third parties’ rights. The manufacturer preserves the right to put changes to product, technical data or installation and operation instructions without prior notice. As soon as it becomes evident that safe operation is no longer possible (e.g. visible damage). Please immediate take the device out of operation. Note: ensure that the device can’t be accidentally placed into
Page 4 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 operation.

1.4 Important information We have carefully checked the text and pictures of this manual and provided the best of our knowledge and ideas, however inevitable errors maybe exist. Please note that we cannot guarantee that this manual is given in the integrity of image and text, they are just some examples, and they apply only to our own system. Incorrect, incomplete and erroneous information and the resulting damage we do not take responsibility.

1.5 Signal description Safety indication: Safety instructions in the text are marked with a warning triangle. They indicate measures which can lead to injury of person or safety risks. Operation steps: small triangle “”is used to indicate operation step. Notes: Contains important information about operation or functions.

1.6 HMI button

LED indicator lamp

Controller is operated with the 5 buttons besides the screen ” ” holiday button “SET” button: confirm / selection “” upwards button: increase the value “” downwards button: reduce the value “ESC” button return/ exit: return to the previous menu
Note: TST is temperature of tank 1(on screen)
Page 5 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 1.7 Meaning of icons appeared on the screen

Icon Meaning Exceed the maximum temperature of tank Running of tank emergency shutdown function Running of collector emergency shutdown function Running of collector cooling function Running of tank cooling function Running of system cooling function Activating of anti-freezing function
Running of anti-freezing function
Activating of collector minimum temperature function Error of temperature sensor
Error of flow sensor

Code SMX

Icon is lighting

LEM

CEM

CMAX OSTC OSYC

CFRO
CMIN T —L/M —-

Icon is blinking +
+ +

Overview

Controller introduction
LED large screen display 6 relay outputs 1 low voltage relay output for boiler on/off control 8 sensor inputs 1 Input for Grundfos Direct Sensor TM (VFS) 1 Input for (FRT)rotary blade electronic flow meter 3 Variable frequency PWM outputs for the speed control of the high efficiency pump Data saved on the TF card (Micro SD)

Page 6 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 19 systems for choose
2.2 Delivery list 1 SR658 controller 1 user manual 2 screws and expansion 2 P1000 temperature sensor (650mm,cable length 1.5meter) 4 NTC10K temperature sensor (650mm,cable length 3meter) 1 clamp bag
2.3 Technical data Inputs 2 PT1000 temperature sensors
6
NTC10K, B=3950 temperature sensors 1 Grundfos Direct Sensor (VFS type) 1 Rotary blade electronic flow meter(FRT) Output 3 Electromagnetic relay, Max. current 1A 3 Semiconductor repay, Max. current1A 1 low voltagerelay(on/off signal), boiler on/off control 3 PWM variable frequency output (switchable 0-10V) Functions: operating hour counter, tube collector function, thermostat function, pump speed control, heat quantity measurement, external heat exchange, swimming pool circuit system, adjustable system parameters and optional functions (menu-structure), balance and diagnostics Power supply:100…240V ~ (50…60Hz) Rated impulse voltage:2.5KV Data interface : TF (Micro SD) HousingPlastic ABS MountingWall mounting Indication / Display: System-Monitoring-Display, for visualization of the systems, LED display, and background illumination Operation: 5 push buttons at the front cover Protection type: IP41 Protection class: I Ambient temperature: 0 … 40 °C Dimensions: 20815843mm
Page 7 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Note: TF (Micro SD) isn’t included in the delivery list 3.Installation
Note:The unit should only be installed in the dry interior rooms. Please separate routing of sensor wires and mains wires. Make sure the controller as well as the system are not exposed to the strong electromagnetic fields. 3.1 Mounting controller Follow the below steps to mount the controller on the wall. Unscrew the crosshead screw from the cover and
remove it along with the cover from the housing. Mark the upper fastening point on the wall. Drill and
fasten the enclosed wall plug and screw leaving the head protruding. Hang the housing from the upper fastening point and mark the lower fastening points (centers 180 mm). Drill and insert lower wall plugs. Fasten the housing to the wall with the lower fastening screw and tighten. Carry out the electrical wiring in accordance with the terminal allocation Put the cover on the housing. Attach with the fastening screw. 3.2 Wiring connection According to the way of installation, wire can be connected from hole A on the bottom plate or from hole B, using a suitable tool (like knife) to cut the plastic of A. Note: wires must be fastened by fixing clamps on position C.
Page 8 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 3.3 Terminal connection
Note: before opening the housing! Always disconnect the controller from power supply and obey the local electrical supply regulation.
Input terminals
T0T1: PT1000 temperature sensor, for measuring the temperature of collector T2T7: NTC10K, B=3950 temperature sensor, for measuring temperature of tank and pipe PWM1,PWM2, PWM3: Signal ports for high efficiency pump, detailed connection see below
picture HK-A, HK-B: Dry connection on/off signal ports, (HK and HR simultaneously open or close, for
boiler heating control) Communication port 485ELA485, for remote control communication( function not available now) FRTFor Rotary blade electronic flow meter VFSForGrundfos flowmeter sensor Advice regarding the installation of temperature sensors: Only original factory equipped Pt1000 temperature sensors are approved for using with
the collector, it is equipped with 1.5m silicon cable and suitable for all weather conditions, the cable is temperature resistant up to 280oC, connect the temperature sensors to the corresponding terminals with either polarity. Only original factory equipped NTC10K,B=3950 temperature sensors are approved for
Page 9 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 using with tank and pipe, it is equipped with 3m PVC cable, and the cable is temperature resistant up to 105oC, connect the temperature sensors to the corresponding terminals with either polarity.
All sensor cables carry low voltage, and to avoid inductive effects, must not be laid close to 230 Volt or 400 Volt cables (minimum separation of 100mm).
If external inductive effects are existed, e.g. from heavy current cables, overhead train cables, transformer substations, radio and television devices, amateur radio stations, microwave devices etc., then the cables to the sensors must be adequately shielded.
Sensor cables may be extended to a maximum length of ca. 100 meter, when cable’s length is up to 50m, and then 0.75mm2 cable should be used. When cable’s length is up to 100m, and then 1.5mm2 cables should be used.
Output terminal
Input Ports L, N: for power connection, L: live wire, N: zero wire, protective ground wire Output R1:Semiconductor relays (SCR), designed for pump speed control, Max. Current: 1A Output R2: Semiconductor relays (SCR), designed for pump speed control, Max. Current: 1A Output R3: Semiconductor relays (SCR), designed for pump speed control, Max. Current: 1A OutputR4:Electromagnetic relays, designed for on/off control of pump or 3-ways
electromagnetic valve, Max. Current: 1A Output R5: Electromagnetic relays, designed for on/off control of pump or 3-ways
electromagnetic valve, Max. Current: 1A Output HR: Electromagnetic relays, designed for on/off control of back-up heating device, Max.
Current: 1A
Page 10 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 R4, R5 terminals for 3-ways valve / pump connection
Valve with 3 wires

Valve with 2 wires

Pump connection
R4R5: When it is for control 3 ways electromagnetic valve,3 is normally close port, 2 is normally open port ,1 is common port When it is for control pump, (2 is normally open port, 1 is common port)
Connection with high efficiency pump

Page 11 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Connecting the signal wire from the high-efficiency pump
Signal wire 1 from the high-efficiency pump is connected to GND port of controller Signal wire 2 from the high-efficiency pump is connected to PWM1 port of controller Signalwire3 from the high-efficiency pump is signal wire FB1, it is not connected to FB1 port of controller Some pumps connections are available as above, for example: Wilo Yonos PARA ST15/7.0 PWM2 M Grundfos UPM3 SOLAR 15-75 130 CZA
Note: High-efficiency pump with 0-10V signal only has 2 signal wires, connected to the
corresponding port GND, PWM1 (PWM2 or PWM3) of controller. Blue wire not always represent for “GND” and brown wire not always represent for
“PWM”. “PWM” from pump must be match for “PWM” from controller. “GND”from pump must be match for “GND” from controller.
3.4 TF (MicroSD) Card Controller is equipped with a slot for TF (Micro SD) card. With TF (MicroSD) card, following functions can be carried out Save the measurement value and parameters value onto the MicroSD TFcard. After
transferring the data to a computer, the value can be opened and visualized, e. g. in a spreadsheet. Copy the updated firmware program from computer and install it on the controller via MicroSD card.
Page 12 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 TFMicroSDcard slot Note:TF (MicroSD) card is not listed in the standard delivery package, self-purchase if
need, more detailed about TF (MicroSD) see paragraph 7 (25)
Page 13 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 4. System introduction 4.1 Overview of the available systems
Page 14 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Page 15 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
4.2 Description of 19 systems
System 1: Standard solar system with 1 tank, 1 collector field Description: The controller calculates the temperature difference between collector sensor T1 and tank sensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, the solar circulation pump (R1) will be switched on and the tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.

Sensor T1 T2 T3
T6
T7

Description Temperature of collector Temperature of tank base Temperature of tank upper (optional one) Optional free sensor, undefined(optional) Temperature for thermal energy measurement (optional one)

Relay R1 HR

Description Solar circulation pump Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

Sensor

Relay output

T5/flow switcher

R2

(connected on T5 port)

T0

R3

R4

R5

Page 16 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

OPARR Parallel relay

AH

Thermostat function

T2/T3/T4optional

R2/R3/R4/R5 optional R5

System 2: Solar system with 1 tank, 1 collector field, 3-ways valve for tank loading in layers
Description: The controller calculates the temperature difference between collector sensor T1 and tank base and upper sensor T2, T3. If the difference is larger than or identical to the adjusted switch-on temperature difference, the solar circulation pump (R1) will be switched on, and simultaneously valve R4 turns to the corresponding tank zone and this zone will be loaded until the switch-off temperature difference or the maximum tank temperature is reached. The priority logic effects prior loading of the upper zone of the tank. Please refer the Paragraph of “LLOGI Tank priority logic”

Sensor T1 T2 T3
T6
T7

Description Temperature of collector Temperature of tank base Temperature of tank upper (optional one) Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Relay R1 R4 HR

Description Solar circulation pump 1. Valve of solar circuit Back-up heating

Page 17 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T5/flow switcher

R2

(connected on T5 port)

T0

R3

R5

T2/T3/T4 optional

R5
R2/R3/R5 optional R5

System 3: Solar system with1collectorfiled, 2tanks and thermal energy transferring between 2 tanks
Description:
The controller calculates the temperature difference between collector sensor T1 andtank1 base sensor T2. If the differences is larger than or identical to the adjusted switch-on temperature difference, then the solar circulation pump (R1) will be switched on, tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
Thermal energy transferring means the other tank (2) is heated, another temperature difference controls the running of pump R2difference betweenT3and T4 temperature. Please refer the Paragraph 7.14 of “HEATX Energy exchange between tanks”

Page 18 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor Description

T1

Temperature of collector

T2

Temperature of tank 1 base

T3

Temperature of tank 1 upper

(optional one)

T4

Temperature of tank 2

T6

Return sensor(for thermal

energy measurement)

T7

Flow sensor(for thermal energy

measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Relay R1 R2
HR

Description Solar circulation pump Pump for thermal transfer between tank Back-up heating

Sensor

Relay output

T5/flow switcher

R4

(connected on T5 port)

T0

R3

R5

T2/T3/T4/T6 optional

R5
R3/R4/R5 optional R5

System 4: Standard solar system with heat exchanger control logic Description: The controller calculates the temperature difference between collector sensor T1 and tank base sensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then the corresponding solar circulation pump (R1) will be switched on, heat exchanger is heated until the switch-off temperature difference or the maximum exchanger temperature is reached. By using another temperature difference between T4 and T2 controls pump R2 to load tank
Note: if sensor T4is not installed, then when temperature difference between collector T1 and tank T2 is reached, pump R1 and R2 are triggered simultaneously, and pumps are ceased until the switch-off temperature reaches or the maximum exchanger temperature is reached. Please refer the Paragraph 7.17of “EXHX external heat exchanger”

Page 19 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor Description

T1

Temperature of collector

T2

Temperature of tank base

T3

Temperature of tank upper (optional )

T4

Temperature of heat

exchanger(optional)

T6

Return sensor(for thermal energy

measurement)

T7

Flow sensor(for thermal energy

measurement)

Relay R1 R2
HR

Description Solar circulation pump1 Pump for thermal transfer between heat exchanger and tank Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T5/flow switcher

R4

(connected on T5 port)

T0

R3

R5

T2/T3/T6 optional

R5
R3/R4/R5 optional R5

Page 20 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
System 5: Solar system with 1 collector field, 2tanks, pump -logic control
Description:
The controller calculates the temperature difference between collector sensor T1 andtank1 and tank 2’s base sensor T2 and T4. If any difference is larger than or identical to the adjusted switch-on temperature difference, then the corresponding solar circulation pump (R1 or R2) will be switched on, tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
The priority logic effects prior loading of the tank 1. Please refer the Paragraph 7.12of “LLOGI Tank priority logic”

Sensor T1 T2 T3 T4 T5 T6
T7

Description Temperature of collector Temperature of tank 1 base Temperature of tank 1 upper (optional) Temperature of tank2base Temperature of tank2upper (optional) Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Relay R1 R2 HR

Description Solar circulation pump 1 Solar circulation pump 2 Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

Sensor

Relay output

T5/flow switcher

R4

(connected on T5 port)

T0

R3

R5

Page 21 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

TIMER OPARR

radiator Timer function Parallel relay

AH

Thermostat function

T2/T3/T4/T6 optional

R5
R3/R4/R5 optional R5

System 6: Solar system with 1 collector field, 1 tank, valve logic control Description: The controller calculates the temperature difference between collector sensor T1 andtank1 and tank 2’s base sensor T2 and T4. If any difference is larger than or identical to the adjusted switch-on temperature difference, then the solar circulation pump (R1) will be switched on, and simultaneously valve R4 turns to the corresponding tank, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.

The priority logic effects prior loading of the tank 1. Please refer the Paragraph 7.12of “LLOGI Tank priority logic”

Sensor T1 T2 T3
T4 T5
T6
T7

Description Temperature of collector Temperature of tank 1 base Temperature of tank 1 upper (optional) Temperature of tank2base Temperature of tank2upper (optional) Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Relay R1 R4 HR

Description Solar circulation pump 1 Valve of solar circuit Back-up heating

Page 22 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T5/flow switcher

R2

(connected on T5 port)

T0

R3

R5

T2/T3/T4/T6 optional

R5
R2/R3/R5 optional R5

System 7: Solar system with east/west collector fields, 1 tank
Description:
The controller calculates the temperature difference between east/ west collector sensor T1 and T0 and tank base sensor T2. If any difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 or R2) will be switched on, and tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.

Sensor T0 T1 T2 T3
T6

Description Temperature of collector 2 Temperature of collector 1 Temperature of tank base Temperature of tank upper (optional) Return sensor(for thermal energy measurement)

Relay R1 R2 HR

Description Solar circulation pump 1 Solar circulation pump 2 Back-up heating

Page 23 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

T7

Flow sensor(for thermal energy

measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T5/flow switcher

R4

(connected on T5 port)

T0

R3

R5

T2/T3/T6 optional

R5
R3/R4/R5 optional R5

System 8: Solar system with east/west collector field, valvelogiccontrol, loading in
layers
Description:
The controller calculates the temperature difference between east/ west collector sensor T1 and T0 and tank base/ upper sensor T2 and T3. If any difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 or R2) will be switched on, and simultaneously valve R4 turns to the corresponding tank part, and this tank part will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
The priority logic effects prior loading of the upper part of tank. Please refer the Paragraph 7.12of “LLOGI Tank priority logic”

Page 24 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor T0 T1 T2 T3
T6
T7

Description Temperature of collector 2 Temperature of collector 1 Temperature of tank base Temperature of tank upper (optional) Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Relay R1 R2 R4 HR

Description Solar circulation pump 1 Solar circulation pump 2 Valve of solar circuit Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T4/flow switcher

R5

(connected on T4 port)

T0

R3

R5

T2/T3/T6 optional

R5
R3/R5 optional R5

System 9: Solar system with east/west collector fields, 2 tanks, valve logic control
Description:
The controller calculates the temperature difference between east/ west collector sensor T1 and T0 and 2 tanks base sensor T2 and T4. If any difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 or R2) will be switched on, and simultaneously valve R4 turns to the corresponding tank, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached. The priority logic effects prior loading of the tank

  1. Please refer the Paragraph 7.12 of “LLOGI Tank priority logic”

Page 25 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor T0 T1 T2 T3
T4 T5
T6
T7

Description Temperature of collector 2 Temperature of collector 1 Temperature of tank 1 base Temperature of tank 1 upper (optional) Temperature of tank 2 base Temperature of tank 2 upper (optional) Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Relay R1 R2 R4 HR

Description Solar circulation pump 1 Solar circulation pump 2 Valve of solar circuit Back-up heating

Sensor

Relay output

T6/flow switcher

R5

(connected on T6 port)

T0

R3

R5

T2/T3/T4/T6 optional

R5
R3/R5 optional R5

System 10: Solar system with east/west collector fields, 1 tank, loading the heating
return
Description:
The controller calculates the temperature difference between east/ west collector sensor T1 and T0 and tank base sensor T2. If any difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 or R2) will be switched on, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
By using another temperature difference between T4 and T5 controls valve R4 to load the heating return flow. Please refer the Paragraph7.15 of “RPH Heating return pipe preheat”

Page 26 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor T0 T1 T2 T3
T4
T5 T6
T7

Description Temperature of collector 2 Temperature of collector 1 Temperature of tank base Temperature of tank upper (optional) Temperature of tank middle for heating return(optional) Temperature of heating return Return sensor(for thermal energy measurement) Flow sensor(for thermal energy measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Relay R1 R2 R4 HR

Description Solar circulation pump 1 Solar circulation pump 2 Valve of heating return Back-up heating

Sensor

Relay output

T6/flow switcher

R3

(connected on T6 port)

T6

R3

R5

T2/T3/T4/T6 optional

R5
R3/R5 optional R5

Page 27 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
System 11: Solar system with1 collector field,1tank, loading the heating return Description: The controller calculates the temperature difference between collector sensor T1and tank sensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
By using another temperature difference between T4 and T5 controls valve R4 to load the heating return flow. Please refer the Paragraph 7.15of “RPH Heating return pipe preheat”

Sensor Description

T1

Temperature of collector

T2

Temperature of tank base

T3

Temperature of tank upper

(optional)

T4

Temperature of tank middle for

heating return(optional)

T5

Temperature of heating return

T6

Return sensor(for thermal energy

measurement)

T7

Flow sensor(for thermal energy

measurement)

Relay R1 R4 HR

Description Solar circulation pump 1 Valve of heating return Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

Sensor

Relay output

T6/flow switcher

R2

(connected on T6 port)

Page 28 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

SFB OHDP
TIMER OPARR

Solid fuel boiler Thermal transfer -by external radiator Timer function Parallel relay

AH

Thermostat function

T0

R3

R5

T2/T3/T4/T6 optional

R5
R2/R3/R5 optional R5

System 12: Solar system with1 collector field, 2 tanks, valvelogic, heating return
loading
Description:
The controller calculates the temperature difference between collector sensor T1and 2 tank’s sensor T2 and T4. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on, and simultaneously valve R4 turns to the corresponding tank, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.

The priority logic effects prior loading of the tank 1. Please refer the Paragraph 7.12 of “LLOGI Tank priority logic”

By using another temperature difference between T5 and T6 controls valve R5 to load the heating return flow. Please refer the Paragraph 7.15 of “RPH Heating return pipe preheat”

Sensor T0 T1 T2 T3

Description Temperature of heating return Temperature of collector Temperature of tank 1 base Temperature of tank 1 upper (optional)

Relay R1 R4 R5 HR

Description Solar circulation pump 1 Valve of solar circuit Valve of heating return Back-up heating

Page 29 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

T4

Temperature of tank 2 base

T5

Temperature of tank 2 upper

(optional)

T6

Return sensor(for thermal energy

measurement)

T7

Flow sensor(for thermal energy

measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T6/flow switcher

R3

(connected on T6 port)

T6

R3

R2

T2/T3/T4/T5optional

R2
R2/R3/ optional R2

System 13: Solar system with 1collector field, 2 tanks, thermal energy transferring
Description:
The controller calculates the temperature difference between collector sensor T1and tank 1’s sensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on, and this tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached.
Thermal energy transferring between 2 tanks: When tank 1’s temperature reaches the switch-on temperature (L1H2O), and temperature of tank 1 is larger than tank 2 (T3>T4), pump R2 is triggered; when tank 1’s temperature drops below its switch off temperature (L1H2F) or temperature of tank 2 rises to the same temperature of tank 1, or temperature of tank 2 reaches its maximum value S2MAX, then pump R2 is stopped
When tank 2’s temperature reaches the switch-on temperature (L2H1O), and temperature of tank 2 is larger than tank 1 (T4>T3), pump R3 is triggered; when tank 2’s temperature drops below its switch off temperature (L2H1F) or temperature of tank 1 rises to the same temperature of tank 2, or temperature of tank 1 reaches its maximum value SMAX, then pump R3 is stopped. Please refer the Paragraph 7.16 of “DLHTX Thermal energy transferring between tanks”

Page 30 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor Description

T1

Temperature of collector

T2

Temperature of tank1base

T3

Temperature of tank1 upper

(optional)

T4

Temperature of tank2

T6

Return sensor(for thermal energy

measurement)

T7

Flow sensor(for thermal energy

measurement)

Relay R1 R2 R3 HR

Description Solar circulation pump 1 Heating transfer 1 to 2 pump 2 Heating transfer 2 to 1 pump 3 Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor

Relay output

T5/flow switcher

R4

(connected on T5 port)

T0

R5

R5

T2/T3/T4optional

R5
R4/R5 optional R5

System 14: Solar system with 1 collector field, swimming pool heating
Description:
The controller calculates the temperature difference between collector sensor T1andswimmingpoolsensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on, and swimming pool will be loaded until the switch- off temperature difference or the maximum

Page 31 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 swimmingpool temperature is reached.

Sensor Description

T1

Temperature of collector

T2

Temperature of swimming pool

T6

Return sensor(for thermal energy

measurement)

T7

Flow sensor(for thermal energy

measurement)

Auxiliary functions

Function

Function description

code

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Relay Description R1 Solar circulation pump HR Back-up heating

Sensor T2/T3/T4/T5optional

Relay output
R4
R5 R2/R3/R4/R5 optional R5

System 15: Solar system with 1 collector field, heat exchanger and swimming pool heating Description: The controller calculates the temperature difference between collector sensor T1and heat exchanger sensor T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on. When

Page 32 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 temperature difference between collector sensor T1and heat exchanger sensor T2drops to the switch-off temperature difference or the maximum swimming pool temperature is reached, then solar pump R1 is ceased. By using another temperature difference between T4 and T2, R2 can be trigged to heat swimming pool. The controller calculates the temperature difference between heat exchanger sensor T4 and swimming pool T2. If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R2) will be switched on. When temperature difference between heat exchanger sensor T4 and swimming pool T2drops to the switch-off temperature difference or the maximum swimming pool (T2) temperature is reached, then solar pump R2 is ceased. Note: when T4 is not installed, then temperature difference between collector T1 and swimming pool T2 is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 and R2) will be switched on simultaneously. And when temperature difference between collector sensor T1and swimming pool T2 drops to the switch-off temperature difference or the maximum swimming pool (T2) temperature is reached, then solar pump R1 and R2 are ceased simultaneously. Please refer the Paragraph 7.17 of “EXHX external heat exchanger function”
Page 33 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Sensor T1 T2
T4
T6
T7

Description

Temperature of collector

Temperature

of

swimming

pool(optional)

Temperature of heat

exchanger(optional)

Return sensor(for thermal energy

measurement)

Flow sensor(for thermal energy

measurement)

Relay R1 R2
HR

Description Solar circulation pump 1 Circuit pump between HE and swimming pool Back-up heating

Auxiliary functions

Function

Function description

code

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Sensor T2/T3/T5optional

Relay output
R5
R4 R3/R4/R5 optional R4

System 16: Solar system with 1 collector field,1 tank, swimming pool, valve and heat exchanger control Description: The controller calculates the temperature difference between collector sensor T1andtankor heat exchanger sensor(T2, T5). If the difference is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1) will be switched on. And according to priority logic, valve R4 turns to the tank or heat exchanger, tank and heat exchanger is heated one by one. When temperature difference between collector sensor T1and tank or heat exchanger sensor T2,T5drops to the switch-off temperature difference or the maximum temperature of tank (T2) or swimming pool(T5) is reached, then solar pump R1 is ceased.

The priority logic effects prior loading of the tank. Please refer the paragraph 7.12 of “LLOGI Tank priority logic”

By using another temperature difference between T5 and T4, R2 can be trigged to heat swimming pool. Note: when T5 is not installed, then temperature difference between collector T1 and swimming pool T4is larger than or identical to the adjusted switch-on temperature difference, then solar circulation pump (R1 and R2) and valve R4 all will be switched on simultaneously. And when temperature difference between collector sensor T1and swimming pool T4drops to

Page 34 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
the switch-off temperature difference or the maximum swimming pool (T4) temperature is reached, then solar pump R1, R2 and valve R4 are ceased simultaneously. Please refer the paragraph 7.17 of “EXHX external heatex changer function”

Sensor Description

T1

Temperature of collector

T2

Temperature of tank base

T3

Temperature

of

upper(optional)

tank

T4

Temperature of swimming pool

T5

Temperature

of

exchanger(optional)

heat

T6

Return sensor(for thermal energy measurement)

T7

Flow sensor(for thermal energy measurement)

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB

Solid fuel boiler

OHDP Thermal transfer -by external

radiator

TIMER Timer function

OPARR Parallel relay

AH

Thermostat function

Relay Description

R1 Solar circulation pump 1

R2

Circuit pump for external heat exchanger

R4 Solar circuit valve

HR Back-up heating

Sensor

Relay output

T6/flow switcher

R5

(connected on T6 port)

T0

R3

R5

T2/T3/T4/T6optional

R5
R3/R5 optional R5

Page 35 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
System 17: System with 1 tank and solid fuel boiler Description: solid fuel boiler function is designed to transfer the thermal energy from solid fuel boiler to tank. The controller calculates the temperature difference between solid fuel boiler sensor T0 and tank sensor (T2 or T3). If the difference is larger than or identical to the adjusted switch-on temperature difference, and meet below two conditions, circulation pump (R1) will be switched on. And when temperature difference between sensor T0 and tank T2 or T3 drops to the switch-off temperature difference, pump R1 is ceased.

  1. Temperature of solid fuel boiler is higher than the preset minimum temperature of boiler. 2) Temperature of tank sensor is lower than the preset maximum temperature of tank. Please refer the paragraph 7.18of “Solid fuel boiler function”

Sensor Description

T2

Temperature of tank base

T3

Temperature

of

upper(Optional)

tank

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB

Solid fuel boiler

TIMER Timer function

AH

Thermostat function

Relay Description HR Back-up heating

Sensor

Relay output

T6/flow switcher

R3

(connected on T6 port)

T0

R1

R4

T2/T3/T4optional

R5

Page 36 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
System 18: System with 2 tanks, thermal energy transferring and solid fuel boiler Description: Thermal energy transferring function is deigned to heat one tank by another tank which has heat source tank/ T4 tank be heated) Please refer the paragraph7.14 of “HEATX Energy exchange between tanks”
solid fuel boiler function is designed to transfer the thermal energy from solid fuel boiler to tank. Please refer the paragraph7.18 of ” SFB solid fuel boiler function”

Sensor Description

T2

Temperature of tank1 base

T3

Temperature

of

upper(Optional)

tank1

T4

Temperature of tank2 base

T5

Temperature

of

upper(Optional)

tank2

Relay Description R1 Pump for tank heat transferring HR Back-up heating

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB

Solid fuel boiler

TIMER Timer function

AH

Thermostat function

Sensor

Relay output

T6/flow switcher

R3

(connected on T6 port)

T0

R2

R4

T2/T3/T4/T5 optional R5

Page 37 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
System 19: System with 1 tank, heating return and solid fuel boiler Description: Temperature between heat source T4and heating return T5 is deigned to trigger valve R4.. Please refer the Paragraph 7.15 of “RPH Heating return pipe preheat”
solid fuel boiler function is designed to transfer the thermal energy from solid fuel boiler to tank. Please refer the paragraph7.18 of ” SFB solid fuel boiler function”

Sensor Description

T2

Temperature of tank base

T3

Temperature of tank upper (Optional)

T4

Temperature of tank middle for heating return (Optional)

T5

Temperature of heating return

Auxiliary functions

Function

Function description

code

CIRC DHW circulation (controlled by

temperature or flow impulse)

SFB

Solid fuel boiler

TIMER Timer function

AH

Thermostat function

Relay Description R4 Valve of heating return HR Back-up heating

Sensor

Relay output

T6/flow switcher

R3

(connected on T6 port)

T0

R1

R2

T2/T3/T4optional

R5

Page 38 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 4.3 Commissioning
Before connecting the controller to the mains, ensure system is filled and ready for operation, please connecting all sensors to the input terminals, pumps or valves to the output terminals and fill the system. After power is switch on, the controller runs an initialization phase for 5 seconds, then controller runs a commissioning menu, it leads the user through the most important adjustment channels needed for operating the system. 5. Functions and options 5.1Overview of menu structure
Page 39 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 5.2 Menu operation description Access main menu press “SET” button to access main menu Press “”, “” to select menu Press “SET” button to enter the submenu
Access submenu Press “SET” button to access submenu Press””, “” button to select submenu to be adjusted Press “SET” button to enter this submenu Press “SET” button, “OFF” or “ON”blinks on the screen Press “”, “” button, select “ON” to trigger the menu, or select “OFF” to close the menu Press “SET”or “ESC” button, to confirm the selection Press “” button to access the next submenu Press “SET” button to access value adjust Press “”, “” button to adjust value Press “SET”or “ESC” button,to confirm the value Press “ESC” to exit the menu.
Note: Enter the menu adjustment interface, if you don’t press any button within 5 minutes, screen will exit the adjustment and turn to the main interface. 5.3 Check value At the normal operation mode, press “”, “” button, you can view the temperature of collector and tank, temperature of Grundfos sensor(TVFS), pump speed(n%), accumulated pump running time(hR),current thermal energy(DKWH) accumulated thermal energy(KWh /MWh), flow rate(L/M), controller running time (DAYS), software version (SW),Year/Month/Day, Time Under standby status, press “SET” button for 3 seconds, then press “”, “” button to check the type of pump and unblock function.
Note: Enter the value checking interface, if you don’t press any button within 5 minutes, screen will exit the adjustment and turn to the main interface.
Page 40 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 5.4 Quick trigger function of back- up heating and circuit pump 1.understandby status, press “ESC” button for 3 seconds, it is possible to manual trigger on the circuit pump, after fifteen minutes or repress the “ESC” button for 3 seconds, then circuit pump is stopped.
2. under standby status, press “” for 3 seconds, manual back-up heating is triggered. Press “”, “” button to adjust the temperature set point, press “ESC” button to confirm the parameter and trigger back-up heating, when temperature reaches, manual heating is stopped. During the period of manual heating process, repress “” for 3 seconds, to switch-off manual heating immediately.(this function is only available when the back-up heating THET function is running.
6. Menu function and parameter set (for user)
1Date(Time/ Date set) Menu structure

Main menu DATE

Submenu Submenu

Default set

1

2

Adjust range

TIME ADST YYYY MM/DD

OFF

ON/OFF

Adjust step

Description
Time/date setup Hour/minute Summer time on/off Year Month/day

ADST: Switch on/off the summer time function When you deactivate the “summer time function”, controller can still run, “ADST” is only referring directives Europe 200/84/EG, only suitable for Europe union country.

Note:In the case power to controller is switched-off, date and time will be remembered in

Page 41 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 controller for 36 hours.
Function setup: Press “SET” button, select DATEmenu Press “SET” button, “TIME00:00” displays on the screen Press “SET” button, time zone hour”00″ blinks Press “”, “” button to adjust hour time Press “SET” button, time zone minute “00” blinks Press “”, “” button to adjust minute time Press “SET”or “ESC” button, to confirm the setting
Press “”button, “ADST OFF” displays on the screen (summer time) Press “SET” button, “OFF” blinks Press “”, “” button to activate summer timer function Press “SET”or “ESC” button, to confirm the setting
Press “”button, “YYYY2015” displays on the screen, adjust year. Press “SET” button, “2015” blinks Press “”, “” button to adjust year Press “SET”or “ESC” button, to confirm the setting Press “”button, “MM01” displays on the screen, adjust month. Press “SET” button, “01” blinks Press “”, “” button to adjust month Press “SET”or “ESC” button, to confirm the setting Press “”button, “DD01” displays on the screen, adjust day. Press “SET” button, “01” blinks Press “”, “” button to adjust day Press “SET”or “ESC” button, to confirm the setting 2THET Timed back-up heating Timed heating An electrical back-up heater is possible to be installed in a solar system, controller can provide automatic thermostat control function, when tank temperature T2 drops below the preset switch ­ on temperature of this function, electrical heater(HR) will be triggered and when tank temperature T2 rises to the preset switch-off temperature, electrical heater(HR) is stopped.
Page 42 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Two kinds of heating device(heating mode) are available: Electrical heater as back-up heat resource (ELET) Boiler as back-up heat resource (BOIL)

Note: system 4, 14,15 has no heating mode option, when time heating function is

activated, sign

displays on the screen.

Three time – sections can be set for back-up heater Factory default set: The first time – section of heating starts at 04:00and stops at 05:00a.m. The second time – section of heating starts at 10:00 and stops at 10:00a.m. The third time – section of heating starts at 17:00 and stops at 22:00 p.m. For all time – sections, default temperature for control back-up heating is triggered at
temperature of 40oC, and stopped at temperature of 50oC. If it is needed to deactivate the back-up heating function in one time – section, then just
set the start time and stop time with a same value, for example, for the second-time section, the start time is 10:00 a.m, and the stop time is also 10:00 a.m. Within three time – sections, the adjust range of the switch-on temperature is 0oC ~(OFF-2oC), and the switch-off temperature is (ON+2oC) ~95oC.

SMT Intelligent heating At the case that solar energy is insufficient to heat the tank, to ensure user has sufficient hot water, controller will check the temperature of tank automatically at the pre-set time, if tank’s temperature is not reached to the desired temperature, then back-up heat producer will be triggered, and when tank’s temperature rises to the desired value, then back- up heat producer is stopped.
Factory set(not adjustable) of SMT function: Default at 13:00 of the first time to trigger the back-up heat device to heat tank to 30 oC, Default at 14:00 of the second time to trigger the back-up heat device to heat tank to 35
oC, Default at 15:00 of the third time to trigger the back-up heat device to heat tank to 40 oC, Default at 16:00 of the fourth time to trigger the back-up heat device to heat tank to 45 oC, Default at 17:00 of the fifth time to trigger the back-up heat device to heat tank to 50 oC.

Diagram of back-up boiler connection (BOIL)

Page 43 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

ON/OFFsignal customized available

AC100-220V

If boiler is selected as back-up heat producer, output HK and HR is controlled by T3 or T2(Optional). When T3 or T2(Optional) is reached to the switch-on temperature of back-up heating function, then back-up heating output HK and HR are triggered, when T3 or T2(Optional) is exceeded the switch-off temperature of back-up heating function, then back-up heating output HK and HR are closed.
Note: if electrical heater is selected as back-up heater, then according to the power of the heater, an appropriate AC contactor and safety protection device should be installed, we recommend installing the accessory “SR802” (see accessories in paragraph11)
Menu structure

Page 44 of 113 Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Main menu THET

Submenu 1 MODE

Submenu 2

Default set ELET

Adjust range ELET / BOIL

THS

T2

T2, T3

SMT

OFF

ON/OFF

tH1O

04:00/40 00:00-23:59/0.0-93

tH1F

05:00/50 00:00-23:59/2-95

tH2O

10:00/40 00:00-23:59/0.0-93

tH2F

10:00/50 00:00-23:59/2-95

tH3O

17:00/50 00:00-23:59/0.0-93

tH3F

22:00/55 00:00-23:59/2-95

Adjust step
Timed heating function
Heating device select
Target sensor for timed heating
function
Intelligent heating on or off Start time and switch-on temperature for the first time- section Close time and switch-off temperature for the first time- section Start time and switch-on temperature for the second time – section Close time and switch-off temperature for the second time – section Start time and switch-on temperature for the third time- section Close time and switch- off temperature for the third time- section

Function set: Press “SET” button, access main menu, press””button to select THET timed heating menu Press “SET” button, “THETOFF” displays Press “SET” button, “OFF” blinks Press “”, “” button to activate the function, “THET ON” displays on the screen Press “SET”or “ESC” button, to confirm the setting

Press “”,”MODE ELET” displays on the screen, select the heater type. Press “SET” button, “ELET” blinks on the screen. Press “”, “” button to select heater type Press “SET”or “ESC” button, to confirm the setting
Press “”, to select the sensor for heating function, “THS T2” displays on the screen

Page 45 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “SET” button, “T2” blinks Press “”, “” button to select the available sensor Press “SET”or “ESC” button, to confirm the setting
Press “”, to access the intelligent heating window, “SMTOFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate the intelligent heating function, “SMTON” displays on the screen Press “SET”or “ESC” button, to confirm the setting
Press “”, to access the window of the start time and switch-on temperature setting of heating in the first-time – section, “tH1O 04:00” displays on the screen Press “SET” button, hour time zone “04” blinks Press “”, “” button to set the hour of the start time of heating in the first-time – section Press “SET” button, minute time zone “00” blinks Press “”, “” button to set the minute of the start time of heating in the first-time – section Press “”, to access the switch-on temperature of heating in the first-time – section,”tH1O 40oC” displays on the screen Press “SET” button, temperature “40oC” blinks Press “”, “” button to adjust the switch-on temperature of heating in the first-time – section Press “SET”or “ESC” button, to confirm the setting
Press “”, to access the window of the close time and switch-off temperature setting of heating in the first-time – section, “tH1F 05:00” displays on the screen Press “SET” button, hour time zone “05” blinks Press “”, “” button to set the hour of the close time of heating in the first-time – section Press “SET” button, minute time zone “00” blinks Press “”, “” button to set the minute of the close time of heating in the first-time – section Press “”, to access the switch-off temperature of heating in the first-time – section, “tH1F 45oC” displays on the screen Press “SET” button, temperature “45oC” blinks
Page 46 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Press “”, “” button to adjust the switch-off temperature of heating in the first-time – section Press “SET”or “ESC” button, to confirm the setting

Press “”, to access the window of the start time and switch-on temperature setting for

back-up heating in the second time – section, same steps like above description to set the

parameters for second and third time – sections.

When the icon of the timed heating

blinks on the screen, it indicates the back-up

heating is activated.

3CIRC DHWcircuit pump controlled by temperature in three time – sections / flow switcher

Note: 1. Because of the system selection, in this system, several auxiliary functions may be allocated to the same output, for example to R2 output, (see paragraph 4.2 system diagram and its auxiliary functions), then only one function can be activated, other functions are deactivated automatically, and displays “NONE”. 2. And because of system selection, the sensor and relay for a same function may be different.
Function description: This function is designed to get warm water quickly when customer open the stopcock. In the case stopcock is closed, hot water pipe is also used as the circuit pipe. Two hot water circuit supply modes are available, temperature controlled mode and flow switcher controlled mode. For using this function, an extra circuit pump RX or a flow switcher or a temperature sensor (mounted on the hot water return pipe (TX)) should be installed in the system. (and due to the solar system difference, output relay or sensor input used for circuit pump RX and temperature sensor TXmay be different also, see detailed in paragraph 4.2)

2 control mode of DHW circuit pump are designed in this controller: temperature control in three time sections and flow switch control in three time sections.
This sign displays on the screen, it indicates temperature control mode is activated. If this sign blinks,it indicates DHW circuit pump is running.
This sign displays on the screen, it indicates flow switcher control mode is activated. If this sign blinks,it indicates DHW circuit pump is running.
Note:

Page 47 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
1. for 2 DHW circuit pump control modes, only one mode can be selected. 2. for 2 DHW control modes, three time – sections/temperature control mode and three time – sections /flow switcher control mode, their parameter adjust steps of two control mode are same.

Three time – sections/ temperature control mode TEMP Within the time – section (default: DHW temperature is less than 40oC, DHW circuit pump is trigger, when temperature rises to 45oC, DHW circuit pump is stopped).

Trigger on conditions of temperature controlled DHW circuit pump (STAT): when tank temperature (T2 or T3) is 2oC higher than the preset switch-off temperature (CYCF) of this function, DHW pump just can be triggered.

Default time – section set: The first time – section: start at 05:00 and stops at 07:00a.m The second time – section: starts at 11:00 and stops at 13:00 The third time – section: starts at 17:00 and stops at 22:00 p.m.

Note: if this sensor is necessary to be installed in the system, in order to avoid the measure error, please ensure its position is 1.5m far to the tank.

Three time – sections/ flow switcher control mode CYCFS

Function description:

Open the stopcock, water flows through pipe, a flow signal is felt

by a flow switcher which is mounted on the cold-water pipe and

sent to the controller, and then controller will trigger the DHW

circuit pump (RX) and it pumps hot water from tank to the circuit

pipe. The running time of circuit pump is adjustable, when the

preset time runs out, pump stops.

Flow switch
This stopcock seems like a remote controller to control the

To TX input

running of circuit pump. This operation mode is an environment-friendly, energy-saving control

solution.

Open the stopcock for a shortly time, the flow switcher which is mounted on the cold flow pipe

Page 48 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 of tank will feel the flow signal, and then controller will trigger the circuit pump RX, and pump will feed hot water from tank to the pipe. Then when you re-open the stopcock, hot water flows out immediately. Once the pump’s running time finishes,then pump is stopped. When hot water is not used, to avoid the heat releasing through pipe due to the running of circuit pump, controller will stop the pump after the pre-set running time. To avoid the pump being re-triggered just after it stopped, parameter “rest time” is used for this control.
Open the stopcock within a pre-set time – section, pump running as the default design: pump running for every three minutes and then rest for 15minutes (the adjustable range of the running time is 1-30 MIN and the rest time is 0-60MIN)
Note: Installed a checkvalve on the inlet pipe of circuit pump to avoid the water which is from
tank mixing with water from circuit pipe. If the stop time is set with value 0 minute, then when flow switcher feels the flow and
thus to trigger the pump, pump will run for the whole time – section. And when the stopcock is closed, pump is stopped automatically. Default time – section set: The first time – section: start at 05:00 and stops at 07:00a.m The second time – section: starts at 11:00 and stops at 13:00 The third time – section: starts at 17:00 and stops at 22:00 p.m.
Flow switch fitting: Material of fitting: brass House: plastic Connection: G3/4 Reed of flow switch: Max 300V DC/1A
Note: 1. Notethe flow direction indicated on the flow switch! 2. Lead the wires from flow switcher to input ports of controller, no polarity required. 3. Flow switch is not included in the delivery list of this controller, please buy it separately.
Page 49 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Menu structure

Main menu CIRC
o

Submen u 1
MODE

Submen u 2

Default set
OFF CYFS

Adjust range
ON/OFF CYFS / TEMP

STAT

ON

ON/OFF

CYCO CYCF t C1O t C1F t C2O t C2F t C3O

40/3min 5-53/1-30min

45

/15min

05:00

7-55/0-60min 00:00-23:59

07:00

00:00-23:59

11:00

00:00-23:59

13:00

00:00-23:59

17:00

00:00-23:59

Adjust step
0.5 /1min 0.5 /1min

Main menu

DHW circuit function

Control

mode

by

temperature or by flow

switcher.

Trigger condition of DHW

circuit pump

Tank temperature (T3 or

T2,T3 was prority)is 2oChigherthanthe switch-off

temperature Switch-on temperature or

running time

Switch-off temperature or the rest time

Start time of the first time- section Close time of the first time- section
Start time of the second time- section Close time of the second time – section Start time of the third time-

Page 50 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

t C3F

22:00

00:00-23:59

section Close time of the third time – section

Function set: (take DHW three time – sections temperature control mode as example) Press “SET” button, select main menu CIRC Press “SET” button, “CIRC OFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate the function, “CIRC ON” displays on the screen Press “SET”or “ESC” button, to confirm the setting Press “”, “MODE CYFS” displays on the screen (three time sections temperature control) Press “SET” button, “CYFS” blinks Press “”, “” button to select the temperature control mode Press “SET”or “ESC” button, to confirm the setting

Press “”, “STAT ON” displays on the screen (condition of pump trigger -on, only available at three time – sections temperature control mode) Press “SET” button, “ON” blinks (default set is ON, activate this function) Press “”, “” button to deactivate the function, “STATOFF” displays on the screen Press “SET”or “ESC” button, to confirm the setting

Press “”, “CYCO 40oC” displays on the screen ( if flowcontrolmodeCYFSON then here displays “CYCO 03Min”,
heretake temperature as example) Press “SET” button, “40oC” blinks Press “”, “” button to adjust the switch-on temperature of DHW circuit pump, adjustable range 0oC ~ (OFF-2oC) Press “SET”or “ESC” button, to confirm the setting

Page 51 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “”, “CYCF 45oC” displays on the screen Press “SET” button, “45oC” blinks Press “”, “” button to adjust the switch-off temperature of DHW circuit pump, adjustable range (ON+2oC) ~OFF Press “SET”or “ESC” button, to confirm the setting
Press “”, “tC1O 05:00” displays on the screen, to set the start time of the first time-section. Press “SET” button, hour time “05” blinks Press “”, “” button to adjust time hour of the start time of the first time-section Press “SET” button, minute time “00” blinks Press “”, “” button to adjust time minute of the start time of the first time-section Press “SET”or “ESC” button, to confirm the setting
Press “”, “tC1F 07:00” displays on the screen, to set the close time of the first time-section. Press “SET” button, hour time “07” blinks Press “”, “” button to adjust time hour of the close time of the first time-section Press “SET” button, minute time “00” blinks Press “”, “” button to adjust time minute of the close time of the first time-section Press “SET”or “ESC” button, to confirm the setting
Press “”, to access the setting of the start time of the second time-section, doing like above descript steps to set the start and close time of second and third time -section. If it is needed to close one time – section, then just set the start time and close time with a same time. (example: at 10:00 start circuit, and at 10:00 close the circuit) 7. Function operation and parameter setting (expertise) 4PRSWD password
Menu structure
Page 52 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Main menu PRSWD

Default set Adjust range 0000

Description Enter password

Press” SET” button access the main menu, press “” and select “PRSWD 0000”. Function set: Press “SET”button, the left first digital blinks to ask for entering the password, default password is”0000” Press “”, “” button to enter the first digital Press “SET” button, the second digital blinks Press “”, “” button to enter the second digital Press “SET” button, the third digital blinks Press “”, “” button to enter the third digital Press “SET” button, the forth digital blinks Press “”, “” button to enter the forth digital Press “SET”to access the main menu Through the password to limit the right of customers to set some important parameters, and four digitals are required to enter, default password is “0000”. If no password is reset, then please press “SET” five times to access main menu directly.
5SYS system selection Main menu

Main menu SYS

Default set System 1

Adjust range System 1-19

Description System selection

For every system, there are many pre-programmed options and setting, they can be activated or adjusted according the system requirement. 19 systems areavailableto be selected in this controller.

Press “SET” button to select main menu “SYS”

Page 53 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “SET” button, “SYS 1” displays on the screen Press “SET” button, “1” blinks Press “”, “” button to select system Press “SET”or “ESC” button, to confirm the setting 67LOAD/LOAD2 Tank heating set Function description:
T DT Temperature difference The controller works with a standard differential control logic. If the temperature reaches or exceeds the switch-on temperature difference (DTO), the pump switches on. When the temperature difference reaches or falls below the adjusted switch-off temperature difference DTF, the respective relay switches off.
Note:The switch-on temperature difference must be 0.5K higher than the switch- off temperature difference. The set temperature difference must be at least 0.5K higher than the switch-on temperature difference.
Note: In systems with 2 tanks or tank loading in layers, 2 separate menus(LOAD and LOAD 2) will be displayed.
Speed control If the temperature reaches or exceeds the switch-on temperature difference, the pump switches on at 100% speed for 10s. Then, the speed is reduced to the minimum pump speed value. If the temperature difference reaches the set temperature difference DTS, the pump speed increases by one step (10%). The response of the controller can be adapted via the parameter RIS. If the difference increases by the adjustable rise value RIS, the pump speed increases by 10% until the maximum pump speed of 100% is reached. If the temperature difference decreases by the adjustable rise value RIS, pump speed will be decreased by one step 10%.
Note: To enable speed control, the corresponding pump should be set to (MIN, MAX) and relay control should be set to (PULS, PSOL, PHEA or 0-10 V) (under adjustment menu PUMP).
SMAX Maximum tank temperature protection set If the tank temperature reaches the pre-set maximum temperature, the tank will no longer be
Page 54 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

loaded to avoid damage caused by overheating. If the maximum tank temperature is

exceeded, Max icon

is displayed and code SMX displays.

The sensor for tank maximum limitation (SMAXS) can be selected. The maximum limitation always refers to the sensor selected. The switch-on hysteresis (HYST) is selectable. Default is 2oCfor example, when tank maximum temperature is set to 70oC, then at 68 oC, Maximum tank temperature protection function is deactivated automatically.

Mainm enu
LOAD

Submenu
DTO DTF DTS RIS

SMAX SMAXS

HYST

LOAD2

DT2O DT2F DT2S

RIS2

S2MAX SMAXS

HYST2

Default Set
6K 4K 10K 2K
70 T2
2K
6K 4K 10K
2K
70 T4
2K

Adjustran ge
1-50K 0.5-49.5K 1.5-50K 1-20K
4-95 T2.T3
0.1-10K
1-50K 0.5-49.5K 1.5-50K
1-20K
4-95 T4.T5
0.1-10K

Adjust step 0.5K 0.5K 0.5K 1K
1
0.1K
0.5K 0.5K 0.5K 1K
1
0.1K

Main menu
Tank1 loading set Switch-on temperature of tank 1 Switch-offtemperatureoftank1 Temperature difference for pump speed control Temperature increase rate for pump speed control Maximum temperature of tank 1
Sensor select for maximum temperature of tank 1 Temperature hysteresis of maximum temperature of tank 1 Tank2 loading set Switch-on temperature of tank 2 Switch-offtemperatureoftank2 Temperature difference for pump speed control of tank 2 Temperature increase rate of pump speed control of tank 2 Maximum temperature of tank 2
Sensor select for maximum temperature of tank 2 Temperature hysteresis of maximum temperature of tank 2

Function set: Press “SET” button to select main menu “LOAD” Press “SET” button, “DTO6K” displays on the screen Press “SET” button, “6K” blinks Press “”, “” button to adjust the switch-on temperature difference of the circuit pump. Press “SET”or “ESC” button, to confirm the setting

Page 55 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “” button, “DTF 4K” display on the screen Press “SET” button, “4K” blinks Press “”, “” button to adjust the switch-off temperature difference of the circuit pump. Press “SET”or “ESC” button, to confirm the setting Press “” button, “DTS 10K” display on the screen Press “SET” button, “10K” blinks Press “”, “” button to adjust the standard temperature difference of the circuit pump. Press “SET”or “ESC” button, to confirm the setting Press “” button, “RIS2K” display on the screen Press “SET” button, “2K” blinks Press “”, “” button to adjust the temperature difference increase rate of the circuit pump. Press “SET”or “ESC” button, to confirm the setting Press “” button, “SMAX70oC” display on the screen Press “SET” button, “70oC” blinks Press “”, “” button to adjust the maximum temperature of tank Press “SET”or “ESC” button, to confirm the setting Press “” button, “SMAXS T2” display on the screen Press “SET” button, “T2” blinks Press “”, “” button to select sensor used for measuring the maximum temperature of tank. Press “SET”or “ESC” button, to confirm the setting Press “” button, “HYST 2K” display on the screen Press “SET” button, “2K” blinks Press “”, “” button to adjust the hysteresis temperature of the maximum temperature of tank Press “SET”or “ESC” button, to confirm the setting Load 2 function is set same like above steps.
89COL/COL2 Collector function Function description:
OCEM (2) Collector emergency shutdown When the collector temperature exceeds the adjusted collector emergency temperature, Then solar pump R1(2) switches off to protect the system components against overheating
Page 56 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

(collector emergency shutdown). If the maximum collector temperature is exceededOCEM,

Warning iconis

displayed and code CEM displays.

Note: In systems with east- / west collectors, 2 separate menus (COL and COL 2) will be displayed. Warning! Risk of injury! Risk of system damage by pressure surge! If water is used as the heat transfer fluid in pressure systems, water will boil at 100 °C. Do not set the collector limit temperature higher than 95 °C.

OCCO(2) Collector cooling The collector cooling function is designed to keep the temperature increase of collector within the operating range by the way of heating tank. If the tank temperature reaches 95 °C, this function will switch off the pump due to safety of system.

When the tank temperature exceeds the pre-set maximum tank temperature, then solar pump is switched off. And then collector temperature may rise, if the collector temperature rises to its maximum temperature, the solar pump is switched on again to transfer the energy from collector to tank, pump keeps running until the collector temperature falls below the maximum collector temperature, in this heating process, tank temperature may exceed its maximum temperature, but only up to 95°C (emergency shutdown of the tank),both icons
are blinks on the screen and code LEM displays, and then pump is stopped.

If the collector cooling is activated, is displayed and code CMAX displays.

This function is only available when the system cooling function (OSYC) and the heat transfer function(OHDP) are deactivated.

OCMI (2) Collector minimum temperature

The minimum collector temperature is the lowest switch-on temperature for triggering the solar

pumpR1(2), If the collector temperature falls below the minimum temperature,

is

displayed and code CMIN displays.

OCFR(2)Collector antifreeze function When the collector temperature falls below the switch-on temperature CFRO(2)of antifreeze function, this function activates the solar pump to circuit system between collector and tank.

Page 57 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
This will protect the fluid against freezing or coagulating. If collector temperature rises and exceeds the switch-off temperature CFRF(2)of anti-freeze function, the solar pump will be switched off.

If collector antifreeze function is activated, If collector antifreeze function is running, displays.

is displayed on the screen. are blinks on the screen, and code CFRO

Note: Since this function uses the limited heat energy stored in the tank, the antifreeze function should be used only in regions with few days of temperatures around the freezing point.

OTCO (2)Tube collector function This function is used for improving the switch-on behavior in systems with non-ideal sensor positions (e. g. with some tube collectors).

This function operates within a pre-set time – section. It activates the collector circuit pumpR1(2) intermittently to compensate for the delayed temperature measurement caused by poor sensor position.

If the runtime is set to more than 10s, the pump will run at 100% speed during the first10s, and pump will run at the minimum speed during the remaining runtime.

If the collector sensor is defective, this function will be switched off.

In 2-collectorfields systems, the tube collector function is available for each individual collector field.

In 2-collector fields systems, the tube collector function will affect the inactive collector field only. The solar pump of the active collector field will remain switched on until the switch-off conditions are fulfilled.

Page 58 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Menu structure

Mainm enu
COL

Submen u 1
OCEM

Submen Default

u 2

Set

ON

CEM

130

OCCO OCMI OCFR
OTCO

CMAX
CMIN CFRO CFRF
TCST TCEN TCRU TCIN

OFF 110
OFF
10 OFF 4
5
OFF 07:00 19:00
30s 30min

Adjustrange
80-200
70-160
10-90 -40-8 -39-9 00:00-23:00 00:00-23:00 30-300s 5-60min

Adjust step
1
1
1 0.5 0.5 1min 1min 1s 1min

Main menu
Collector function Emergency shutdown function of collector 1 Switch-off temperature difference of emergency shutdown of collector 1 (hysteresis 10oC) Collector 1coolingfunction Collector1coolingtemperature hysteresis5oC Minimum temperature function of
collector 1 Minimum temperature of collector 1
Anti-freeze function of collector 1 Switch-on temperature of anti-freeze function of collector 1 Switch-off temperature of anti-freeze function of collector 1 Tube collector function 1 Start time of tube collector function 1 Close time of tube collector function 1 Run time of tube collector function 1 Stop time of tube collector function 1

Page 59 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Mainm enu
COL2

Submen u 1
OCEM2

Submen Default

u 2

Set

ON

Adjustrange

Adjust step

Main menu
Collector 2 function Emergency shutdown function of collector 2

CEM2

130

80-200

1

Switch-off temperature difference of

emergency shutdown of collector 2

(hysteresis 20oC)

OCCO2

OFF

Collector 2coolingfunction

CMAX2 110

70-160

1

Collector2coolingtemperature

hysteresis5oC

OCMI2

OFF

Minimum temperature function of

collector 2

OCFR2 OTCO2

CMIN2 CFRO2 CFRF2
TCST2 TCEN2

10 OFF 4
5
OFF 07:00 19:00

TCRU2 TCIN2

30s 30min

10-90
-40-8 -39-9
00:00-23:00 00:00-23:00 30-300s 5-60min

1
0.5 0.5
1min 1min 1s 1min

Minimum temperature of collector 2
Anti-freeze function of collector 2 Switch-on temperature of anti-freeze function of collector 2 Switch-off temperature of anti-freeze function of collector 2 Tube collector function 2 Start time of tube collector function 2 Close time of tube collector function 2 Run time of tube collector function 2 Stop time of tube collector function 2

Function setting: OCEM(Collector emergency shutdown function) Press “SET” button to select main menu “COL” Press “SET” button, “OCEM” displays on the screen Press “SET” button, “OCEM ON” displays on the screen. Press “SET” button, “ON” blinks If to close the function, then press “”, “” to switch to “OFF” Press “SET”or “ESC” button, to confirm the setting Press “”, “CEM 130oC”displays on the screen Press “SET” button, “130oC” blinks Press “”, “” button to adjust the switch-off temperature of the collector emergency shutdown function Press “SET”or “ESC” button, to confirm the setting

Page 60 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “ESC” button to return to the previous menu
OCCO (Collector cooling function) setting Press “”, “OCCO” displays on the screen Press “SET” button, “OCCO OFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate this function, “OCCO ON” displays on the screen Press “”, “CMAX 110oC” displays on the screen Press “SET” button, “110oC” blinks Press “”, “” button to adjust the collector cooling temperature Press “SET”or “ESC” button, to confirm the setting Press “ESC” button to return to the previous menu
OCMI(Minimum collector temperature) setting Press “”, “OCMI” displays on the screen Press “SET” button, “OCMI OFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate this function, “OCMI ON” displays on the screen Press “”, “CMIN 10oC” displays on the screen Press “SET” button, “10oC” blinks Press “”, “” button to adjust the collector minimum temperature Press “SET”or “ESC” button, to confirm the setting Press “ESC” button to return to the previous menu
OCFR (Anti-freezing function) setting Press “”, “OCFR” displays on the screen Press “SET” button, “OCFR OFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate this function, “OCFR ON” displays on the screen Press “”, “CFRO4oC” displays on the screen Press “SET” button, “4oC” blinks Press “”, “” button to adjust the switch-on temperature of
Page 61 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 anti-freezing function Press “SET”or “ESC” button, to confirm the setting Press “”, “” button to activate this function, “OCFR ON” displays on the screen Press “”, “CFRF 5oC” displays on the screen Press “SET” button, “5oC” blinks Press “”, “” button to adjust the switch-off temperature of anti-freezing function Press “SET”or “ESC” button, to confirm the setting Press “ESC” button to return to the previous menu OTCO (Tube collector function) set Press “”, “OTCO” displays on the screen Press “SET” button, “OTCO OFF” displays on the screen Press “SET” button, “OFF” blinks Press “”, “” button to activate this function, “OTCO ON” displays on the screen Press “”, “TCST 07:00” displays on the screen Press “SET” button, hour “07” blinks Press “”, “” button to adjust time hour of this function Press “SET” button, minute “00” blinks Press “”, “” button to adjust time minute of this function Press “SET”or “ESC” button, to confirm the setting Press “”, “TCEN 19:00” displays on the screen Press “SET” button, hour “19” blinks Press “”, “” button to adjust time hour of this function Press “SET” button, minute “00” blinks Press “”, “” button to adjust time minute of this function Press “SET”or “ESC” button, to confirm the setting Press “”, “TCRU 30” displays on the screen Press “SET” button, runtime “30” blinks Press “”, “” button to adjust the runtime (unit: second) Press “SET”or “ESC” button, to confirm the setting Press “”, “TCIN 30Min” displays on the screen Press “SET” button, runtime “30” blinks Press “”, “” button to adjust the stop time (unit: second) Press “SET”or “ESC” button, to confirm the setting
Page 62 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “ESC” button to return to the previous menu For COL2 function, its setup steps are same as above description.
10PINTV Swimming pool function This function is designed to improve the operation of swimming pool system, in which sensor position is not ideal.
This function operates within a pre-set time – section. It activates the swimming pool circuit pump R1 or R2 intermittently to compensate for the delayed temperature measurement caused by poor sensor position.
If the runtime is set to more than 10s, the pump will run at 100% speed during the first 10s, and pump will run at the minimum speed during the remaining runtime.
Menu structure

Main menu PINTV

Submenu

Default set

tPST

00:00

tPEN tPRU tPIN

23:59 30S 30MIN

Adjust range

Adjust step

00:00-23:59 30min

00:00-23:59 30-300s 5-60min

30min 5s 1min

Description
Swimming pool function Start time of swimming pool function Stop time of swimming pool function Runtime of swimming pool function Stop time of swimming pool function

Function setting: PINTV(Swimming pool function) Press “SET” button to select main menu “PINTV” Press “SET” button, “PINTVOFF” displays on the screen Press “SET” button, “OFF” displays on the screen

Page 63 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “”, “”button, to activate this function, “PINTVON” displays Press “SET” or “ESC” button, to confirm the setting Press “”, “tPST 00:00” displays on the screen Press “SET” button, hour “00” blinks Press “”, “” button to adjust hour of the start time of swimming pool function Press “SET” button, minute “00” blinks Press “”, “” button to adjust minute of the start time of swimming pool function Press “SET”or “ESC” button, to confirm the setting Press “”, “tPEN 23:59” displays on the screen Press “SET” button, hour “23” blinks Press “”, “” button to adjust hour of the close time of swimming pool function Press “SET” button, minute “59” blinks Press “”, “” button to adjust minute of the close time of swimming pool function Press “SET”or “ESC” button, to confirm the setting Press “”, “tPRU 30” displays on the screen Press “SET” button, time “30” blinks Press “”, “” button to adjust runtime of the swimming pool function (unit: second) Press “SET”or “ESC” button, to confirm the setting Press “”, “tPIN 30MIN” displays on the screen Press “SET” button, time “30” blinks Press “”, “” button to adjust stop time of the swimming pool function (unit: minute) Press “SET”or “ESC” button, to confirm the setting
11PUMP Pump control mode Function description: With this parameter, the control mode of pump’s relay can be adjusted. The following types can be selected:
Control mode for standard pump without speed control: OnOF: Pump on / pump off
Control mode for standard pump with speed control: PULS: Burst control via semiconductor relay
Control mode for high-efficiency pump (HE pump)
Page 64 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 · PSOL: PWM signal logic of solar pump
· PHEA: PWM signal logic of heating pump
· 0-10: PWM 0 – 10 V signal logic of Speed control
Note: 1. More information about connection of high efficiency pump see paragraph3.3 2. Minimum pump speed: Under the adjustment menu MIN1 (2, 3), a relative minimum
speed for the connected pump can be allocated to the outputs R1(2,3) 3. Maximum pump speed:Under the adjustment menu MAX1 (2, 3), a relative maximum
speed for the connected pump can be allocated to the outputs R1(2,3) 4. When the devices which are not speed-controlled are used (e. g. valves), the pump
Page 65 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
speed value of the corresponding relay must be set to 100 % or the control type must be set to ON/OF to deactivate pump speed control 5. Allocation for PWM output relay: a relay can be allocated to a PWM output;PWM1 for R1, PWM2 for R2,PWM3 for R3 Menu structure

Main menu PUMP

Submenu 1 Subme nu 2
PMP1(2,3) ONOF
PULS

Subme nu3
MIN1 MAX1

Default Set
ON
OFF 50% 100%

Adjustra nge
ON/OFF
ON/OFF 20-95% 25-100%

Adjust step
5% 5%

Description
Pump control mode Pump R1(R2, R3) selection ON/OFF control of standard pump, (without pump speed adjust) Pulse control of standard pump (through semiconductor relay)

PSOL PHEA 0-10

MIN1 MAX1
MIN1 MAX1
MIN1 MAX1

OFF 50% 100% OFF 50% 100% OFF 50% 100%

ON/OFF 20-95% 5% 25-100% 5% ON/OFF
20-95% 5% 25-100% 5% ON/OFF 20-95% 5% 25-100% 5%

PWM profile solar pump
PWM profile heating pump
0-10V signal control pump speed

Function set: Press “SET” button to select main menu “PUMP” Press “SET” button, “PMP1” displays on the screen (pump R1 control type selection)

Page 66 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “SET” button, “ONOF ON” displays on the screen Press “”, “”button, to select pump control type “PLUS, PSOL, PHEA, 0-10V” After select pump type, press “SET”to access the pump type window Press “SET” button, “OFF” blinks Press “”, “” button to activate the selected pump type Press “SET”or “ESC” button, to confirm the setting Press “ESC” button to return to the previous menu Press “”to access the PMP2 set (pump R2 control mode selection)
Note: 1.PMP2, PMP3 setup step is same as PMP1 2. only one type can be selected from five types ONOFPLUSPSOLPHEA0-10V Example: if you select “PLUS ON” type, then the others are closed automatically.
12LLOGI Tank priority logic Priority logic Priority logic is designed for systems with 2-tanks or systems with tank loading in layers; it determines how the heat is divided between the tanks. Several different priority logic types can be selected: Tanks loading in sequence (1 and 2) Successive loading (Su 1 and Su 2) Parallel loading (0) Tanks heated in sequence (1 and 2) If the priority tank is not loaded because its switch-on condition is not reached, then the subordinate tank is checked whether its switch-on condition is reached, if yes, then it is loaded during the circulation runtime (tRUN). After runtime, heating process stops, then break time timer tLB starts to ensure collector to receive more solar energy, during the break time,if the priority tank switch-on condition is still not reached, then the subordinate tank will be loaded again for the circulation runtime.
As soon as the priority tank meets its switch-on condition, controller triggers to heat it immediately, if the priority tank’s switch-on condition is still not reached, controller heats the subordinate tank continuously. If the priority tank reaches to its preset temperature, and then tank heated sequence function is stopped.
Page 67 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 In systems with 2 tanks or tank loading in layers, all tanks or zones will be heated to its preset temperature firstly (base the priority and sequence control logic). Only when all tanks or zoneshave exceeded its preset temperature, they just can be heated to their maximum temperature continuously, and it is also heated base the priority and sequence control logic.
If the tank sequence heating function is activated and system is switched to heat the priority tank, then parameter “heating break time” can also act as stabilization time, during which the switch – off temperature difference will be ignored while the system operation stabilizes.
Successive loading (Su 1 and Su 2) Successive loading means that the priority tank will be heated to its maximum temperature. After the priority tank reaches its maximum temperature, then the second tank will just be heated. If the temperature of the priority tank falls below its pre-set temperature, then the second tank will no longer be heated, regardless of whether the switch-on condition of the priority tank or the second tank is met.
If both tanks are heated to their preset temperature, the same process will occur until the tank reaches its maximum temperature
Parallel loading (0) In systems with 2 pumps, if parallel loading control logic is selected, 2 tanks will be heated parallelly. In system with 3 – ways valve, tank which temperature is lower will be heated in advance until its temperature is 5K higher than another tank, and then the second tank just can be heated. Two tanks are alternately heated with a 5K temperature difference.
OSTS Tank set option (only available at LLOGI/PRIO 1or 2 mode) If the priority tank reaches its pre-set temperature, then the subordinate tank will be heated until to its set temperature. After this, priority tank can be loaded to its maximum temperature, and then system is switched to load the subordinate tank. This function is suitable for 2 tanks’ system.
OSE Spread loading function (only available at LLOGI/PRIO1,2,Su1 or Su2mode) Insystem5, spread loading function will be activated. When the spread temperature difference DTSE between collector and priority tank is reached, the second tank will be loaded in parallel unless it is blocked. If the spread temperature
Page 68 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 difference falls 2K below DTSE temperature, the pump will be switched off. The collector temperature should be higher than the tank temperature.
PDELR Pump delay running Considering the trigger-on time of the electromagnetic valve this function delays the start of the pump, if this function is activated, corresponding valve relay is triggered firstly, and pump is delayed starting in 20 seconds. Menu structure

Mainm enu
LLOGI

Subm enu 1
PRIO

Subme nu 2

tLB tRUN OSTS

OSE PDELR

Submen Default

u3

Set

1

2min 15min OFF

TST1 TST2
DTSE

45
45 OFF 40K

0FF

Adjust Adjustrange step

1/2/SU1/SU
2/0 1-30min 1-30min ON/OFF

1min 1min

4-85

1

4-85

1

ON/OFF

20-90K

1K

ON/OFF

Description
Tank heating logic Tank priority logic
Heating runtime Heating rest time Tank temperature set option Temperature set of tank 1
Temperature set of tank2
Spread loading function Spread temperature difference Pump delay running function

Function set: Press “SET” button to select main menu “LLOGI”
Press “SET” button, “PRIO 1” displays on the screen (here takePRIO1 as example)

Page 69 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “SET” button, “1” blinks on the screen Press “”, “”button, to select tank priority logic Press “SET”or “ESC” button, to confirm the setting Press “”, “tLB 2min” displays on the screen Press “SET” button, “2min” blinks on the screen Press “”, “”button, to adjust the runtime of heating Press “SET”or “ESC” button, to confirm the setting Press “”, “tRUN 15min” displays on the screen Press “SET” button, “15min” blinks on the screen Press “”, “”button, to adjust the break time of heating Press “SET”or “ESC” button, to confirm the setting Press “”, “OSTSOFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate tank temperature set function Press “SET”or “ESC” button, to confirm the setting Press “”, “TST1 45oC” displays on the screen Press “SET” button, “45oC” blinks on the screen Press “”, “”button, to adjust the temperature of tank 1 Press “SET”or “ESC” button, to confirm the setting Press “”, “TST2 45oC” displays on the screen Press “SET” button, “45oC” blinks on the screen Press “”, “”button, to adjust the temperature of tank 2 Press “SET”or “ESC” button, to confirm the setting Press “”, “OSE OFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate spread loading function Press “SET”or “ESC” button, to confirm the setting Press “”, “DTSE 40K” displays on the screen Press “SET” button, “40K” blinks on the screen Press “”, “”button, to adjust the spread temperature difference Press “SET”or “ESC” button, to confirm the setting Press “”, “PDELR OFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate the pump delay running function Press “SET”or “ESC” button, to confirm the setting
Page 70 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Press “ESC” button, to return to the previous menu
13COOL Cooling function Function description: Different cooling functions for different devices can be activated: system cooling, tank cooling and external radiator heat transfer.

OSYC System cooling

The system cooling function is designed to keep the solar system operation for a longer time.

The function overrides the maximum tank temperature to transfer the energy from collector

field to the tank. If the tank temperature is higher than its maximum tank temperature already

and the switch-on temperature difference of this function DTCO is reached, then the solar

pump remains running. Solar loading is continued until either the temperature difference falls

below the switch-off temperature DTCF or the collector emergency temperature OCEM

reaches

If the system cooling function is running, then

icon displays, and

icon blinks on

the screen, code OSYC displays on the screen.

Note:This function will only be available when the collector cooling function, external radiator heat transfer functions are not activated.

OSTC Tank cooling

When the tank cooling function is activated, this function is designed to cool down the tank

during the night and provide possibility for solar loading on the following day. If the maximum

tank temperature SMAX is exceeded, the collector temperature falls below the tank

temperature, and it is below the switch on temperature difference DTCO of this cooling

function, then system will be activated to cool down the tank by releasing the energy through

the collector in night

If the tank cooling function is running, icon

displays, and icon

blinks on the

screen, code OSTC displays.

Note: if tank temperature reaches to 95 oC, all cooling functions will be locked. Hysteresis switch on temperature difference is 5K.

OHDP external radiator heat transfer Note

Page 71 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
1. According to the selected system, several auxiliary functions are allocated with a same relay output, at this case, then only one of the several auxiliary functions can be activated, the other functions will be deactivated automatically, its function displays “NONE”.
2. According the different selected system, see paragraph 4.1, the function will assign to different output ports)
Under strong solar irradiation, external radiator heat transfer function is designed to release the excess thermal energy generated by solar system through an external heat exchanger (e. g. fan coil), aim is to keep the temperature of collector or tank within its operation range. For this function, an extra output RX should be added. (system is different, the output relay of circuit pump RX may be different also, detailed allocation see diagram showed in system description)
External radiator heat transfer function can either control an additional pump or valve (OTPUM ON = pump logic, OTPUM OFF = valve logic).
Heat transfer by pump logic: If the collector temperature reaches the switch- on temperature(OTST), the heat transfer pump(RX) on. if the collector temperature falls 5 K below heat transfer temperature(OTST),the heat transfer pump(RX) off. Heat transfer by valve logic: If the collector temperature reaches the switch-on temperature(OTST), the heat transfer valve(RX) and circuit pump(R1) on. if the collector temperature falls 5 K below heat transfer temperature(OTST),the heat transfer valve(RX) and circuit pump(R1) off.
Below is the example of this application for reference.

Heat transfer by collector valve logic

Heat transfer by collector pump logic

Page 72 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

Icon

displays on the screen, it indicates that valve heat transfer function is activated.

Icon

displays on the screen, it indicates that pump heat transfer function is activated.

Note: 1. The collector over-temperature value OTST is blocked 10K lower against the collector
emergency temperature CEM. 2. This function will only be available when the collector cooling function “OCCO” and the
system cooling function “OSYC” are deactivated. Menu structure

Main menu COOL

Subme nu 1
OSYC OSTC

Submen u 2
DTCO

Default Set

Adjustrange

OFF

ON/OFF

OFF

ON/OFF

20K

1-30K

DTCF

15K

0.5-29.5K

OHDP

OFF

ON/OFF

OTST

80

OTPUM ON

20-160
OTPM ON=pump logic OTPM OFF=valve logic

Adjust step
0.5K 0.5K
1

Description
Cooling function System cooling Tank cooling Switch-on temperature difference of cooling Switch-off temperature difference of cooling Heat transfer ­ by extra heat exchanger (only available when there is free relay) Temperature set of heat transfer (Hysteresis 5oC) Pump and valve logic selection

Function set: OSYC System cooling function set Press “SET” button to select main menu “COOL”

Page 73 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “SET” button, “OSYC OFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate this cooling function, “OSYC ON” displays on the screen Press “SET”or “ESC” button, to confirm the setting
OSTC Tank cooling function set Press “”, “OSTC” displays on the screen Press “SET” button, “OSTC OFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate this cooling function, “OSTC ON” displays on the screen Press “SET”or “ESC” button, to confirm the setting Press “”, “DTCO20K” displays on the screen Press “SET” button, “20K” blinks on the screen Press “”, “”button, to adjust the switch-on temperature of cooling function, Press “SET”or “ESC” button, to confirm the setting Press “”, “DTCF 15K” displays on the screen Press “SET” button, “15K” blinks on the screen Press “”, “”button, to adjust the switch-off temperature of cooling function, Press “SET”or “ESC” button, to confirm the setting Press “ESC” button, to return to the previous menu
OHDP Heat transfer function set Press “”, “OHDP” displays on the screen Press “SET” button, “OHDP OFF” displays on the screen
Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate this cooling function, “OHDP ON” displays on the screen Press “SET”or “ESC” button, to confirm the setting Press “”, “OTST 80oC” displays on the screen Press “SET” button, “80oC” blinks on the screen Press “”, “”button, to adjust the switch-on temperature of heat
Page 74 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
transfer function, Press “SET”or “ESC” button, to confirm the setting Press “”, “OTPUM ON” displays on the screen Press “SET” button, “ON” blinks on the screen Press “”, “”button, to adjust the pump or valve logic of heat transfer function, Press “SET”or “ESC” button, to confirm the setting Press “ESC” button, to return to the previous menu
14HEATX Energy exchange between tanks
Note: this function is only available in system 3 and system 18.
The heat exchange function is designed to transfer heat from a heat source tank to another heated tank. The relay is energized when all switch-on conditions below listed are met: 1. The temperature difference between the sensor of heat source tank and heated tank has
exceeded the switch-on temperature difference DTHXO. 2. The temperature at the heat source sensor has exceeded its minimum temperature
MINHXO 3. The temperature at the heated tank sensor is below its maximum temperature MXHXO. 4. When the set temperature difference is exceeded, pump speed control starts. For every
decrease or increase by the rise value, the pump speed will be adjusted by 10%.
Menu structure

Mainm enu
HEATX

Submen u 1

Default Set
0FF

Adjustrang e
ON/OFF

Adjust step

Description Heat transfer between tanks

Page 75 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658

DTHXO 6K

1-50K

0.5K

DTHXF 4K

0.5-49.5K 0.5K

DTHXS 10K

1.5-50K

0.5K

RISHX

2K

1-20K

1K

MXHXO 70 MNHXO 60

0.5-95 0.5 0.5-89.5 0.5

Switch-on temperature difference of heat transfer between tanks Switch-off temperature difference of heat transfer between tanks Pump speed control – Temperature difference of two tanks Pump speed control ­ Temperature increase range of two tanks Maximum temperature of heated tank(Hysteresis 2oC) Minimum temperature of heat source tank (Hysteresis 2oC)

Function set: Press “SET” button to select main menu “HEATX” Press “SET” button, “DTHXO6K” displays on the screen
Press “SET” button, “6K” blinks on the screen Press “”, “”button, to adjust the switch-on temperature difference of heat transfer between 2 tanks Press “SET”or “ESC” button, to confirm the setting Press “”, “DTHXF 4K” displays on the screen Press “SET” button, “4K” blinks on the screen
Press “”, “”button, to adjust the switch-off temperature difference of heat transfer between 2 tanks Press “SET”or “ESC” button, to confirm the setting Press “”, “DTHXS 10K” displays on the screen Press “SET” button, “10K” blinks on the screen Press “”, “”button, to adjust the standard temperature difference of circuit pump Press “SET”or “ESC” button, to confirm the setting Press “”, “RISHX2K” displays on the screen Press “SET” button, “2K” blinks on the screen Press “”, “”button, to adjust the temperature increase range Press “SET”or “ESC” button, to confirm the setting Press “”, “MXHXO70oC” displays on the screen

Page 76 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Press “SET” button, “70oC” blinks on the screen Press “”, “”button, to adjust the maximum temperature of heated tank Press “SET”or “ESC” button, to confirm the setting Press “”, “MINHXO 60oC” displays on the screen Press “SET” button, “60oC” blinks on the screen Press “”, “”button, to adjust the minimum temperature of heat source tank Press “SET”or “ESC” button, to confirm the setting Press “ESC”, to return the previous menu
15RPH Heating return pipe preheat Function description:
Note: this function is available in system 10,11,12,19 The heating return pipe preheat function is designed to transfer energy from a heat source to the heating circuit return. The relay is energized when both switch-on conditions are met:
· The temperature difference between the sensor of heat source tank and sensor of the heating circuit return has exceeded the switch-on temperature difference DTRPO. · The temperature at the heating circuit return has exceeded its minimum temperature MNRPH, the switch-on hysteresis is -5 K.
Menu structure

Mainm enu
RPH

Submenu 1
TANK DTRPO DTRPF MNRPH

Default Set
0FF
T4 6K 4K 30

Adjustrang e
ON/OFF

Adjust step

Description Heating return pipe heat function

T2,T3,T4 1-50K 0.5-49.5K 1.5-89.5

0.5K 0.5K 0.5

Tank sensor selection Switch-on temperature difference Switch-on temperature difference Minimum temperature of heating return pipe (hysteresis 5oC)

Page 77 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
Function set: Press “SET” button to select main menu “RPH” Press “SET” button, “TANK T4” displays on the screen Press “SET” button, “T4” blinks on the screen Press “”, “”button, to select the sensor for heating return pipe heat function Press “SET”or “ESC” button, to confirm the setting Press “”, “DTRPO6K” displays on the screen Press “SET” button, “6K” blinks on the screen Press “”, “”button, to adjust the switch-on temperature Press “SET”or “ESC” button, to confirm the setting Press “”, “DTRPF4K” displays on the screen Press “SET” button, “4K” blinks on the screen Press “”, “”button, to adjust the switch-off temperature Press “SET” or “ESC” button, to confirm the setting Press “”, “MNRPH30oC” displays on the screen Press “SET” button, “30oC” blinks on the screen Press “”, “”button, to adjust the minimum temperature of heating return pipe Press “SET” or “ESC” button, to confirm the setting 16DLHTX Thermal energy transferring between 2 tanks
Note: this function is only available in system 13. Function description: Thermal energy transferred from tank 1 to tank 2 When tank 1 temperature reaches to the switch-on temperature L1H2O, and temperature of tank 1 is higher than tank 2’s, thermal energy will be transferred from tank 1 to tank 2, circuit pump R2 is triggered. When tank 1 temperature reaches to the switch-off temperature L1H2For temperature of tank2 rises to the temperature of tank 1, or tank2’s temperature reaches its maximum S2MAX, then circuit pump R2 is stopped.
Thermal energy transferred from tank 2 to tank 1 When tank 2 temperature reaches to the switch-on temperature L2H1O, and temperature of tank 2 is higher than tank 1’s, thermal energy will be transferred from tank 2 to tank 1, circuit pump R3 is triggered. When tank 2 temperature reaches to the switch-off temperature
Page 78 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
L2H1For temperature of tank 1 rises to the temperature of tank 2, or tank1’s temperature reaches its maximum SMAX, then circuit pump R3 is stopped.
Menu structure

Mainm enu
DLHTX

Submenu 1

Default Set

L1H2O L1H2F L2H1O L2H1F

80 60 60 40

Adjustrange
60~90 0~ON-2 30~60 0~ON-2

Adjust step
0.5 0.5 0.5 0.5

Description
Thermal energy transferring between 2 tanks
Switch-on temperature difference for heat transfer from tank1 to tank 2
Switch-off temperature difference for heat transfer from tank1 to tank 2
Switch-on temperature difference for heat transfer from tank2 to tank1
Switch-off temperature difference for heat transfer from tank2 to tank 1

Function set: Press “SET” button to select main menu “DLHTX” Press “SET” button, “L1H2O 80oC” displays on the screen Press “SET” button, “80oC” blinks on the screen Press “”, “”button, to adjust the switch-on temperature of heat transfer from tank 1 to tank 2
Press “SET”or “ESC” button, to confirm the setting Press “” button, “L1H2F60oC” displays on the screen Press “SET” button, “60oC” blinks on the screen Press “”, “”button, to adjust the switch-off temperature of heat transfer from tank 1 to tank 2 Press “SET”or “ESC” button, to confirm the setting Press “” button, “L2H1O 60oC” displays on the screen Press “SET” button, “60oC” blinks on the screen Press “”, “”button, to adjust the switch- on temperature of heat transfer from tank 2 to tank

Page 79 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 1 Press “SET”or “ESC” button, to confirm the setting Press “” button, “L2H1F 40oC” displays on the screen Press “SET” button, “40oC” blinks on the screen Press “”, “”button, to adjust the switch-off temperature of heat transfer from tank 2 to tank 1 Press “SET”or “ESC” button, to confirm the setting 17EXHX External heat exchanger control function
Note: this function is only available in system 4, system 15 and 16.
External heat exchanger function: when temperature difference between collector and tank rises up to the switch-on temperature difference DTO circuit pump R1is triggered to heat the external heat exchanger. When temperature difference between heat exchanger and tank rises to the switch-on temperature DTEXO, and temperature of heat exchanger is higher than the lowest switch-on temperature (MNEXO), then circuit pump R2is triggered to heat tank.
When temperature difference between collector and tank drops to the switch-off temperature DTF or temperature of the heat exchanger rises to its maximum switch-off temperature (MXEXO), then circuit pump R1isstopped.
When temperature difference between heat exchanger and tank drops to the switch-off temperature DTEXF or temperature of heat exchanger drops below its minimum switch-on temperature (MNEXO), then circuit pump R2isstopped.
Note when no sensor is installed on the external heat exchanger or the sensor is damaged, and when temperature difference between collector and tank reaches its switch-on temperature difference (DTO) , then circuit pump R1,R2aretriggered simultaneously. And when temperature difference drops to the switch-off temperature difference (DTF), then R1,R2arestopped simultaneously.
When the temperature difference exceeds its preset value, pump speed control function starts, when value increases a step of reduces a step, pump speed is changed by 10%perstep
Page 80 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Menu structure

Mainmen u
EXHX

Submenu 1

Default Set

DTEXO

5K

DTEXF

3K

DTEXS

10K

RISEX

2K

MXEXO

80 oC

MNEXO 30 oC

Adjustrange

Adjust step

1-50K 0.5-49.5K 1.5-50K
1-20K
0.5-95 oC

0.5K 0.5K 0.5K
1K
0.5 oC

0.5-93 oC

0.5 oC

Description
External heat exchanger control
function R2 switch-on temperature difference R2 switch-off temperature difference Pump speed control- set the temperature difference Pump speed control- set the increase range Maximum switch-off temperature of external heat exchanger (hysteresis 2oC) Maximum switch-on temperature of external heat exchanger (hysteresis 2oC)

Functionset: Press “SET” button to select main menu “THET” Press “SET” button, “DTEXO 5K” displays on the screen Press “SET” button, “5K” blinks on the screen Press “”, “” button, to adjust the switch-on temperature difference Press “SET”or “ESC” button, to confirm the setting Press “” button, “DTEXF3K” displays on the screen Press “SET” button, “3K” blinks on the screen Press “”, “” button, to adjust the switch-off temperature difference Press “SET”or “ESC” button, to confirm the setting

Page 81 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Press “” button, “DTEXS10K” displays on the screen Press “SET” button, “10K” blinks on the screen Press “”, “” button, to adjust the standard temperature difference of pump Press “SET”or “ESC” button, to confirm the setting Press “” button, “RISEX2K” displays on the screen Press “SET” button, “2K” blinks on the screen Press “”, “” button, to adjust the increase range Press “SET”or “ESC” button, to confirm the setting Press “” button, “MXEXO80oC” displays on the screen Press “SET” button, “80oC” blinks on the screen Press “”, “” button, to adjust the maximum switch-off temperature of external heat exchanger Press “SET”or “ESC” button, to confirm the setting Press “” button, “MNEXO30oC” displays on the screen Press “SET” button, “30oC” blinks on the screen Press “”, “” button, to adjust the minimum switch-on temperature of external heat exchanger Press “SET”or “ESC” button, to confirm the setting Press “ESC” button, to return to the previous menu 18SFB Solid fuel boiler function
Note 1.According the different selected system, several auxiliary functions may be assigned to a same output, then only one auxiliary function can be triggered, others will be deactivated automatically, and its function displays “NONE”. 2.According the different selected system, this function will be assigned to the different object sensors and output ports
The solid fuel boiler function is designed to transfer heat from a solid fuel boiler to a tank, for this function, any sensor input and output relay are needed.
The relay is energized when all switch-on conditions are met: The temperature difference between the sensors of solid fuel boiler and heated tank exceeds the switch-on temperature difference.
Page 82 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 The temperature at the solid fuel boiler sensor exceeds its minimum temperature (MINSFO) The temperature at the heated tank is lower than its maximum temperature (MXSFS)
When the preset temperature difference is exceeded, pump speed control starts. For every increase or decrease by the rise value, the pump speed will be adjusted by 10 %. The switch-on hysteresis is -5 K.
Notesensor on the upper part of the heated tank is the priority sensor, if on the upper part no sensor is installed or sensor is damaged, then controller will take the signal from bottom sensor automatically. Menu Structure

Mainmen u
SFB

Submenu 1
DTSFO DTSFF DTSFS

Default Set
OFF 6K 4K 10K

RISSF

2K

MXSFS MNSFO

60 60

Adjustrange Adjust step

ON/OFF

1-50K

0.5K

0.5-49.5K

0.5K

1.5-50K

0.5K

1-20K

1K

0.5-95

0.5

0.5-89.5 0.5

Description
Solid fuel boiler function Switch-on temperature difference Switch-off temperature difference Pump speed control ­ temperature difference set Pump speed control ­ temperature increase rate Maximum temperature of heated tank (hysteresis 2oC) Minimum temperature of solid fuel boiler (hysteresis 2oC)

Page 83 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 Function set: Press “SET” button to select main menu “SFB” Press “SET” button, “SFB OFF” displays on the screen Press “SET” button, “OFF” blinks on the screen Press “”, “”button, to activate this function “SFBON” displays on the screen Press “SET”or “ESC” button, to confirm the setting Press “” button, “DTSFO 6K” displays on the screen Press “SET” button, “6K” blinks on the screen Press “”, “”button, to adjust the switch-on temperature difference Press “SET”or “ESC” button, to confirm the setting Press “” button, “DTSSF 4K” displays on the screen Press “SET” button, “4K” blinks on the screen Press “”, “”button, to adjust the switch-off temperature difference Press “SET”or “ESC” button, to confirm the setting Press “” button, “DTSFS 10K” displays on the screen Press “SET” button, “10K” blinks on the screen Press “”, “”button, to adjust the standard temperature difference for pump circuit Press “SET”or “ESC” button, to confirm the setting Press “” button, “RISSF 2K” displays on the screen Press “SET” button, “2K” blinks on the screen Press “”, “”button, to adjust temperature increase rate Press “SET”or “ESC” button, to confirm the setting Press “” button, “MXSFS 60oC” displays on the screen Press “SET” button, “60oC” blinks on the screen Press “”, “”button, to adjust the switch-off temperature (maximum) of heated tank Press “SET”or “ESC” button, to confirm the setting Press “” button, “MNSFO 60oC” displays on the screen Press “SET” button, “60oC” blinks on the screen Press “”, “”button, to adjust the minimum switch-on temperature of solid fuel boiler Press “SET”or “ESC” button, to confirm the setting Press “ESC” button, to return to the previous menu
Page 84 of 113
Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658 19AUXAuxiliaryfunctions
Notein a system, if several auxiliary functions are all allocated to output R2 (see system description), then only one auxiliary function can be activated, others function will be deactivated automatically, and these functions displays “NONE” Depend on the selected system; following functions may be triggered.

TIMER (Timer function) (According the different selected system, this function will be assigned to the different output ports)
Timer function can trigger controller’s output port at the pre-set time; therefore, an available output is needed.

When

display on the screen, it’s mean that TIMER function is activate. When the icon

flashes, it means that the function is running.

AH Thermostat function
(According the different selected system, this function will be assigned to the different object sensor and output port)

The thermostat function is independent from the solar operation system, it can e. g.be used for

using surplus energy or for back-up heating. (Every day 3 heating time – sections can be set)

Note:

1. AH O <AH F: Thermostat function used for back-up heating

2. AH O >AH F: Thermostat function used for releasing surplus energy from tank.

3. Icon AH displays on the screen, it means thermostat function for back-up heating is

activated. AH flashes, it indicates this function is running.

4. Icon

displays on the screen, it means thermostat function for heating release

is activated, icon flashes, it means that function is running.

Back-up heating

Surplus energy releasing Page 85 of 113

Downloaded from www.Manualslib.com manuals search engine

Operation manual of solar controller SR658
BEEP Beeper fault warning When system has fault (temperature sensor fault, no flow), beeper will