Braeburn 3100 Non-Programmable Thermostat User Manual
- October 30, 2023
- Braeburn
Table of Contents
Braeburn 3100 Non-Programmable Thermostat
View all Braeburn thermostat manual
WARNING!Important Safety Information
- Always turn off the power to the air conditioning or heating system prior to installing, removing, cleaning or servicing the thermostat.
- Read the manual thoroughly prior to installing, programming or operating the thermostat.
- This thermostat is designed for use with a 24 Volt-AC low-voltage multi-stage heat / cool system.
- Do not use this thermostat on systems with voltages higher than 30 Volt-AC.
- This thermostat requires 24 Volt AC power for normal operation and control of the heating or cooling system.
- Wiring must conform to all building codes and ordinances as required by local and national code authorities having jurisdiction.
- Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
- Do not select the COOL mode of operation if the outside temperature is below 50° F (10° C). This could possibly damage the controlled cooling system and may cause personal injury.
- This thermostat should only be used as described in this manual. Any other use is not recommended and will void the warranty.
SPECIFICATIONS
- Electrical Rating: 24 Volt AC (18-30 Volt AC)
- 2 amp maximum load per terminal
- 4 amp total maximum load (all terminals)
- Control Range: 45° – 90° F (7° – 32° C)
- Accuracy: +/- 1° F (+/- .5° C)
- AC Power: 18-30 Volt AC
- Compatibility: Multi-stage heat/cooling systems with up to two stages of heating and two stages of cooling.
- Terminations: R, Y1, Y2, W1, W2, G, O, B, C
INSTALLATION
Replacing Existing Thermostat
- Always turn off power to the air conditioning or heating system prior to removing the existing thermostat.
- Remove the cover of your old thermostat and locate the wire terminals. Do not remove wires from terminals yet.
- Using small pieces of masking tape to label wires prior to removal from terminals. Use the chart below to determine the new terminal designations for your new thermostat.
Old Terminal from New Terminal for Existing Thermostat New Thermostat Terminal Description
R, V-VR or VR-R | R | 24 VAC |
---|---|---|
Y, Y1 or M Y2 | Y1 Y2 | 1st Stage Cooling 2nd Stage Cooling |
W1W2 or W-U | W1W2 | 1st Stage Heating2nd Stage Heating |
G or FO or R | GO | Fan ControlReversing Valve (Cooling) |
BC, X or B | BC | Reversing Valve (Heating)Transformer Common |
After labeling and removing all wires from terminals, unscrew the existing thermostat sub-base from the wall. Make sure to secure wires to prevent them from slipping back into the hole in the wall.
Replacing Existing Thermostat cont
NOTE: This thermostat is for use on low voltage 24 Volt AC multi-stage
heat / cool systems with up to two stages of heating and two stages of cooling
and requires a transformer common wire for proper installation. This
thermostat is not for use on single-stage heating or cooling systems.
Installing Your New Thermostat
NOTE: If you are installing this thermostat in a new installation be sure to locate the thermostat 4 to 5 feet above the floor in accordance with applicable building codes. Make sure to install the thermostat in a location that provides good airflow characteristics and avoid areas behind doors, near corners, air vents, direct sunlight, or near any heat-generating device. Installation in any of these areas could impact thermostat performance.
- Always turn off power to the air conditioning or heating system prior to installing a thermostat.
- Place the system switch on front of the thermostat to the OFF position.
- Place fan control switch on front of the thermostat to the AUTO position.
- Remove front of the thermostat from the sub-base by pressing the release latch on the bottom of the thermostat.
- Place the thermostat sub-base against wall in the desired thermostat location.
- Guide thermostat wires through center hole in the sub-base. Continue to hold it against the wall.
- Mark placement of mounting holes and drill using a 3/16″ drill bit. Gently tap supplied plastic anchors into the holes in the wall.
- Place the sub-base against the wall in the desired location, making sure the mounting holes are aligned and the thermostat wires are properly inserted through an opening in the sub-base.
- Fasten the sub-base to wall using supplied screws.
- Connect wires to quick wiring terminal block as appropriate using the new terminal designations. Refer to the Wiring Diagram section of this manual if required for assistance.
- Make sure all of the wire connections are secure and are not touching any other terminal to prevent electrical shorts and potential damage to the thermostat.
- Turn the front thermostat body over exposing the rear view of the circuit board.
- Locate the internal ˚F / ˚C switch on the circuit board.
- Using your finger, gently flip the switch toward the preferred temperature ˚F / ˚C scale.
- Locate the internal fan option switch, HG (Gas) / HE (Elec) on the circuit board. This switch controls the heating system fan delay. Select gas for gas or oil fired systems. This will allow the furnace to run for a few seconds before initiating the fan. Select electric for systems with electric furnace elements that require the fan to come on immediately.
- Using your finger, gently flip the switch towards the HG (gas) or HE (Elec) selection which indicates the low voltage heating system the thermostat will control.
- Attach the front body of the thermostat to the sub-base of the thermostat being careful to align the terminal pins on the front body with the terminal block on the sub-base.
- Restore system power so you can test installation.
TESTING YOUR NEW THERMOSTAT
WARNING! Read BEFORE Testing
- Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
- Do not select the COOL mode of operation if the outside temperature is below 50° F (10° C). This could possibly damage the controlled cooling system and may cause personal injury.
- This thermostat includes an automatic compressor protection feature to avoid potential damage to the system from short cycling. This thermostat automatically provides a 5-minute delay after turning off the cooling system output to protect the compressor
NOTE: Test your thermostat prior to programming any user settings. Pressing the RESET button will erase any user entries previously programmed. This will erase all user settings and return them to their default values.
- Place the system switch in the HEAT position.
- Press the button on the keypad until the setpoint temperature setting is a minimum of 3 degrees higher than the current room temperature. The heating system should start within several seconds. The fan may not turn on immediately due to the heating system’s built-in fan delay.
- Place the system switch in the OFF position. The heating system should stop within several seconds.
- Place the system switch in the COOL position.
- Press the button on the keypad until the setpoint temperature is a minimum of 3 degrees lower than the current room temperature.
- The cooling system should start within several seconds. Place the system switch in the OFF position. The cooling system should stop within 90 seconds (dependent on the setting of the Residual Cooling Fan Feature).
- Place the fan switch in the ON position. The system blower should start.
- Place the fan switch in the AUTO position. The system blower should stop.
PROGRAMMING USER SETTINGS
Default Thermostat Settings
Operation Mode | Normal Operating Mode |
---|---|
Room Temperature | 70˚ F (21.0˚ C), to be renewed within5 seconds |
Setpoint Temperature | According to system switch:62˚ F (17.0˚ C) for Heat and |
Off 85˚ F (29.0˚ C) for Cool
Temperature Scale| ˚F or ˚C dependent on switch setting
First Stage Differential| .5˚ F (0.25˚ C)
Second Stage Differential| 2˚ F (1.0˚ C)
Residual Cooling| 60 Seconds
Short Cycle Protection Timer| Reset
Output Relays| Off
Recirculating Fan Timer| Reset with 120 minute off cycle
Keypad Lock| Unlocked
Setting Temperature Differentials
The default settings for the first and second stage differentials and residual
cooling fan delay settings are compatible with most systems and applications.
This is normally set at the time of installation and usually does not require
any modification under normal operating conditions. If you feel that the first
or second stage of your system is turning on too often, or you wish to change
the fan delay settings, follow the instructions below.
NOTE: The first and second stage differential settings are the same for
both the heating and cooling systems.
Setting First Stage Differential
The default setting is .5˚ F (0.25˚ C). The room temperature must change .5˚ F
(0.25˚ C) from the setpoint temperature before the thermostat will initiate
the system in heating or cooling.
-
In normal operating mode, press and hold the button at the same time for 4 seconds. The LCD display will show “SET D1 X˚”, where “X” equals the ˚F / ˚C differential setting. This is the
current first stage differential setting. -
Press the or button to set the first stage differential to your desired setting of .5˚, 1˚, or 2˚ F (0.25˚, .5˚, or 1˚ C).
NOTE: If you do not wish to change the second stage differential setting, you can press the buttons at the same time twice to proceed to the Residual Cooling fan setting–see 4.3. Setting Second Stage Differential The default setting is 2˚ F (1.0˚ C). This means that the room temperature must change 2˚ F (1.0˚ C) in addition to the first stage differential setting before the thermostat will initiate the second stage of the system in heating or cooling. -
Press the and buttons at the same time again and the LCD display will show “SET D2 X˚”, where “X” equals the ˚F / ˚C differential setting. This is the current second-stage differential setting.
-
Press the or button to set the second stage differential to your desired setting of 2˚, 3˚, 4˚, 5˚, or 6˚ F (1.0˚, 1.5˚, 2.0˚, 2.5˚, or 3.0˚ C).
Setting Residual Cooling Fan Feature
The default setting is 60 seconds. During the COOL mode of normal operation,
the fan will stay on for 60 seconds after the cooling system has satisfied the
setpoint temperature and has turned off the compressor. This allows the system
to provide higher efficiency during cooling operation.
- Press the and buttons at the same time again and the LCD display will show “SET FAN XX”, where “XX” equals the fan delay time in seconds during the cooling mode of operation.
- Press the o
- r button to set the residual cooling fan delay to your desired setting of 0 (disabled), 30, 60, or 90 seconds.
- Press the and buttons at the same time again to set the Recirculating Fan Cycle or wait 5 seconds and the thermostat will automatically return to normal operating mode.
Setting the Recirculating Fan Cycle (Also see section 5.3)
The default is 120 minutes.
- The display will show “SET OC XXX”, where XXX is the maximum interval of time (in minutes) that the fan will remain off if the Recirculating Fan Mode is selected.
- Press the or button to change the Recirculating Fan off cycle (120, 60, or 40 minutes).
- Press both the and buttons at the same time again to return to the normal operating mode, or wait 5 seconds for the thermostat to return to the normal mode automatically.
NOTE : To erase all user program settings, gently press the RESET button using a paper clip or a small pencil tip. This will return all thermostat settings to their default values.
OPERATION F FEATURES
- Press and hold the or button. The current setpoint temperature will be displayed in place of the current room temperature, and the indicator SET TEMP will be displayed.
- The display will return to the normal operating mode when the or button is released. Continuing to hold the or button for 3 seconds or longer will allow the user to change the current setpoint temperature (See Changing Set Temperature).
Changing Set Temperature
- Press and hold or button for 3 seconds. The entire display will flash once and the SET TEMP indicator will be flashing. Release the or button and press the or button again as desired to adjust the set temperature.
- The display will return to normal operating mode after 5 seconds.
- The TEMP indicator will be showing in the display indicating that the current temperature shown in the display is the room temperature.
NOTE: Select either Cool or Heat with the system switch to view or change separate cooling or heating setpoints.
Recirculating Fan Mode (see section 4.4)
The Recirculating Fan Mode provides more even temperature distribution and
improves indoor air quality by circulating air through the furnace filtration
system more often. The Recirculating Fan Mode can be selected by moving the
fan switch to the recirculate position ®. If no call for heating or cooling
occurs within the fan off cycle set in section 4.4, the fan will run for 12
minutes. The highest setting, 120 minutes (factory default), will run the fan
least often–10% minimum run time. The lowest setting, 40 minutes, will run the
fan most often–30% minimum run time. During any call for heating or cooling,
fan control operates in the AUTO mode. This feature is available in the HEAT,
OFF, or COOL modes.
Keypad Lockout
To prevent accidental or undesired adjustment of the thermostat set point, the
Keypad Lockout feature disables the operation of the temperature setting keys,
but not the backlight key. In order to enable the
keypad lock, press and hold either the or button together with the backlight
button for 5 seconds. The LOCK icon in the display will flash once per second,
then appear continuously in the display. The keypad is now locked. To unlock
the keypad, press and hold either the or button together with the backlight
key for 1 second. The LOCK icon will disappear from the display, and the
keypad is now unlocked.
Compressor Protection
This thermostat includes an automatic compressor protection feature to avoid
potential damage to the system from short cycling. This thermostat
automatically provides a 5-minute delay after turning off the cooling output
to protect the compressor.
NOTE: The installer can reset the thermostat and bypass the compressor protection features by pressing the RESET button. This will erase all user program settings and should only be used during installation for testing purposes or to reset a thermostat to regain normal operation. This will return all thermostat settings to their default values. The user will have to re- program all of the erased settings.
Resetting Thermostat
The Reset feature allows the user to completely reset the thermostat. To erase
all entered program settings, gently press the RESET button using a paper clip
or a small pencil tip. This will return all thermostat settings to their
default values and register all new manual switch settings.
LED Status Indicator
The LED status indicator located on the front of your thermostat above the
display will notify you of key system information. AUX (Green): This will turn
on when the auxiliary stage of heating or cooling is active.
TROUBLESHOOTING
| |
---|---|---
| SYMPTOM| POTENTIAL SOLUTION
Thermosta t does not turn on heating or cooling system.| Check to see if
OFF is shown in display. This indicates that the system is turned off at
the thermostat. Move the system selector switch to the HEAT or COOL
position. After the compressor short cycle protection 5-minute period expires,
the system should start within a minute.Compressor protection features may be
in effect due to compressor short cycle conditions. See Compressor
Protection section for full explanation of this feature.
Thermostat turns on heating instead of cooling or cooling instead of heating.|
Check thermostat wiring to make sure that the heating and cooling stages are
connected to the correct terminals on the wiring terminal block. See
Installation and Wiring Diagram sections of this manual.
Thermostat turns heating or cooling system on too often or not often enough.|
Increase or decrease first stage temperature differential setting as
appropriate to provide the desired performance level. See Setting
Temperature Differential and Residual Cooling Fan Feature section of
this manual.
Thermostat turns on second (auxiliary) stage of heating or cooling too quickly
or not quickly enough.| Increase or decrease second (auxiliary) stage
temperature differential setting as appropriate to provide the desired
performance level. See Setting Temperature Differential and Residual
Cooling Fan Feature section of this manual.
OFF is shown in thermostat display and heating or cooling system will not
start.| This indicates that the system is turned off at the thermostat. Move
the system selector switch to the HEAT or COOL position. After the
compressor short cycle protection 5-minute period expires the system should
start within several seconds.
| |
---|---|---
| SYMPTOM| POTENTIAL SOLUTION
Thermostat display is blank.| It is possible that AC power is not present at
the thermostat. Check fuse, circuit breaker and thermostat wiring as
appropriate to verify AC power is available.If AC Power is present, call a
professional service technician immediately to verify thermostat and system
performance.
HI is shown in the thermostat display where the room temperature is
normally displayed.| The temperature sensed by the thermostat is higher than
the 90˚ F (32˚ C) upper limit of the thermostats display range.The display
will return to normal after the sensed temperature lowers within the 45˚ to
90˚ F (7˚ to 32˚ C) display range.
Turn on the cooling system or use other methods to lower the temperature accordingly.
This condition could occur from the system being turned off during an exceptionally warm period or upon installation when the thermostat has been stored for a long period of time in a warm vehicle or location prior to being installed. The thermostat is equipped with a mechanical high temperature safety switch that will turn off the thermostat should the temperature exceed 99˚ F (37˚ C).
LO is shown in the thermostat display where the room temperature is normally displayed.| The temperature sensed by the thermostat is lower than the 45˚ F (7˚ C) lower limit of the thermostats display range. The display will return to normal after the sensed temperature rises within the 45˚ to 90˚ F (7˚ to 32˚ C) display range. If the temperature in the controlled space seems to be normal, waitfor the thermostat to acclimate to the correct room temperature. If the room seems to be colder than usual, turn on the heating system to raise the temperature as needed for comfort within the room.
This condition could occur from the system being turned off during a cold weather period or upon installation when the thermostat has been stored for a long period of time in a cold vehicle or location prior to being installed. The thermostat should be allowed to warm up prior to installation to allow proper heating control once installed.
Thermostat will not allow me to program a setpoint temperature higher than 90˚
F (32˚ C).| This is above the normal thermostat temperature setting range of
45˚ to 90˚ F (7˚ to 32˚ C).
Thermostat will not allow me to program a setpoint temperature lower than 45˚
F (7˚ C).| This is below the normal thermostat temperature setting range of
45˚ to 90˚ F (7˚ to 32˚ C).
Fan continues to run all the time whether the system is onor off.| Check that
the fan control switch is in the AUTO position. This will allow the fan
to run only when the heating or cooling system is turned on and running.Check
thermostat wiring to make sure that the fan control wiring is connected to the
correct terminals on the wiring terminal block. See Installation and
Wiring Diagram sections of this manual.
| |
---|---|---
| SYMPTOM| POTENTIAL SOLUTION
Fan continues to run in cooling mode when the system has turned off.| The
Residual Cooling Fan Control Feature can allow up to a 90 second fan delay
after cooling system shutdown for energy efficiency gains. The default setting
is 60 seconds. This can be changed to disable this feature or shorten the time
period if desired. See Setting Residual Cooling Fan Feature section of this
manual.
The room is too warm or too cold.| See Review Set Temperature section of this
manual to verify the current setpoint and make any modifications that are
necessary.
Thermostat will not allow me to change the setpoint.| Keypad is locked. Press
either the or key along with the backlight key to unlock.
Fan runs intermittently or when system is off.| Fan switch is in the
Recirculate Mode ®.
WIRING DIAGRAM
Store this booklet for future reference
Braeburn Systems LLC warrants each new Braeburn thermostat against any defects
that are due to faulty material or workmanship for a period of five years after
the original date of purchase by a professional service technician. This
warranty and our liability do not apply to batteries, nor does it include
damage to merchandise or the thermostat resulting from accident, alteration,
neglect, misuse, improper installation, or any other failure to follow
Braeburn installation and operating instructions. Braeburn Systems LLC agrees
to repair or replace at its option any Braeburn thermostat under warranty
provided it is returned postage prepaid to our warranty facility in a padded
carton within the warranty period, with proof of the original date of purchase
and a brief description of the malfunction. This limited warranty does not
include the cost of removal or re-installation. This warranty gives you
specific legal rights and you may also have other rights that vary from state
to state or province to province. Answers to any questions regarding our
limited warranty may be obtained by writing our corporate offices.
WARRANTY FACILITY: Braeburn Systems LLC Attn: Warranty Department 2215
Cornell Avenue Montgomery, IL 60538 Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance:
www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S. Only)
630-844-1968 (Outside the U.S.)
© 2005 Braeburn Systems LLC Patents Pending All Rights Reserved. Pub. No.
3100-100-006
Braeburn 3100 Non-Programmable Thermostat User Manual