SO-LOW U85 Ultra Low Freezer User Manual

October 30, 2023
SO-LOW

SO LOW U85 Ultra Low Freezer ULTRA LOW FREEZER
U85 / C85 / PH85 / PV85 SERIES
INSTRUCTIONS
USER MANUAL

WARNING: READ BEFORE CONTINUING

To reduce the risk of fire, electric shock or injury to persons using this freezer, read all instructions and follow basic safety precautions before using the unit, including the following:

| not modify the plug provided with the freezer. If it will not fit the outlet, have a proper outlet installed by a qualified electrician.
---|---
| Do not position equipment so it is difficult to disconnect from the power supply freezer must be at least 6″ away from any wall or object on any side.
| While under warranty, do not attempt to repair or replace any part of the freezer for servicing without first contacting the So-Low Service Department.

SYMBOLS AND STARTING INSTRUCTIONS

SAVE THESE INSTRUCTIONS
Explanation

MEANING OF ILLUSTRATED SYMBOLS
ILLUSTRATED SYMBOLS
Various symbols are used in this safety manual in order to use the unit without danger of injury and damage of the unit. Be sure that you understand the warnings and cautions in this manual before operating the unit.|
CAUTION
BLACK WITH YELLOW BACKGROUND
LIGHTNING BOLT
CAUTION, RISK OF ELECTRICAL SHOCK
WARNING
BLACK WITH YELLOW BACKGROUND
EXCLAMATION POINT
CAUTION, REFER TO ACCOMPANYING DOCUMENTS

STARTING INSTRUCTIONS

  1. Move the freezer to an indoor location, and plug the freezer into an appropriate outlet with an adequate power supply. Consult your maintenance department for additional information on the proper electrical configuration for this unit.
  2. Once plugged in, the compressor(s) will start to operate and pull down to the setpoint on the temperature control. The freezers default setpoint is -85°C for cascade units, and -40°C for single stage units.
  3. Allow the freezer to reach the setpoint temperature. Depending on the size of the unit, this may take up to 12 hours.
  4. Product can now be loaded into the freezer for storage.

To prevent overloading the cooling system, product should be loaded gradually, in batches. Allow the temperature to recover to setpoint before the next batch of product is loaded into the unit.

UNIT REQUIREMENTS

Unit Information
PRE-INSTALLATION INFORMATION
RANGE OF ENVIRONMENTAL CONDITIONS
FOR WHICH THIS EQUIPMENT IS DESIGNED

  1. Indoor use.
  2. Altitude up to 2000m.
  3. Ambient temperatures 15°C to 30°C ( 60°F TO 85°F)
  4. Recommended humidity range of 30% to 90%.
  5. Mains supply fluctuations up to -5% to +10% of the nominal voltage.
  6. Transient over-voltages typically present on the mains supply (overvoltage category 11). Pollution degree 1.

WARNING
DURING OPERATION THIS UNIT MUST REMAIN IN UPRIGHT POSITION. DURING TRANSPORATION UNIT MUST NOT BE TIPPED MORE THAN 45° FROM UPRIGHT POSITION.
CAUTION
UNPLUG UNIT AND SWITCH OFF ELECTRICAL BREAKER BEFORE ANY TECHNICAL SERVICE IS PERFORMED.
CAUTION
COVERS ON BACK / SIDE OF FREEZER MAY ONLY BE REMOVED BY AUTHORIZED PERSONNEL. FAILURE TO RE-INSTALL COVER COULD RESULT IN HAZARD.
CAUTION
UNIT MUST BE OPERATED ON A DEDICATED ELECTRICAL LINE. USING A NON-DEDICATED LINE MAY RESULT IN UNIT STARTUP FAILURE.
CAUTION
ONLY PLUG THIS UNIT INTO THE PROPER OUTLET. DO NOT ATTEMPT TO MODIFY PLUG IN ANY WAY. IMPROPER USE OF THE ELECTRICAL PLUG WILL VOID WARRANTY.
WARNING
DO NOT POSITION EQUIPMENT SO IT IS DIFFICULT TO DISCONNECT FROM THE POWER SUPPLY.

PREVENTATIVE MAINTENANCE

FREEZER STORAGE PROCEDURE
The unit can be turned off for storage by unplugging the unit from the wall outlet and/or switching off the electrical breaker in the electrical box.
ATTENTION
RISK OF ELECTRICAL SHOCK USE CAUTION NEAR ELECTRICAL CONNECTIONS
Once the unit is unplugged, the freezer will go into “Power Failure” alarm.
To disable the Power Failure alarm;

  1. Locate the electrical panel on the side of the freezer.
  2. Remove the screws with a Phillips screwdriver, and remove the panel.
  3. Locate the battery (which is clearly marked) in the lower right hand corner.
  4. Disconnect one lead from the battery by removing the connector on the battery.SO LOW U85 Ultra Low Freezer - ATTENTION
  5. When returning the unit to service, complete steps 1-4, but reconnect the unplugged battery in step 4. Then plug the unit into the outlet to restore power.

NOTICE
SEE STARTING INSTRUCTIONS ON PAGE 1 WHEN PUTTING UNIT BACK INTO SERVICE.
ALARM BATTERY REPLACEMENT
NOTICE
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS USING THIS FREEZER, READ ALL INSTRUCTIONS AND FOLLOW BASIC SAFETY PRECAUTIONS.
CAUTION
DISCONNECT THIS UNIT FROM THE POWER SUPPLY BEFORE PERFORMING MAINTENANCE ON THE UNIT.

  1. Unplug freezer from power supply.
  2. Remove cover marked electrical panel located on side of cabinet.
  3. Disconnect wires from battery terminals — Note which color wires were connected to positive/negative. Colors vary depending on when unit was made. Older models used black wire as positive and white as negative. Newer models use red wire as positive and black as negative. See picture for battery location.SO LOW U85 Ultra Low Freezer - POWER SUPPLY
  4. Remove strap holding battery in place.
  5. Replace battery and reconnect wires (see #3)
  6. Test alarm.
  7. Reinstall battery strap and electrical box cover.
  8. Plug freezer back into power supply, and allow up to 24 hours for the new battery to fully charge.

CLEANING PROCEDURE
Wipe down the exterior of the freezer with a soft cloth and/or general spray
type polish. Do not use corrosive cleaners/chemicals on the exterior.
If frost builds up in the chamber, a bucket and ice-scraper can be used to
remove ice. If excessive ice builds up, the unit can be defrosted (see below).
DEFROST PROCEDURE

  1. Remove any product in the freezer, and temporarily store it in a
    back-up freezer or elsewhere.

  2. Unplug the freezer, and fully open the freezer front door/ lid.
    ATTENTION
    FOR UPRIGHT UNITS, IT IS IMPORTANT TO PROTECT THE CONTROL FROM DRIPPING WATER. PLACE A CLOTH OR TOWEL ON THE LEADING EDGE OF THE COOLING CHAMBER ABOVE THE CONTROL TO DEFLECT / ABSORB WATER THAT COULD DRAIN ONTO THE CONTROL.

  3. Air out the freezer, allowing the unit to reach room temperature for at least 12 hours. Using fans to blow air into the unit is recommended.

  4. Take a rag and wipe up all the excess water in the unit (melted frost).

  5. Close the unit, and plug the unit in to activate the start-up process.
    PLEASE CONSULT THE START-UP INSTRUCTIONS ON PAGE 1 FOR UNIT STARTUP

  6. Once the desired temperature is reached, you may slowly begin to add your product back into the unit.

ATTENTION
IT IS RECOMMENDED TO SLOWLY RE-ADD YOUR PRODUCT INTO THE FREEZER TO PREVENT AN EXTREME LOAD ON THE COMPRESSORS, WHICH COULD SHORTEN FREEZER LIFE EXPECTANCY.
CLEANING AIR CONDENSER
Large amounts of dust build-up on the air-cooled condenser can cause excess stress for the refrigeration system. This excess stress may increase the chance of a refrigeration issue and reduce the life expectancy of the refrigeration system.
ATTENTION
IT IS RECOMMENDED TO CLEAN THE CONDENSER AT LEAST ONCE EVERY 90 DAYS TO PREVENT DUST BUILDUP.

  1. Using a Philips Head screwdriver, remove the screws for grill located on front of unit. Once the screws are removed, the front grill can be removed allowing easy access to the air cooled condenser.
    Note: It is recommended to keep the screws in a safe location, so they can be used to re-attach the grill once cleaning is completed.

  2. Use a vacuum cleaner to pull up any dust built up on the condenser fins. The most efficient method of doing this is using a furniture cleaning attachment (if available).
    Note: Cans of compressed air can also be used to blow away dust, however this is not the most  recommended way to clean decondense; as the dust may float through the air and eventually return to clog up the condenser.

  3. Once clean, re-align the front grill and attach it using a screwdriver.

UNIT OPERATION

CHANGING SETPOINT TEMPERATURE
The temperature control is manually adjustable to the desired temperature in 1° C increments within the limits of the control range.
TEMPERATURE SET POINT
The control has two displays;

  1. The upper display ( PV) is the current actual unit temperature.
  2. The lower display ( SV) is the temperature set point.
    The temperature set point has been pre-set at the factory. See page 1 for additional information on factory default setpoint.

CHANGING TEMPERATURE SETPOINT
The temperature set point can be changed by press and HOLD the arrow to raise or the w arrow to lower the temperature set point.
WARNING
CHANGING THE CONTROL PARAMETERS OUTSIDE OF THE MANUFACTURE RECOMMENDED RANGE, COULD CAUSE ISSUES RESULTING IN MECHANICAL FAILURE, AND VOID THE WARRANTY FOR THE UNIT.
CAUTION
THE CONTROLLER IS DESIGNED FOR INDOOR USE ONLY AND IS NOT INTENDED FOR USE IN HAZARDOUS AREAS.
IT SHOULD BE LOCATED/INSTALLED IN SUCH A MANNER AS TO MINIMIZE EFFECTS OF SHOCK, VIBRATION, AND ELECTROMAGNETIC FIELDS, MOTORS, AND TRANSFORMERS.
CAUTION
BEFORE PERFORMING INSTALLATION OR TROUBLESHOOTING PROCEDURES, THE POWER TO THE EQUIPMENT MUST BE DISCONNECTED.
TO MINIMIZE THE POSSIBILITY OF FIRE OR ELECTRICAL SHOCK HAZARDS, DO NOT EXPOSE THIS INSTRUMENT TO RAIN OR EXCESSIVE MOISTURE.

ALARM/ RELAY OPERATION

ALARM SYSTEM
When operating the unit for the first time, the alarm will be disabled until the unit reaches set point, or 8 hours after the unit has been first plugged in.
The alarm will not sound again until the unit goes out of temperature range.
THE FACTORY DEFAULT ALARM RANGE IS ±12°C (20F) FROM SETPOINT.
Note: The freezer contains a back-up battery, which will power the alarm system for approximately 48 hours during a power outage.
ALARM SYSTEM BATTERY REPLACEMENT

  • Rechargeable batteries should be changed approximately every three years with lead acid rechargeable 1.2 Ah minimum, Battery replacement model number PS-1250 or equivalent is factory recommended.

ATTENTION
THE BATTERY DOES NOT POWER THE COOLING SYSTEM.
DRY CONTACT RELAY
The dry contact relay is a terminal strip located on the back of the freezer.
RATING OF THIS CONNECTION:
2A 125 VAC
2A30VDC
RED – NORMALLY CLOSED WHITE – COMMON BLUE – NORMALLY OPEN
WARNING
IF IT IS NECESSARY TO REMOVE METAL COVER SCREEN ON BACK OF FREEZER TO MAKE CONNECTIONS TO ALARM RELAY, COVER MUST BE REPLACED BEFORE FREEZER IS PUT INTO OPERATION

CONTROL PROGRAMMING

CONTROL KEYS & DISPLAYS

SO LOW U85 Ultra Low Freezer - Displays

The FDC-C42 controller is programmed by using four keys on the front panel.
The available function keys are listed in the following table:

TOUCH KEYS FUNCTION DESCRIPTION
Up Key Press and release to increase the current control set point (while

in normal control mode) or to change the value of the selected parameter (while in the Setup Menu).
| Down Key| Press and release to decrease the current control set point (while in normal control mode) or to change the value of the selected parameter (while in the Setup Menu).
| Scroll Key| Press and hold for at least 5 seconds to enter the Setup Menu.
The upper display will show SET and then release the key.
| Reset Key| Press and release to return the display to the home screen (while in User Menu or Setup Menu).

During power-up, the upper display will show PROG and the lower display will show the firmware version for 6 seconds.
DISPLAY/ ERROR/ MODE ICONS

PV Actual Temperature
SV Setpoint Temperature
°C / °F Temperature Scale Indicator
AL1 AL2 AL3 Alarm Indicator
OUT1 Output Indicator
MAN Manual Mode Indicator
COM Communication Indicator
TUNE Auto Tuning Indicator

PROGRAM MENU NAVIGATION

To enter the PROGRAM parameter mode, hold the SCROLL key until the screen changes to ‘SET’, then release. This will take approximately 5 seconds.|
---|---
To access menu parameters; Press and Release the UP and DOWN arrows to adjust the display to the correct menu parameter.|
Once the correct menu parameter is selected, press the SCROLL button to access the desired sub-menu parameter.|
When the desired sub-menu parameter is selected, press the UP and DOWN arrows to adjust the sub-menu parameter values.|
To exit tap RESET key until the temperature/setpoint screen appears.|

**** THE FOLLOWING VALUES WERE FACTORY SET WHEN THIS UNIT WAS SHIPPED. INCORRECT MODIFICATION OF THESE VALUES CAN VOID THE WARRANTY OF THE UNIT.

PARAMETER SUB PARAMETERS DESCRIPTION °F °C
bASE SP1L Lower Setpoint -148 -100
bASE SP1H Upper Setpoint -40 -40
bASE UNIT Temperature Scale T °C
bASE OFTL Calibration
ALRM Al DV Alarm Differential 22 12
ALRM Al HY Alarm Hysteresis 0.1 0.1
OUT 01 HY Output Hysteresis 4. 2.0

CALIBRATION PROCEDURE
Each unit is calibrated at the factory before shipment. The user can still modify the calibration in the field. The basic calibration of the controller is highly stable and set for life. User calibration allows the user to offset the permanent factory calibration in order to:

  • Calibrate the controller to meet a user reference standard.
  • Match the calibration of the controller to that of a particular transducer or sensor input.
  • Calibrate the controller to suit the characteristics of a particular installation.
  • Remove long term drift in the factory set calibration.

TO CALIBRATE THE CONTROLLER FOLLOW THE BELOW STEPS

4| | Hold the SCROLL key until the screen changes to SET, then release. This will take approximately 5 seconds.
---|---|---
2| | Press and Release the UP and DOWN arrows until the value: bASE is displayed.
3| | Press and Release the SCROLL button until the value: OFTL is displayed.
4| | Press the UP and DOWN arrows to adjust the calibration value to the desired value.
5| | Press and hold the SCROLL button for 5 seconds to complete the calibration process. –
6| | Press and hold the RESET button to exit out of the programming menu.

CAUTION
INCORRECT MODIFICATION OF THESE VALUES CAN RESULT IN MALFUNCTION OR UNEXPECTED OPERATION OF THE UNIT, AND MAY VOID THE WARRANTY OF THE UNIT.
ALARM DIFFERENTIAL
The alarm type for relay output 2 (AL1) is pre-configured for deviation band. This means that the alarm deviation set point (A1DV) follows the control set point evenly above and below the main control set point. The alarm hysteresis (A1HY) is safe sided.
The alarm relay’s output will operate in the following manner. For example, the main control set point is -80° (F or C), the alarm deviation set point (A1DV) is 12° and the alarm hysteresis value (A1HY) is 0.1. The alarm relay’s output will be energized when the temperature is outside of the deviation alarm band (below -92° or above -68°). The alarm relay will de­ energize when the temperature falls within the hysteresis band (between -91.9° and -68.1 °).
When the alarm relay’s output is energized, the alarm output status indicator (labeled AL1 on the front panel) will be illuminated. To change the alarm set point and hysteresis values, enter the Setup menu and access the alarm parameters as follows:

1| | Hold the SCROLL key until the screen changes to SET, then release. This will take approximately 5 seconds.
---|---|---
2| | Press and Release the UP and DOWN arrows until the value: OUT is displayed.
3| | Press and Release the SCROLL button until the value: A1HY is displayed.
4| | Press the UP and DOWN arrows to adjust the value to the desired value.
5| | Press and Release the SCROLL button until the value: A1DV is displayed.
6| | Press the UP and DOWN arrows to adjust the value to the desired value.
7| | Press and hold the RESET button to exit out of the programming menu.

CONTROL HYSTERESIS
The control type for relay output 1 is pre-configured for cooling (direct action). The control hysteresis (prompt O1HY) is safe-sided. The control relay’s output will operate in the following manner. For example, the set point is -80° (F or C), and the control  hysteresis value is 2.0. The control relay’s output will be energized until the temperature reached -82° and then de-energize. When the temperature rises to -80° or above, the control relay’s output is energized. When the control relay’s output is energized, the control output status indicator (labeled OUT1 on the front panel) will be illuminated. To change the control hysteresis, enter the Setup menu and access the output parameters as follows:

1| | Hold the SCROLL key until the screen changes to SET, then release. This will take approximately 5 seconds.
---|---|---
2| | Press and Release the UP and DOWN arrows until the value:ALRM is displayed.
3| | Press and Release the SCROLL button until the value: 01HY is displayed.
4| | Press the UP and DOWN arrows to adjust the value to the desired value.
5| | Press and hold the RESET button to exit out of the programming menu.

POWER STATUS ALARM INDICATORS

The FDC-C42 events inputs 1 and 2 and alarm outputs 2 and 3 are pre-configured to act as power supply status alarms. Event input 1 and alarm output 2 (AL2) are utilized to indicate a power failure. Under normal operation, event input 1 will be activated indicating power is present. When main power is lost, event input 1 will deactivate, and in turn cause alarm 2 relay output to energize. When the alarm relay’s output is energized, the alarm output status indicator (labeled AL2 on the front panel) will be illuminated. Event input 2 and alarm output 2 (AL3) are utilized to indicate low battery. Under normal operation, event input 2 will be deactivated. When the battery is low, event input 2 will be activated and in turn cause alarm 3 relay output to energize. When the alarm relay’s output is energized, the alarm output status indicator (labeled AL3 on the front panel) will be illuminated.

FREQUENTLY ASKED QUESITONS COMMON QUESTIONS

Q: When should I defrost my unit?

- A: Units should be defrosted when ice accumulation reaches approximately 1/2 inch thick. Ice acts like an insulator and has to work harder to reach the same temperature.

Q: Is this unit self-defrosting?

- A: No, this unit is a manual defrost unit.

Q: Should I leave my freezer operating when I am not using it?

- A: This unit is designed to operate continuously. Leaving the refrigeration system in operation, (even if not in use) may extend the life of the freezer, and reduce the chance of refrigeration issues that may occur if the freezer is not in operation for long periods of time.

Q: What ambient conditions is this unit designed for?

- A: This unit is designed for: • Indoor use • Altitude up to 2000m. • Temperatures 15°C to 32°C ( 60°F TO 85°F ) • Recommended humidity range of 30% to 90%.

Q: What electrical conditions is this unit designed for?

- A: This unit is designed for: • Mains supply fluctuations up to -5% to +10% of the nominal voltage. Consult the serial tag for nominal voltage. • Transient overvoltage typically present on the mains supply (overvoltage category II). Pollution degree 1.

Q: Does my unit require a dedicated electrical line?

- A: Yes, this unit requires a dedicated electrical line. Please consult the labels on your unit for specific electrical requirements.

Q: Will the backup battery keep my unit cool during power failure?

- A: NO, the backup battery only powers the alarm during power failure. It will not power the refrigeration system, and will not keep the unit cooling during power outages.

Q: Will the freezer start up after a power outage?

- A: Yes, the freezer will automatically re-start when power is restored. The overall restart process will begin in stages to prevent system overloads; and may take up to minutes after re-start before cooling resumes.

REPLACEMENT PARTS LIST

COMPRESSOR MODEL| HP| VOLTAGE| HERTZ| PHASE| PART if
---|---|---|---|---|---
TECUMSEH AJB2433ZXA| 1| 115| 50/60| 1| AJB24-115
TECUMSEH AJB2433ZXD| 1| 208/220/230| 50/60| 1| AJB24-208
EMBRACO FFI12HBX| | 115| 50/60| 1| FF12-115
DANFOSS SC15FTX| | 115| 50/60| 1| SC15-115
DAN FOSS SC18FTX| | 208/220/230| 50/60| 1| SC15-208
TEMPERATURE CONTROL PARTS| PART #
---|---
FDC C42| FDC-C42-VOLTAGE
FDC nCOMPASS| nCOMPASS
CASCADE ELECTRICAL PARTS| PART #
---|---
Heater Harness No. H-200| 217-VOLTAGE
Refrigeration Switch No. 2X464| TOGGLE
Condenser Fan Motor No. GE-5411 – 115/60/1| 500-115
Condenser Fan Motor No. GE-5421 – 230/50-60/1| 500-VOLTAGE
Electrical Cord No. 8-3 (Please Specify Voltage)| PWRCRD-VOLTAGE
Control Board No. CECB2TUV (Please Specify Voltage)| 231-VOLTAGE
REFRIGERATION HIGH STAGE PARTS| PART #
---|---
Air Cooled Condenser No. 3CZ0602B| 254
Drier No. C-053-S| 256H
Capillary Tube| HS-17, HS-20
Oil Separator, Temprite Series 900 (If Applicable)| 900
REFRIGERATION LOW STAGE PARTS| PART #
---|---
Pressure Control No. 20PS01-0039| 259
Receiver Condenser| RCN-LS
Drier No. CO-52S-S| 256L
Capillary Tube| LS-28, LS-31
Oil Separator, Temprite Series 900 (If Applicable)| 900
HARDWARE PARTS| PART #
---|---
Latch No. METL-L1-99| REX37L1-3
Chest Hinge| 59-928M
Upright Hinge No. Polar 109-LH| 59-928U
Cabinet Gasket| NX504B1
Lid or Door Gasket| PSOS
Grill No. 650H| 356F, 356S
Sub-Lids (Must have Model Number)| SL-MODEL NUMBER
Inner Door (Must have Model & Serial Number)| 357-MODEL NUMBER-SERIAL NUMBER
Clips & Rollers for Inner Doors (Quantity 10 minimum)| 405
Shelves for Freezer (Must have Model Number)| 4015-MODEL NUMBER

TECHNICAL SUPPORT

TECHNICAL ASSISTANCE
IN CASE OF REQUEST FOR REPAIR
If failure occurs, stop operation of unit, and turn OFF the breaker power switch located in the electrical panel box, and unplug the power plug.
WARNING
IF FAILURE OCCURS AND UNIT IS STILL UNDER WARRANTY, DO NOT ATTEMPT TO MAKE ANY REPAIR MODIFICATIONS TO THE UNIT BEFORE CONTACTING THE SO-LOW SERVICE DEPARTMENT, AS THIS MAY RESULT IN WARRANTY BEING VOIDED.
< CHECK FOLLOWING ITEMS BEFORE CALLING OR EMAILING
Model Number of Product
◆ Serial Number of Product
◆ Issue (as detailed as possible)
So-Low Environmental Equipment Company 10310 Spartan Drive
Cincinnati, OH 45215-1221
Tel: 513-772-9410
http://www.so-low.com
For customer service:
Email: sales@so-low.com
For parts replacement:
Email: parts@so-low.com
For technical support:
Email: service@so-low.com

MAINTENANCE CHECKLIST

IT IS RECOMMENDED TO COMPLETE CHECKLIST EVERY 30 DAYS
♦ MODEL NUMBER OF PRODUCT
♦ SERIAL NUMBER OF PRODUCT
Checked that freezer is operating at the correct setpoint temperature.
Checked operation of condenser fans, and cleaned air cooled condenser
Confirmed unit is at least 6 inches away from walls, or obstacles, on all sides to allow for sufficient air flow.
Confirmed ambient room temperature is within range acceptable ranges. Recommended room temperature range is 15°C to 26°C ( 60°F TO 80°F )
♦ AMBIENT ROOM TEMPERATURE IS: Checked operation of alarm system on unit.
Note: Alarm can be simulated by temporarily raising setpoint out of range. Checked temperature recorders for proper operation (If applicable).
Note: If there are any deviations observed, further diagnosing may be required.
Check operation of CO2 or LN2 backup system. (If applicable)
ITEMS BELOW MUST BE CHECKED BY YOUR IN-HOUSE TECHNICAL PROFESSIONAL USE CAUTION WHEN WORKING AROUND ELECTRICAL CIRCUITS
Checked AMP draw of unit when compressors stabilize. Checked incoming voltage and voltage drop when compressors start up.
♦ NOTES

115 VOLT ELECTRICAL DIAGRAM

NOTE: DIAGRAM ONLY APPLIES TO 115 VOLTS, AND MAY NOT APPLY TO YOUR SPECIFIC UNIT.

SO LOW U85 Ultra Low Freezer - Digram

208 I 230 VOLT ELECTRICAL DIAGRAM

NOTE: DIAGRAM ONLY APPLIES TO 208 or 230 VOLTS, AND MAY NOT APPLY TO YOUR SPECIFIC UNIT.

SO LOW U85 Ultra Low Freezer - Digram 1

ALARM DIAGRAM

Connection to the alarm relays and audible alarm require external control relays that are not part of the control assembly. One relay is utilized to provide remote contacts for customer connection for remote alarm indication (shown as CR1 in the following diagram) and is optional. The other relay is utilized for the audible alarm silence (shown as CR2 in the following diagram) which is required.

SO LOW U85 Ultra Low Freezer - Digram 2

Note that alarm 3 (low battery) is utilized for indication only. When an alarm relay is energized, the corresponding alarm indicator, AL1 for alarm 1 (temperature), AL2 for alarm 2 (power failure) or AL3 for alarm 3 (low battery), will be illuminated on the upper left of the C42 LCD display. When either a high/low temperature or power failure alarm activates, the audible alarm will sound as power from the alarm contact will pass through the normally closed contact of relay CR2. When the silence button is pressed,
the coil of relay CR2 will be energized. Since the normally open contact of CR2 will then close, power will pass through the relay contact and will in turn hold the relay coil energized even after the push-button is released.
This will hold the normally closed contact of the relay open, removing power from the audible alarm so that it will no longer sound. Once both alarm conditions are no longer present, both alarm 1 and alarm 2 outputs of the C42 will be de-energized. This will in turn remove power from the coil of relay CR2 causing it to de-energize. This will then ensure that upon the next activation of either the temperature or power failure alarm output, power will again pass to the audible alarm causing it to sound until the alarm
condition clears or the operator presses the silence button.

REFRIGERATION FLOW DIAGRAM

SO LOW U85 Ultra Low Freezer - Digram 3

So-Low Environmental Equipment Company
10310 Spartan Drive
Cincinnati, OH 45215-1221
Tel: 513-772-9410http://www.so-low.com
For customer service: “
Email: sales@so-low.com
For parts replacement:
Email:partsaso-low.com
For technical support:
Email:service@so-low.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals