Superior Life PQL-54893 LED Pir Outdoor Sensor Instruction Manual
- June 4, 2024
- Superior Life
Table of Contents
LED PIR OUTDOOR SENSOR • 54893
INSTALL INSTRUCTIONS
PLEASE FIND A QUALIFIED ELECTRICIAN FOR INSTALLATION. Please read the
instructions before you install the sensor and use the luminaire.
GENERAL: ALL ELECTRICAL CONNECTIONS MUST BE IN ACCORDANCE WITH LOCAL AND
NATIONAL ELECTRICAL CODES (N.E.C.) STANDARDS. IF YOU ARE
UNFAMILIAR WITH PROPER ELECTRICAL WIRING CONNECTIONS OBTAIN THE SERVICES OF A
QUALIFIED ELECTRICIAN. REMOVE FROM THE BOX AND MAKE SURE THAT NO PARTS ARE
MISSING.
WARNING – Risk of fire or electric shock. Sensor installation requires
knowledge of luminaire electrical systems. If not qualified, do not attempt
installation.
Contact a qualified electrician.
WARNING – Risk of fire or electric shock. Install this sensor only in
luminaires that have the construction features and dimensions shown in the
photographs
and/or drawings and where the input rating of the sensor does not exceed the
input rating of the luminaire.
WARNING – To prevent wiring damage or abrasion, do not expose wiring to
the edges of sheet metal or other sharp objects. Risk of Electric Shock:
Disconnect power or circuit breaker before installing or servicing. Do not
make or alter any open holes in an enclosure of wiring or electrical
components during installation.
WARNING
NOTE: Warm-up time is 40 seconds. After the sensor connects to input
power for the first time, the light will stay on for 40 seconds, then operate
per sensor settings.
NOTE: Once powering up the device, the sensor will use the factory
default settings to operate. Factory Default Settings: Sensitivity set to
100%. Hold on time 5 min. Daylight sensor at. Dimming level at 30%. Dimming
time at 60 minutes.
NOTE: RC-100 remote (sold separately) required to make adjustments to any
sensor settings. The LED light will turn on/off as confirmation of the change.
WARNING DISCONNECT POWER BEFORE INSTALLING OR SERVICING.
SENSOR SPECIFICATIONS
Power Supply| 100-347V – Single Phase – 60Hz
208/230/480V – Phase-to-Phase – 60Hz
---|---
Maximum Load| 100-120V – 800W Tungsten
100-120V – 800W Electronic Ballast/ LED Driver
230-240V – 300W Electronic Ballast/ LED Driver
277V -1200W Electronic Ballast/ LED Driver
347V -1200W Electronic Ballast/ LED Driver
480V – 480W Electronic Ballast/ LED Driver
HF System| 5,8GHz CW
Dim Control Output| 0-10VDC 50mA
Detection Radius| Max, 26ft / 8 Meters – 360°
Mounting Height| Max 40ft /12 Meters
Remote Range (optional)| 50ft / 15 Meters Indoor, No Backlight
Time Setting| 10 sec, – 60 min. (Adjustable)
Light Control| 10-500 LUX (Adjustable)
Temperature| -40° ∼ 158°F (-40° ∼70°C)
WIRING DIAGRAM
SENSOR COVERAGE
PREMIUM QUALITY LIGHTING®
• www.PQLighting.com
© P.Q.L., Inc. • 2285 Ward Avenue
• Simi Valley, CA 93065 • 800-323-8107
Specifications subject to change without notice. Photos and line drawings may
not be to scale and are for general reference only.