Scigiene RFP-0254-2 Wireless AC Current Meter User Guide

June 10, 2024
Scigiene

Scigiene RFP-0254-2 Wireless AC Current Meter User Guide
Scigiene RFP-0254-2 Wireless AC Current Meter

ABOUT THE WIRELESS AC CURRENT METER

The GEN 2 Wireless AC Current Meter measures the RMS current of an alternating current (AC) system using a current transformer (CT) that wraps around the hot wire of a two wire (hot, common, ground(optional)) power system. The sensor reports Minimum RMS current, maximum RMS current, average RMS current, and amp hours to the Scigiene Premiere system. The Scigiene Premiere system is capable of generating watt hour or kilowatt hour readings as well.

  • Measures amp hours, max RMS current, min RMS current, and average RMS current
  • Two different current transducers available:
    • Low Current: 0–20 amp
    • Medium Current: 0–150 amp
    • High Current: 0–500 amp
  • Capable of generating watt hour or kilowatt hour readings using Scigiene Premiere Data logging for accumulated amp hour readings · Can notify based on current levels or changes in current levels · Simple and safe installation of current/power measurement hardware, no rewiring
  • required.

To measure current, clip the CT around only a single wire of the AC system (clipping around a hot and neutral wire at the same time will result in 0 current readings). After the sensor powers on and connects to the gateway it will begin taking measurements based on the averaging interval (5 seconds default). It will report data to Scigiene Premiere every heartbeat or if the current goes outside of the aware thresholds set in Scigiene Premiere. The sensor reports amp hours, max RMS current, min RMS current, and average RMS current. Scigiene Premiere can also generate watt hour or kilowatt hour readings if a default RMS voltage is set in Scigiene Premiere.

GEN 2 WIRELESS AC CURRENT METER FEATURES

  • Wireless range of 1,200+ feet through 12+ walls * Frequency-Hopping Spread Spectrum (FHSS) Interference immunity · Power management for longer battery life **
  • Encrypt-RFO Security (Diffie-Hellman Key Exchange + AES-128 CBC for sensor data messages)
  • Onboard data memory stores up to hundreds of readings per sensor:
  • 10-minute heartbeats = 22 days
  • 2-hour heartbeats = 266 days Over-the-air updates (future proof)
  • Free Scigiene Premiere basic online wireless sensor monitoring and notification system to configure sensors, view data and set alerts via SMS text and email.

*Actual range may vary depending on environment.

“Battery life is determined by sensor reporting frequency and other variables. Other power options are also available.

EXAMPLE APPLICATIONS

  • Current Monitoring
  • Current Usage
  • Amperage Monitoring
  • Amp Hour Meter

ORDER OF OPERATIONS

It is important to understand the order of operations for activating your sensor. If performed out of sequence, your sensor may have trouble communicating with Scigiene Premiere. Please perform the steps below in the order indicated to make sure you are performing your set-up correctly.

  1. Create Scigiene Premiere Account (If new user).

  2. Register all sensors and gateways to a network in Scigiene Premiere.
    Sensors can only communicate with gateways on the same Scigiene Premiere network.

  3. Connect/power on gateway and wait till it checks into Scigiene Premiere.

  4. Power on sensor and verify it checks into Scigiene Premiere. We recommend powering the sensor on near the gateway then moving to the installation location, checking signal strength along the way.

  5. Configure sensor for use (This can be done at any point after step 2)

  6. Install sensor in final location.

Note: For information on setting up Scigiene Premiere and the gateway refer to the Scigiene Premiere User Guide and the gateways user guide.

SETUP AND INSTALLATION

If this is your first time using the Scigiene Premiere online portal, you will need to create a new account. If you have already created an account, start by logging in. For instructions on how to register and setup your Scigiene Premiere account, please consult the Scigiene Premiere User Guide.

STEP 1: ADD DEVICE

  1. Add the sensor on Scigiene Premiere.
    Add the sensor to your account by choosing Sensors in the main menu. Navigate to the Add Sensor button.
    Desktop
    Sensor Button
    Mobile
    Sensor Button

  2. Find the device ID. See Figure 1.
    The Device ID (ID) and Security Code (SC) are necessary to add a sensor. These can both be located on the label on the side of your device.
    Instructions

  3. Adding your device. See Figure 2.
    You will need to enter the Device ID and the Security Code from your Sensor in the corresponding text boxes. Use the camera on your smartphone to scan the QR code on your device. If you do not have a camera on your phone, or the system is not accepting the QR code, you may enter the Device ID and Security Code manually.
    Adding Devices
    The Device ID is a unique number located on each device label.
    Next, you’ll be asked to enter the Security Code from your device. A security code consists of letters and must be entered in upper case (no numbers). It can also be found on the barcode label of your device.

    • When completed, select the Add Device button.

STEP 2: SETUP

  • * Select your use case. **See Figure 3.  

    ** Unlike most sensors, choosing a use case in Step 2 of adding this sensor does not give you the option to customize your settings. These will need to be adjusted in the settings tab for your device. See page 9 for instructions.
    Select the Skip button when completed.
    Setup Instructions

STEP 3: VALIDATION

Check your signal. See Figure 4.
The validation checklist will help you ensure your sensor is communicating with the gateway properly and you have a strong signal.

Checkpoint 4 will only complete when your sensor achieves a solid connection to the gateway. Once you insert the batteries (or flip the switch on an industrial sensor) the sensor will communicate with the gateway every 30 seconds for the first few minutes.
Select the Save button when completed.
VALIDATION

STEP 4: ACTIONS
Choose your actions. See Figure 5.
Actions are the alerts that will be sent to your phone or email in the event of an emergency. Low battery life and device inactivity are two of the most common actions to have enabled on your device. See page 12 for how to set actions for your sensor.

Select the Done button when completed.
ACTIONS

SETTING UP YOUR AC CURRENT METER

When you are finished adding the sensor to your account, the next step is to insert the battery. The type of battery you use will depend on the category of your sensor. GEN 2 Wireless AC Current Meter will either be powered by commercial AA, or an industrial battery.

INSTALLING BATTERIES
GEN 2 commercial current meters are powered by AA batteries. Industrial sensors need a 3.6V Lithium battery supplied from Scigiene or another industrial battery supplier. Scigiene encourages customers to recycle all old batteries.

AA Batteries
The standard version of this current meter is powered by two replaceable 1.5 V AA sized batteries (included with purchase). The typical battery life is up to 10 years.

This current meter is also available with a line power option. The line powered version of this meter has a barrel power connector allowing it to be powered by a standard 3.0—3.6 V power supply. The line powered version also uses two standard 1.5 V AA batteries as backup for uninterrupted operation in the event of line power outage.
INSTALLING BATTERIES

Power options must be selected at time of purchase, as the internal hardware of the meter must be changed to support the selected power requirements.

Place batteries in the device by first taking the meter and sliding the battery door open. Insert fresh AA batteries in the carriage, then shut the battery door.

Complete the process by opening up Scigiene Premiere and selecting Sensors from the main navigation menu. Verify that Scigiene Premiere is showing the meter has a full battery level.
INSTALLING BATTERIES

Industrial Batteries

3.6V Lithium batteries for the Industrial Wireless Amp AC Current Meter is supplied by Scigiene. The GEN 2 battery life for the Industrial battery is up to 7 years. TheIndustrial meter doesnot need tohavebatteries installed. The batteries are already in the meters when they are shipped.

OpenScigiene Premiere and select Sensors from the main menu. Verify that Scigiene Premiere is showing the sensor has a full battery level.
Industrial Batteries

In order for the meter to function properly, you will need to attach the included antenna.
Simply screw the antenna onto the barrel connector on the top of the device. Make sure to snug the antenna connection, but do not overtighten. When placing the meter, make sure to mount the sensor with the antenna oriented straight up (vertical) to ensure the best wireless radio signal.
Since the electronics are sealed with in the meter housing, we have added an “On/Off’  switch to the unit for your convenience. If you are not using the meter, simply leave the button in the off position to preserve battery life. If the meter needs to be reset for any reason, you can simply cycle the power by turning the switch to the “Off’ position and waiting 30 seconds before powering back on.

In order for the meter to function properly, you will need to attach the included antenna. Simply screw the antenna onto the barrel connector on the top of the device. Make sure to snug the antenna connection, but do not over tighten. When placing the meter, make sure to mount the sensor with the antenna oriented straight up (vertical) to ensure the best wireless radio signal.

Since the electronics are sealed with in the meter housing, we have added an “On/Off’ switch to the unit  for your convenience. If you are not using the meter, simply leave the button in the off position to preserve battery life. If the meter needs to be reset for any reason, you can simply cycle the power by turning the switch to the “Off’ position and waiting 30 seconds before powering back on.

ANTENNA ORIENTATION
In order to get the best performance out of your GEN 2Wireless Sensors, it is important to note proper antenna orientation and sensor positioning. Antennas should all be oriented in the same direction, pointing vertically from the sensor. If the sensor is mounted flat on its back on a horizontal surface, you should bend the antenna as close to the sensor housing
aspossiblegivingyouthemostamountofantennapointingvertical.Youshouldmakethe antenna wire as straight as possible, avoiding any kinks and curving of the wire. Sensors must be at least 3 ft. away from other sensors and the wireless gateway to function.
ANTENNA ORIENTATION

SENSOR OVERVIEW IN SCIGIENE PREMIERE

Select Sensors from the main navigation menu on Scigiene Premiere to access the sensor overview page and begin making adjustments to your Current Meter.

MENU SYSTEM
MENU SYSTEM

A. Details – Displays a graph of recent sensor data
B. History – List of all past heartbeats and readings
C. Actions – List of all actions attached to this sensor
D. Settings – Editable levels for your sensor
E. Calibrate – Set your sensor to read more accurately
F. Scale – Change the scale of readings for your sensor

Directly under the tab bar is an overview of your sensor. This allows you to see the signal strength and the battery level of the selected sensor. A colored dot in the left corner of the sensor icon denotes its status.

  • Green indicates the sensor is checking in and within user-defined safe parameters.

  • Red indicates the sensor has met or exceeded a user-defined threshold or triggered event.
    Gray indicates that no sensor readings are being recorded, rendering the sensor inactive.

  • Yellow indicates that the sensor reading is out of date, due to perhaps a missed heartbeat check-in.

Details View

The Details View will be the first page you see upon selecting which sensor you would like to modify.
Details View

A. The sensor overview section will be above every page. This will consistently display the present reading, signal strength, battery level, and status.
B. The Recent Readings section below the chart shows your most recent data received by the sensor.
C. This graph charts how the sensor fluctuates throughout a set date range. To change the date range displayed in the graph, navigate up to the top of the Readings Chart section on the right-hand corner to change the from and/or to date.

Readings View

Selecting the Readings Tab within the tab bar allows you to view the sensor’s data history as time stamped data.

  • On the far right of the Sensor History Data is a cloud icon. ( ) Selecting this icon will export an Excel file for your sensor into your download folder.

Note: Make sure you have the date range for the data you need input in the “From” and “To” text boxes. This will be the previous day by default. Only the first 2,500 entries in the selected date range will be exported.

The data file will have the following fields:

MessagelD: Unique identifier of the message in our database.
Sensor ID: If multiple sensors are exported, you can distinguish between the sensors using this number — even if the names are the same.
Sensor Name: The name you have given the sensor.
Date: The date the message was transmitted from the sensor.
Value: Data presented with transformations applied, but without additional labels.
Formatted Value: Data transformed and presented as it is shown in the monitoring portal.
Raw Data: Raw data as it is stored from the sensor.
Sensor State: Binary field represented as an integer containing information about the state of the sensor when the message was transmitted. (See “Sensor State” explained below.)
Alert Sent: Boolean indicating if this reading triggered a notification to be sent from the system.

Sensor State
The value presented here is generated from a single byte of stored data.
A byte consists of 8 bits of data that we read as Boolean (True (1) / False (0)) fields.

When broken into individual bits, the State byte contains the following information: aaaabcde
STS: This value is specific to the sensor profile and is often used to indicate error states and other sensor conditions.
UNUSED: This sensor does not use these bits.
AWARE: Sensors become aware when critical sensor specific conditions are met. Going aware can cause the sensor to trigger and report before the heartbeat and cause the gateway to forward the data to the server immediately resulting in near immediate transmission of the data.
TEST: This bit is active when the sensor is first powered on or reset and remains active for the first 9 messages when using default configurations.

STS Specific Codes:
0 = No problems, sensor is functioning normally.
1 = Open circuit detected in lead.
2 = Short circuit detected in lead.
3 = Range error. Temperature is reading outside of -40 F and 257 F (-40 C and 125 C).

If the user has calibrated the sensor, the Calibrate Active field is set to False (0) and the sensor is operating inside the Min and Max Thresholds, the bits look like 00000000, this is represented as 0.

If the sensor is using factory calibrations and it is outside the threshold, the bit values are 00010010 and are represented as 18(16+2 because both the bit in the 16 value is set and the bit in the 2 value is set).

Settings View

To edit the operational settings for a sensor, choose the Sensor option in the main navigation menu and then select the Settings Tab to access the configuration page. See Figure 12.
Settings View

  • A. Sensor Name is a unique name you give the meter to easily identify it in a list and in any notifications.
  • B. The Heartbeat Interval is how often the sensor communicates with the gateway when NOT in an Aware State.
  • C. Aware State Heartbeat is how often the meter communicates with the gateway while in an Aware State.
  • D. Minimum Threshold is the low amp threshold. Assessments below this value will cause the sensor to enter the Aware State and report data if not already in the Aware State.
  • E. Maximum Threshold is the high amp threshold. Assessments above this value will cause the sensor to enter the Aware State and report data if not already in the Aware State.
  • F. The Aware State Buffer is a buffer to prevent the sensor from bouncing between Standard Operation and Aware State when the assessments are very close to a threshold. The sensor must read within the threshold(s) by this value to exit the Aware State.
  • G. Averaging Interval is how often the sensor makes an assessment within the sensor’s heartbeat. The measurements taken on this interval will be averaged together to calculate the Average Current reading  the sensor produces.
  • H. Accumulate, when On, causes the Ah readings to accumulate from one data point to the next. When Off the Ah count will reset to 0 after the data is sent to the gateway.
  • I. Show Full Data Value, when On, will make the software show all the data the sensor reports (AmpHours, Average Current, Max Current, Min Current). When Off the software only reports AmpHours. The sensor still reports the same data to Scigiene Premiere, this only changes how the data is displayed.
  • J. In small sensor networks the sensors can be set to synchronize their communications. The default setting off allows the sensors to randomize their communications therefore maximizing communication robustness. Setting this will synchronize the communication of the sensors.
  • K. Failed transmissions before link mode is the number of transmissions the sensor sends without response from a gateway before it goes to battery saving link mode. In link mode, The sensor will scan and Join a gateway at the following intervals: @ 0 Seconds, 3 sec, 6 sec, 9 sec, 15 sec, 30 sec, 1 min, 2 min, 5 min, 15 min, 30 min, and 60 min, then 60 minutes thereafter. While attempting to link, the sensor will continue to measure. A lower number will allow sensors to find new gateways with fewer missed readings. High numbers will enable the sensor to remain with its current gateway in a noisy RF environment better.

Finish by selecting the Save button.

Calibrate View
If a sensor type has readings that need to be reset, the “Calibrate” tab will be available for selection in the sensor tab bar.
To calibrate a sensor, ensure that the environment of the sensor and other calibration devices are stable.

Enter the actual (accurate) reading from the calibration device into the text field. If you need to change the unit of measurement you can do that here. Press Calibrate.
Calibrate View

To ensure that the calibration command is received prior to the sensors next check-in, press the control button on the back of the gateway, once, to force communication (Cellular and Ethernet gateways).

After pressing the “Calibrate” button and choosing the gateway button, the server will send the command to calibrate the specified sensor to the gateway. When the sensor checks-in, it will send the pre-calibration reading to the gateway, then receive the calibration command and update its configuration. When the process is completed, it will send a “Calibration Successful” message. The server will display the sensor’s last pre-calibrated reading for this check-in, then all future readings from the sensor will be based on the new calibration setting. It is important to note that after calibrating the sensor, the sensor reading returned to the server is based on pre-calibration settings. The new calibration settings will take effect on the next sensor heartbeat.

Note: Be sure to select the Save button anytime you make a change to any of the sensor parameters. All changes made to the sensor settings will be downloaded to the sensor on the next sensor heartbeat (check-in). Once a change has been made and saved, you will not be able to edit that sensor’s configuration again until it has downloaded the new setting.

Creating a Calibration Certificate

Creating a sensor calibration certificate will mask the calibration tab from those who should not have permissions to adjust these settings. Permissions for self-certifying a calibration must be enabled in user permissions. Directly below the calibrate button is the selection to “Create Calibration Certificate.
Calibration Certificate

A. The Calibration Facility Field will be filled. Select the dropdown menu to change your facility.
B. The “Certificate Valid Until” field must be set one day after the date contained in the “Date Certified” field.
C. “Calibration Number” and “Calibration Type” are unique values to your certificate.
D. If necessary, you can reset the heartbeat interval here to 10 minutes, 60 minutes, or 120 minutes. By default, this will be set to no change.
E. Choose the “Save” button before moving on.

When the new certificate is accepted, the Calibration tab will change to a Certificate tab.
Instructions

You will still be able to edit the certificate by choosing the Certificate Tab and navigating down to “Edit Calibration Certificate.”

The tab will revert back to “Calibrate” after the period for the certificate ends.

Scale View
To change the unit of measurement for Amp Hours and Volts, choose the scale option in the tab bar.

Choose the text box to trigger a pop-up window allowing you to change the scale. Select the scale you prefer and push “Set.”

Press the “Save” button to complete your adjustment. Changing units here will also change units on the sensor physical display. Units changed locally on the sensor itself will not be change this setting in Scigiene Premiere.
Scale View

ACTIONS OVERVIEW

Device notifications can be created, deleted, and edited by selecting the Actions Tab in the tab bar.

You can toggle the Action Trigger on or off by selecting the switch under Current Action Triggers. See Figure 17.
ACTIONS OVERVIEW

CREATING AN ACTION

  • Actions are triggers or alarms set to notify you when a sensor reading identifies that immediate attention is needed. Types of actions include sensor readings, device inactivity, and scheduled data. Any one of these can be set to send a notification or trigger an action in the system.

Choose Actions in the main navigation menu.
CREATING AN ACTION

  • A list of previously created actions will display on the screen. From here, you have the ability to filter, refresh, and add new actions to the list.
    Note: If this is your first time adding an action, the screen will be blank.

From the Actions page, tap Add Action in the left hand corner.
Instructions

Step 1: What triggers your action?
The drop-down menu will have the following options for Action Types (See Figure 20):

  • Sensor Reading: Set actions based on activity or reading.

  • Device Inactivity: Actions when the device doesn’t communicate for an extended period of time.

  • Advanced: Actions based on advanced rules, such as comparing past data points with current ones.

  • Scheduled: These actions are performed at a time set basis.
    Triggers your action

  • Select Sensor Reading from the drop-down menu.

  • A second drop-down menu will appear. From here, you will be able to see a list of the different type of sensors registered to your account. Choose Current Meter – 20A, Current Meter – 150 A, or Current Meter – 500 A in the drop-down menu.

  • Next, you will be asked to input the trigger settings for AmpHours, AvgCurrent, Max Current, and MinCurrent. You have the option of setting this trigger to detect greater than or less than a desired reading.
    Triggers your action

Press the Save button.

Step 2: Actions

  • Press the Add Action button under the information header, available action types will then be presented in a select list.
  • Notification Action: Specify account users to receive notification when this event triggers.
  • System Action: Assign actions for the system to process when this event triggers.
  • Choose Notification Action from the notification list.

A. Input the subject for the notification. See Figure 22.
Actions
B. Customize the message body for the notification. See Figure 22.
C. Recipient list identifies who will receive the notification. See Figure 23.
Actions

  • Select the icon next to a user to specify how they will be notified.
  • Choose if you want notifications sent immediately, when triggered, or if you want a delay before sending and press Set.
  • A green icon indicates that the users that will receive the notifications. If a delay has been selected, the delay time will display beside the icon.

Select System Action from the Add Action list. See Figure 24.
System Action

Activate: Enable an action trigger.
Deactivate: Disable an action trigger.

Step 3: Action Name and Devices

  • By default, the sensor(s) will not be assigned to the action conditions you’ve just set. To assign a sensor, find the device(s) you want to designate for this action and select. Selected sensor boxes will turn green when activated. Choose the sensor box again to unassign the sensor from the action. See Figure 25.
  • Continue toggling the sensor(s) corresponding to this new action until you are satisfied with your selection. These can be adjusted later by returning to this page.
    Action Name and Devices 

Press the Check-mark button to complete the process.

SECURITY

Data security and integrity is paramount at Scigiene. Each layer of the system is secured using encryption and protocols designed to protect customer data and information. The system consists of sensor(s), gateway(s), and Scigiene Premiere software. One or more sensors communicate with Scigiene Premiere software through a gateway.

SENSOR TO GATEWAY
Sensor and gateway radio modules are purpose-built devices with proprietary unreadable firmware, which means the sensor cannot be physically hacked or re- purposed for malicious purposes. This adds a strong level of inherent security even before considering encryption. Data transmission between the sensor and gateway are secured using Encrypt-RF Security (DiffieHellman Key Exchange + AES-128 CBC for sensor data messages). Beyond the encryption, data transmissions are also structurally verified and CRC checked before they are passed up to Scigiene Premiere or down to the sensor, this ensures the integrity of the data itself.

GATEWAY TO SCIGIENE PREMIERE
Data transmissions between the gateway and Scigiene Premiere software are secured using 256-bit, bank level encryption.

SCIGIENE PREMIERE
Access is granted through the Scigiene Premiere user interface, or an Application Programming Interface (API) safeguarded by 256-bit Transport Layer Security (TLS 1.2) encryption. TLS is a blanket of protection to encrypt all data exchanged between Scigiene Premiere and you. The same encryption is available to you whether you are a Basic or Premiere user of Scigiene Premiere. You can rest assured that your data is safe with Scigiene Premiere.

SENSOR PRINTS
Sensor prints utilize a shared key between the software and the sensor to ensure that once the data comes to Scigiene Premiere it is guaranteed to be from the device identified by the sensor print. If this feature is purchased for the device (via Scigiene Premiere software) the devices data becomes impossible to spoof by any malicious device.

SUPPORT

For technical support, trouble shooting tips and for error reporting, please contact Scigiene.

WARRANTY INFORMATION

(a) Scigiene warrants that Scigiene-branded products (Products) will be free from defects in materials and workmanship for a period of one (1) year from the date of delivery with respect to hardware and will materially conform to their published specifications for a period of one (1) year with respect to software. Scigiene may resell sensors manufactured by other entities and are subject to their individual warranties; Scigiene will not enhance or extend those warranties.
Scigiene does not warrant that the software or any portion thereof is error free. Scigiene will have no warranty obligation with respect to Products subjected to abuse, misuse, negligence or accident. If any software or firmware incorporated in any Product fails to conform to the warranty set forth in this Section, Scigiene shall provide a bug fix or software patch correcting such nonconformance within a reasonable period after Scigiene receives from Customer (i) notice of such non-conformance, and (ii) sufficient information regarding such non-conformance so as to permit Scigiene to create such bug fix or software patch. If any hardware component of any Product fails to conform to the warranty in this Section, Scigiene shall, at its option, refund the purchase price less any discounts, or repair or replace nonconforming Products with conforming Products or Products having substantially identical form, fit, and function and deliver the repaired or replacement

Product to a carrier for land shipment to customer within a reasonable period after Scigiene receives from Customer (i) notice of such non-conformance, and (ii) the non-conforming
Product provided; however, if, in its opinion, Scigiene cannot repair or replace on commercially reasonable terms it may choose to refund the purchase price. Repair parts and replacement Products may be reconditioned or new. All replacement Products and parts become the property of Scigiene. Repaired or replacement Products  shall be subject to the warranty, if any remains, originally applicable to the product repaired or replaced.

Customer must obtain from Scigiene a Return Material Authorization Number (RMA) prior to returning any Products to Scigiene. Products returned under this Warranty must be unmodified. Customer may return all Products for repair or replacement due to defects in original materials and workmanship if Scigiene is notified within one year of customer’s receipt of the product. Scigiene reserves the right to repair or replace Products at its own and complete discretion. Customer must obtain from Scigiene a Return Material Authorization Number (RMA) prior to returning any Products to Scigiene. Products returned under this Warranty must be unmodified and in original packaging. Scigiene reserves the right to refuse warranty repairs or replacements for any Products that are damaged or not in original form. For Products outside the one year warranty period repair services are available at Scigiene at standard labor rates for a period of one year from the Customer’s original date of receipt.

(b) As a condition to Scigiene’s obligations under the immediately preceding paragraphs, Customer shall return Products to be examined and replaced to Scigiene’s facilities, in shipping cartons which clearly display a valid RMA number provided by Scigiene. Customer acknowledges that replacement Products may be repaired, refurbished or tested and found to be complying. Customer shall bear the risk of loss for such return shipment and shall bear all shipping costs. Scigiene shall deliver replacements for Products determined by Scigiene to be properly returned, shall bear the risk of loss and such costs of shipment of repaired Products or replacements, and shall credit Customer’s reasonable costs of shipping such returned Products against future purchases.

(c) Scigiene’s sole obligation under the warranty described or set forth here shall be to repair or replace non-conforming products as set forth in the immediately preceding paragraph, or to refund the documented purchase price for non-conforming Products to Customer. Scigiene’s warranty obligations shall run solely to Customer, and Scigiene shall have no obligation to customers of Customer or other users of the Products.

Limitation of Warranty and Remedies.

THE WARRANTY SET FORTH HEREIN IS THE ONLY WARRANTY APPLICABLE TO PRODUCTS PURCHASED BY CUSTOMER. ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY DISCLAIMED. SCIGIENE’S LIABILITY WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE PURCHASE PRICE PAID BY CUSTOMER FOR THE PRODUCT. UNDER NO CIRCUMSTANCES SHALL SCIGIENE BE LIABLE FOR SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE PRODUCTS IS A CONSIDERATION IN LIMITING SCIGIENE’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THIS AGREEMENT MAY BE BROUGHT BY CUSTOMER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.

IN ADDITION TO THE WARRANTIES DISCLAIMED ABOVE, SCIGIENE SPECIFICALLY DISCLAIMS ANY AND ALL LIABILITY AND WARRANTIES, IMPLIED OR EXPRESSED, FOR USES REQUIRING FAIL-SAFE PERFORMANCE IN WHICH FAILURE OF A PRODUCT COULD LEAD TO DEATH, SERIOUS PERSONAL INJURY, OR SEVERE PHYSICAL ORENVIRONMENTAL DAMAGE SUCH AS, BUT NOT LIMITED TO, LIFE SUPPORT OR MEDICAL  DEVICES OR NUCLEAR APPLICATIONS. PRODUCTS ARE NOT DESIGNED FOR ANDSHOULD NOT BE USED IN ANY OF THESE APPLICATIONS.

CERTIFICATIONS

United States FCC

This equipment has been tested and found to comply with the limits for a Class B digital devices, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radiofrequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radiocommunications.However,thereisnoguaranteethatinterferencewillnotoccurin a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of more of the following measures:

Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver
Connect the equipment in to an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.

Warning: Changes or modifications not expressly approved by Scigiene could void the user’s authority to operate the equipment.

RF Exposure

WARNING: To satisfy FCC RF exposure requirements for mobile transmitting devices, the antenna used for this transmitter must not be co-located in conjunction with any antenna or transmitter.

Scigiene and GEN 2 Wireless Sensors:

This equipment complies with the radiation exposure limits prescribed for an uncontrolled
environmentforfixedandmobileuseconditions.Thisequipmentshouldbeinstalledand
operated with a minimum distance of20cmbetweentheradiatorandthebodyoftheuser
or nearby persons.

All GEN 2 Wireless Sensors Contain FCC ID: ZTL-G2SC1. Approved Antennas
GEN 2 devices have been designed to operate with an approved antenna listed below, and havingamaximum gainof14 dBi.Antennas having againgreaterthan14dBiarestrictly prohibited for use with this device. The required antenna impedance is 50 ohms.

Xianzi XQZ-900E (5 dBi Dipole Omnidirectional)
HyperLink HG908U-PRO (8 dBi Fiberglass Omnidirectional)
HyperLink HG8909P (9 dBd Flat Panel Antenna)
HyperLink HG914YE-NF (14 dBd Yagi)
Specialized Manufacturing MC-ANT-20/4.0C (1 dBi 4” whip)

Canada (IC)
English
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the Equivalent Isotopically Radiated Power (E.I.R.P.) is not more than that necessary for successful communication.

The radio transmitters (IC:9794A-RFSC1, IC:9794A-G2SC1, IC:4160a-CNN0301,IC: 5131A-CE910DUAL, IC: 5131A-HE910NA, IC: 5131A-GE910 and IC: 8595A2AGQN4NNN) have been approved by Industry Canada to operate with the antenna types listed on previouspagewiththemaximumpermissiblegainandrequiredantennaimpedancefor each antenna type indicated. Antenna types not included in this list, having a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with this device.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:(1) this device may not cause interference, and(2) this device must accept any interference, including interference that may cause undesired operation of the device.

SAFETY RECOMMENDATIONS – READ CAREFULLY

Be sure the use of this product is allowed in the country and in the environment required. The use of this product may be dangerous and has to be avoided in the following areas:

  • Where it can interfere with other electronic devices in environments such as hospitals airports, aircrafts, etc.
    Where there is risk of explosion such as gasoline stations, oil refineries, etc.

It is responsibility of the user to enforce the country regulation and the specific environment regulation.

Do not disassemble the product, any mark of tampering will compromise the warranty validity. We recommend following the instructions of this user guide for correct setup and use of the product.

Please handle the product with care, avoiding any dropping and contact with the internal circuit board as electrostatic discharges may damage the product itself. The same precautions should be taken if manually inserting a SIM card, checking carefully the instruction for its use. Do not insert or remove the SIM when the product is in power saving mode.

Every device has to be equipped with a proper antenna with specific characteristics. The antenna has to be installed with care in order to avoid any interference with other electronic devices and has to guarantee a minimum distance from the body (23 cm). In case this requirement cannot be satisfied, the system integrator has to assess the final product against the SAR regulation.

Additional Information and Support

For additional information or more detailed instructions on how to use your Scigiene Wireless Sensors or the Scigiene Premiere Online System, please visit us on the web at Scigiene.com.