Schneider Electric CFMT02ZB Flush-Mounted Thermostat Instruction Manual
- June 10, 2024
- Schneider Electric
Table of Contents
Schneider Electric CFMT02ZB Flush-Mounted Thermostat
INSTALLATION
Product Information
The Wiser Flush-mounted Thermostat 2 A is a device used for water-based heating and cooling applications like underfloor heating and radiator heating. It is not suitable for directly connecting an electrical heating. The package includes a thermostat insert, design frame, control module, and installation instructions. The product has a dot matrix display, touch buttons, and control options like closed.
Technical Specifications
- Nominal Voltage: AC 230 V ~, 50 Hz
- Maximum Current Rating: 2 A
- Standby: max. 0.4 W
- Connecting Terminals: Neutral conductor is required
- Ambient: Operating Temperature:
- Relative Humidity: max. 90% non-condensing
- Temperature: Accuracy:
- Temperature: Measurement Resolution:
- Display: 7×5 dot matrix, 3 additional LEDs
- Operating Frequency: 2.405 GHz to 2.48 GHz
- Max. Radio-frequency Power Transmitted: < 10 mW
- Communication Protocol: Zigbee 3.0 certified
- Protection Class: II
- Working Voltage: 230 V
- Over-voltage Category: III
- Rated Impulse Voltage: 4 kV
- Pollution Degree: 2
- CTI Rating of Insulation Components: min. 175 V
- Material Group: IIIa (based on CTI value)
- Disconnection Type: 1.B
Product Usage Instructions
Follow the steps below to use the Wiser Flush-mounted Thermostat 2 A:
- Select Object > Generate QR Code… to create a link to the DUG chapter.
- Place the generated QR code and apply the Object Style QR-Code_Frame.
- Position the QR code graphic over this text.
- Size: 30×30 mm x:35 mm Y: frame + 2 mm
- After the first power up or reset, select a preset by rotating the rotary push-button. Clockwise to increase the preset value or counterclockwise to decrease the preset value.
- To confirm the selection, press the push button for > 1 s.
- If you need to change the preset, reset the thermostat. For more information about factory-reset, refer to the Device User Guide.
- You can find detailed information about the presets in the Device User Guide.
Note: Follow the electrical connection wiring options mentioned in the product manual. Do not connect components that produce heat, such as dimmers or electronic switches. Also, follow all safety instructions and regulations mentioned in the product manual to avoid any accidents or injuries.
Wiser Flush-mounted Thermostat 2 A
About this product
The Wiser Flush-mounted Thermostat 2 A (hereinafter referred to as thermostat)
is mainly used for water-based heating and cooling applications, such as
water-based underfloor heating and radiator heating.
NOTE: The thermostat is not suitable for directly connecting an electrical heating.
Control options
Direct operation: The thermostat can always be controlled on-site.
- Heat/cool change over (external)
- Universal input setback/presence (external)
- Heating and cooling mode
- Volt-free or live control, normally open or normally closed
Package content
- A Thermostat Insert
- B Design Frame
- C Control module
- D Installation instructions
Product details
- A Dot matrix display
- B Touch buttons
Selecting the installation site
In order for the thermostat to be operated, the internal temperature sensor
must be protected as far as possible against external influences and
temperature fluctuations. This helps to guarantee reliable measurement of the
room temperature.
The following should therefore be taken into account when considering the
installation site:
- Minimum installation height: 1.5 m above the floor.
- Do not install too close to windows, doors or venti-lation openings.
- Do not install above heaters or other heat sources.
- Do not cover or install behind curtains.
- Avoid direct sunlight and light from lamps.
- Do not install in power strips next to or above components that produce heat, such as dimmers or electronic switches.
Electrical Connections
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Safe electrical installation must be carried out only by skilled professionals. Skilled professionals must prove profound knowledge in the following areas:
- Connecting to installation networks.
- Connecting several electrical devices.
- Laying electric cables.
- Safety standards, local wiring rules and regulations.
Failure to follow these instructions will result in death or serious injury.
DANGER: RISK OF FATAL INJURY FROM ELECTRIC SHOCK
The output may carry electrical current even when the load is switched off.
- Disconnect the device from the supply by means of the fuse in the incoming circuit before working on the device.
- Make sure the mains input has a 2 A fuse.
Failure to follow these instructions will result in death or serious injury.
Wiring options
- a. Volt-free wiring. Normally open
- b. Switch live wiring with L-COM jumper wire. Normally open
- c. Volt-free wiring. Normally closed
- d. Switch live wiring with L-COM jumper wire. Normally closed
- A Output: max. 2 A resistive load
- B Input: setback / presence detection C Heating / Cooling input
Mounting
Presets: A preset must be selected after the first power up or reset.
- Preset: Configuration
- P1: Heat Pump/Oil Boiler
- P2: Hydronic Radiator/Gas Boiler
- P3: Hydronic Underfloor
NOTE: When a preset is selected, it can only be changed by resetting the thermostat. For more information about factory-reset, refer to the Device User Guide.
Selecting a preset
To switch between presets, rotate the rotary push-but-ton. Clockwise to
increase the preset value or counter-clockwise to decrease the preset value.
Confirming the preset
To confirm the selection, press the push button for
You can find detailed information about the presets in the Device User Guide.
Reading the full Device User Guide online
Scan the QR code and choose your language for complete information about the
device, including operation, configuration and using the product with a Wiser
system.
Technical data
Nominal voltage: | AC 230 V ~, 50 Hz |
---|---|
Maximum current rating: | 2 A |
Standby: | max. 0.4 W |
Connecting terminals: | Terminals for |
max. 2.5 mm²
Neutral conductor:| Required
Ambient operating tem- perature:| ****
0 to 45 °C
Relative humidity:| max. 90% non-condensing
Temperature accuracy:| max. ±0.5 °C (accross the range of 4 to 30 °C)
Temperature measurement resolution:| ****
max. 0.1 °C
Display:| 7×5 dot matrix, 3 additional LEDs
Operating frequency:| 2.405 GHz to 2.48 GHz
Max. radio-frequency power
transmitted:
| ****
< 10 mW
Communication protocol:| Zigbee 3.0 certified
Protection Class:| II
Working voltage:| 230 V
Over-voltage category:| III
Rated impulse voltage:| 4 kV
Pollution degree:| 2
CTI rating of insulation components:| ****
min. 175 V
Material group:| IIIa (based on CTI value)
Disconnection type:| 1.B
Trademarks
- Wiser™ is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
- Zigbee® is a registered trademark of the Connectivity Standards Alliance. Other brands and registered trademarks are properties of their relevant owners
EU Declaration of Conformity
Hereby, Schneider Electric Industries, declares that this product is in
compliance with the essential requirements and other relevant provisions of
RADIO EQUIPMENT DIRECTIVE 2014/53/EU. Declaration of conformity can be
downloaded on:se.com/docs.
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in
your country.se.com/contact
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>