CloudLink Cat M1 Modem
R110
Software Change Notice
Revision Date: April 7, 2022
Document ID: Software Change Notice
Notices and Trademarks
© Honeywell International Inc. 2012. All Rights Reserved.
While this information is presented in good faith and believed to be accurate,
Honeywell disclaims the implied warranties of merchantability and fitness for
a particular purpose and makes no express warranties except as may be stated
in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any indirect, special or
consequential damages. The information and specifications in this document are
subject to change without notice.
Other brand or product names are trademarks of their respective owners.
Honeywell Process Solutions
1250 W Sam Houston Pkwy S
Houston, Tx 77042 USA
www.honeywellprocess.com
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol | Definition |
---|---|
ATTENTION: Identifies information that requires special consideration. | |
TIP: Identifies advice or hints for the user, often in terms of performing a |
task.
| REFERENCE -EXTERNAL: Identifies an additional source of information outside
of the booklet.
| REFERENCE – INTERNAL: Identifies an additional source of information within
the booklet.
CAUTION| Indicates a situation which, if not avoided, may result in
equipment or work (data) on the system being damaged or lost, or may result in
the inability to properly operate the process.
| CAUTION: Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to alert against
unsafe practices.
CAUTION symbol on the equipment refers the user to the product manual for
additional information. The symbol appears next to required information in the
manual.
| WARNING: Indicates a potentially hazardous situation, which, if not
avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product manual for
additional information. The symbol appears next to
required information in the manual.
| WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS
LIVE voltages greater than 30 Vrms, 42.4 Peak, or 60 VDC may be accessible.
| ESD HAZARD: Danger of an electro-static discharge to which equipment may be
sensitive. Observe precautions for handling electrostatic sensitive devices.
| Protective Earth (PE) terminal: Provided for connection of the
protective earth (green or green/yellow) supply system conductor.
| Functional earth terminal: Used for non-safety purposes such as noise
immunity improvement. NOTE: This connection shall be bonded to Protective
Earth at the source of supply in accordance with national local electrical
code requirements.
| Earth Ground: Functional earth connection. NOTE: This connection shall be
bonded to Protective Earth at the source of supply in accordance with
national and local electrical code requirements.
| Chassis Ground: Identifies a connection to the chassis or frame of the
equipment shall be bonded to Protective Earth at the source of supply in
accordance with national and local electrical code requirements.
Introduction
1.1 About CloudLink Cat M1 Modem
Cloud Link is a future proof intrinsically safe cellular radio (Cloud Link)
with form factor, certifications and carrier approvals that can also be used
as a component in a variety of industrial process control and monitoring
applications and wireless platforms. Cloud Link can be used with wireless
applications with cellular and BLE.
1.2 About this Document
The Cloud Link R110 Release Notes is intended for service engineers who are
assigned to provision, configure, operate Cloud Link Cat M1 device
1.3 Limitations
N/A
1.4 Technical Assistance
Honeywell PMC
2101 City West Blvd,
Houston, TX 77042
Telephone: 855-251-7065
Email: MI-TAC-Support@Honeywell.com
Website: https://www.honeywell.com/ps
Contents of Release
Cloud Link R110 Firmware version is v1.02.12
Table 1 Cloud Link Cat M1 Modem
Product | Part Number |
---|---|
CloudLink- R110 Hex file | 51121638-100 |
Cloud Link- R110 Bin file | 51121638-200 |
Release Overview
3.1 Features
Key features of Cloud Link are mentioned below:
-
Cellular Communication
Supported Bands:
i. LTE(CatM1) : Band 13. -
Supports IPv4 Internet Protocols
-
Call in / Call out
• CloudLink Supports Call in (CloudLink device connects to the host system (Power Spring) over IPv4 through LTE(CatM1).
• CloudLink Supports Call Out (CloudLink listens for connections from the host system (Master Link / Power Spring) over IPv4 through LTE(CatM1). -
Bluetooth Low Energy (BLE) communication
• Bluetooth Low Energy Communication is short range wireless communication used for communicating with Mobile devices, Mobile Tabs -
Serial Communication
• RS232 Interface
• RS485 Interface -
Firmware upgrade
• CloudLink device firmware can be upgraded remotely using Cellular Interface (Over The Air) by host software (Master Link/CloudLink Connect)
• CloudLink firmware upgrade can also be done using RS232, RS485, BLE interfaces in the field. -
Pulse Counting
a. CloudLink Supports one pulse input, these pulse count can be read remotely by sending AT commands over serial interface -
Diagnostics Support
• CloudLink device has 4 LEDs used for various diagnostic indication
• CloudLink device logs diagnostic information can be read remotely over cellular interface -
Cellular Statistics
• CloudLink device logs each call data like Access Technology, RSSI, Location ID / TAC, Cell ID, Physical Cell ID, MCC, MNC, Last Call Duration, Last Call Status -
AT commands
• Custom commands provided to read Cloud Link Diagnostic and pulse count information -
Alarms
• CloudLink generates alarms in case of Emergency call in (Magnetic switch call) and Low Battery Indication -
Field / Remote Configuration
• Device can be configured remotely or in the field -
Password protected communication
• Configuration Over Serial Interface, BLE, EC350 IR, Cellular Interface -
Transparent modem
• CloudLink will act as integrated transparent modem, or standalone modem -
Security
• Supports BLE Just Works and Passkey Entry
• Whitelisting
3.2 New Features
This release contains the following new enhancements:
3.2.1 New alarms types added. Item i3189 provides the active alarms
conditions.
- Radio Power ON Failure
- SIM Card Error
- Radio Registration Failure
- Radio Module Not Responding
- Data Connection Failure
- Host Not Reachable – Call Failure
3.2.2 Network drop recovery mechanism, new item number i3193 introduced for recovering from network drop (RGASMETER-284)
S.NO | Description | Item number | Default value |
---|---|---|---|
1. | TCP server refresh configuration parameter | 3193 | 1800 seconds |
2. | DNS/Ping server IP address | 3042 | 127.0.0.1 |
3. | DNS/Ping server IP address Enable to change default IP address | 3036 |
Disable
Note:
- Recovery mechanism works based on principle of creating a network traffic from the unit to cellular network at defined time interval to avoid out-off network for longer duration.
- This is achieved through the item number i3193. TCP server is closed periodically for the time mentioned in the item number i3193 and opens TCP client and gets connect to the IP address mentioned in item number i3042. By doing this, unit will try to connect to the IP address mentioned in i3042 which creates a network traffic from the unit to cellular network.
- The default IP address in i3042 can be changed only if i3036 is ENABLE.
3.3 Changes to Existing Functionality
This release contains the following changes to existing functionality:
3.3.1 FOTA feature is improved in this build.
Refer to FOTA update Procedure from the FOTA update instructions
- To setup FTP server you can refer to our knowledge base article Setup FTP server with FileZilla.
- When FOTA is initiated, continuous server mode or call out window is closed and proceed with FOTA process. After FOTA process if continuous server mode is enabled, continue with continuous server mode.
- Event logs are enhanced for FOTA in this build.
- New Radio FW version is updated in item number i3021 after FOTA.
Note:
- To perform FOTA, firstly application FW must be upgrade with this build v1.02.12 using master link
- Perform FOTA only if radio FW version in item number i3021 is other than 30.10.002-B003. This radio FW version is having a fix from radio vendor side for radio not responding and LED error code -12.
3.3.2 AT command response timing delay increased as suggested by Tallit radio
vendor to prevent radio going into nonresponse state and need to upgrade radio
FW version to 30.10.002-B003 through FOTA as mentioned in above point 3.3.1
note – 2. (RGASMETER – 444).
3.3.3 Changed firmware upgrade item number i3107 behavior as explained below:
Item number | Enum description | Default value |
---|---|---|
3107 | Enable 4 Firmware upgrade on the unit is allowed. | Disable |
Disable 4 Firmware upgrade of the unit is not allowed.
Note: After firmware upgrade item number i3107 is automatically reverted
to default state.
3.3.4 Error shown in master link for FW upgrade, changed from access code
error (error code 27) to data write denied (error code – 39).
3.3.5 Fix call-in failure (from not flushing comma buffers from previous call)
(RGASMETER 463)
3.3.6 Fix call-in failure (from premature cellular network registration
timeout) (RGASMETER491)
3.3.7 Fix call-in failure (from premature IP packet time-out – call dropped
and reported as Network Read/Write error in PS)
3.3.8 Fix call-in failure (from sending RG packets out of order – call dropped
and reported as BAD CRC error in PS) (RGASMETER-476)
3.3.9 Fix to preserve item 3113 pulse count through soft reset operation
3.3.10 Fix BLE start/stop time functionality
3.3.11 Fix BLE pass-through to instrument disable (3162=0 was not blocking it
as intended)
3.3.12 Fix duplicate cellular logs for same call
3.3.13 Fix call duration in cellular logs
3.4 Retired Features
The following features and functions have been removed from the release:
N/A
Software/Hardware/Firmware Compatibility
Description | Release / Version |
---|---|
CloudLink Power board | Rev A |
CloudLink Radio board | Rev A |
Master Link | Software utility R515.1, Build version: 15.1.35.0 |
Power Spring | R301.1 |
EC350 R100 release HW | Rev E |
EC350 R144 and R147 release FW | 1.4410, 1.4712 |
Mi Wireless with Mini Max | Mini Max FW version 2.97 |
Mi Wireless with ERX | ERX FW version 3.3201 |
CNI4 | v3.1303 |
Documentation Updates/Additional Information
N/A
Problems Resolved
This section provides an overview of the problems resolved in this release.
S.NO | Description | ID’s |
---|---|---|
1 | CL R110 Modem Error 12 | RGASMETER – 444 |
2 | CloudLink causing call in failure (not flushing comma buffers from previous | |
call) | RGASMETER – 463 | |
3 | CLR110 – call in failure due to registration timeout | RGASMETER – 491 |
4 | CloudLink R110: packets out of order causing call failure with PS (BAD | |
CRC) | RGASMETER — 476 | |
5 | CL R110 Cat M1 4G modem won’t stay on the cellular network | RGASMETER — 284 |
Installation and Migration
N/A
Un-Install Instructions
N/A
Issues
N/A
Security-Related Issues
N/A
Special Considerations
N/A
Third-Party Software Components
N/A
Appendix
N/A
Milestone Completion Checklist
Software Change Notices are directly related to a specific release. The criteria for assessing SCNs are not dependent on the phase.
Construction
For most HIP types, the draft SCN for the final release shall be available by
end-of-construction and shall include content in all sections.
For the Express Delivery HIP type, which features only a Construction phase,
the draft SCN needs to be complete as builds are turned over to Test, who then
verifies the work product as a part of the test efforts.
Phase in which Release Occurred
Process Compliance Checklist High Level Evaluation Criterion:
- Software Change Notice prepared & reviewed prior to gaining acceptance to Release.
Content at Milestone | Comments (optional) |
---|
All sections completed.
The hidden test within this document should be used when reviewing content.|
All sections completed.
The hidden test within this document should be used when reviewing content.|
Check for evidence of review & that resulting issues have been tracked-to-
closure.
Cloud Link Cat M1 Modem Release R110
Software Change Notice