Dwyer Instruments AVUL-3DA1-LCD Air Velocity Transmitter Instruction Manual

June 10, 2024
Dwyer Instruments

Dwyer Instruments AVUL-3DA1-LCD Air Velocity Transmitter

AVUL-3DA1-LCD Air Velocity Transmitter

The Series AVUL Air Velocity Transmitter quickly and accurately measures air velocity or volumetric flow in imperial or metric units. Simultaneous current and voltage outputs on all models provide universal inputs to monitoring equipment while the output range, units, and 0-5/10 VDC output can be configured via local DIP switches. The optional integral display, or the portable remote display tool, provide a convenient way to locally monitor process values and configure the unit.

Models are available in 3% and 5% of reading accuracy models to suit a variety of needs, and the optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows units to be daisy-chained while providing access to all of the velocity and flow data, as well as additional information such as air temperature.

MODEL CHART

Model| AVUL| -3| D| A1| -LCD| AVUL-3DA1-LCD
Accuracy| | 5

3

| | | | ±(0.2 m/s + 5% of reading) @ standard conditions
±(0.2 m/s + 3% of reading) @ standard conditions
Mounting| | | D| | | Duct mount
Output| | | | A1

B1 M1

| | Analog universal (0-5 VDC, 0-10 VDC, 4-20 mA)
Analog + BACnet MS/TP Analog + Modbus® RTU/ASCII
Options| | | | | LCD FC NIST GLD SF| LCD display
Factory calibration certificate NIST certificate
Electrical cable gland Silicone free

SPECIFICATIONS

Service: Clean air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Range: 1000, 2000, 3000, 4000 FPM (5, 10, 15, 20 m/s); Field selectable.
Accuracy: ±(5% of reading + 0.2 m/s) or ±(3% of reading + 0.2 m/s) @ standard conditions, depending on model.
Temperature Limits: 32 to 122°F (0 to 50°C).
Power Requirements: 24 VDC ±20% or 24 VAC ±20%.
Humidity Limits: 5 to 95% RH, non-condensing.
Output Signals: 4-20 mA, 0-5 VDC, 0-10 VDC.
Response Time (90%): 10 s, typical.
Zero and Span Adjustments: Digital push buttons.
Output Load Resistance: Current output: 0 to 1100 Ω max.; Voltage output: Minimum load resistance 1 kΩ.
Current Consumption: 60 mA max.
Display (Optional): 5 digit LCD.
Electrical Connections (Analog): Power and output: 4-wire removable European style terminal block for 16 to 26 AWG.
Communication (Optional): Connections: BACnet MS/TP or Modbus® RTU/ASCII: 3-wire removable European style terminal block for 16 to 26 AWG; Supported baud rates: 9600, 19200, 38400, 57600, 76800, 115200.
Device Load: 1/8 unit load.
Electrical Entry: 1/2˝ NPS thread. Accessory (A-151): Cable gland for 5 to 10 mm diameter cable.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Flow direction must be parallel to the sensor tip; See Installation section for details.
Weight: 6.0 oz (160 g).
Compliance: CE.
Specifications

INSTALLATION

Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling coils, and other equipment that will effect the measurement of the air velocity. It is recommended that the AVUL is mounted 10 duct diameters downstream of any disturbances and 5 duct diameters upstream of any disturbances, if possible.

  1. Mark and drill a 0.750 to 0.938˝ (20 to 24 mm) diameter hole into the duct.
  2. Insert and center the duct mount flange in the previously drilled hole and mark location of the three mounting screw holes.
  3. Remove the mounting flange and drill or punch the mounting holes in the marked locations.
  4. Fasten the flange to the duct using three #8 x 1/2 pan head sheet metal screws. Do not over tighten screws.
  5. Insert the AVUL probe into the ducts mount flange and set the desired insertion depth.
  6. Note the flow direction and unit alignment as shown on sensor tip and product label, tighten probe retention set screw on the duct mount flange screw to affix the probe in place.
Electrical Connection:

The Series AVUL is powered and simultaneously transmits a 2-wire 4-20 mA current output and a three-wire 0-5 VDC or 0-10 VDC voltage output via a removable four conductor terminal block. The transmitter power supply common is used to reference the current and voltage outputs so either current, voltage, or current and voltage may be wired according to the application. The range of the voltage output can be selected using the on board DIP switches as described in the Analog DIP Switch Settings section of this manual.

Power Supply

Choose a power supply with a voltage and current rating sufficient to meet the power specifications under all operating conditions. If the power supply is unregulated, make sure the output voltage remains within the required voltage range under all power line conditions. Ripple on the supply should not exceed 100 mV.

CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

**Current Output Operation

**

CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. As the power supply and outputs share the same common signal (GND), the outputs may have separate wires but must effectively join at terminal 2 of the transmitter, as shown in Figure 1. The connections to the transmitter are made to terminals 1, 2, and 3 (PWR, GND, and IOUT respectively) on the terminal block as shown in Figure 4.
Current Output Operation
Although low loop resistances are recommended, the absolute maximum current loop load resistance, RMAX , is defined by the following the equation:
RMAX = (VPS – 2.0) 0.02 where VPS is the power supply voltage
For a 24 VDC nominal power supply, this evaluates to RMAX = 1100 ohms.
Shielded two wire cable is recommended for current output loop wiring. Ground the shield at the power supply end only

The maximum length of connecting wire between the current transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 ft.), it is desirable to select receivers with higher resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 ft, connecting lead wire as small as No. 22 Ga. can be used.

Voltage Output Operation

CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 2. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, and 4 (PWR, GND, and VOUT respectively) on the terminal block as shown in Figure 4.
Voltage Output Operation

The minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gauge, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%.
The output across VOUT and COM will be either 0-5 VDC, 0-10 VDC, or the inverse depending on the DIP switch setting. See the Analog DIP Switch Settings section for more information.

Simultaneous Current and Voltage Output Operation

CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 3. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, 3 and 4 (PWR, GND, IOUT, and VOUT respectively) on the terminal block as shown in Figure 4, which reflects both the 4-20 mA and 0-5/10 VDC outputs in the same circuit. Details of each output are detailed in their electrical connection sections.

Figure 3: Simultaneous current and voltage output wiring

ANALOG DIP SWITCH SETTINGS

The analog output DIP switches (SW1) are located above the terminal blocks on the left are as shown in Figure 4. A small screw driver or pen can be used to change the position of the switches as required. DIP switch positions for SW2 and SW3 are RESERVED or have no affect.

WARNING All power should be turned off to the transmitter before adjusting the DIP switch settings to avoid electrical shock.

ANALOG DIP SWITCH SETTINGS

Factory Default Settings (DIP SW1 – All Switches ON)

Range = Highest Range Setting (4000 FPM)
Units = Imperial (FPM)
Voltage Output Range = 0-10 VDC
Direct / Reverse Output Action = Direct

Setting the Air Velocity Range

The range of the instrument is selected by using DIP switches 1 and 2 on SW1. Table 1 shows the maximum full scale value for the selected range and unit. Refer to Setting the Engineering Units section for information on setting the unit.

DIP Switch SW1 Full Scale Range
1 2
ON ON
ON OFF
OFF ON
OFF OFF

Table 1: DIP switch SW1 settings for full-scale range

Setting the Engineering Units

The Series AVUL can be configured to indicate velocity in imperial (FPM, CFM) or metric (m/s, m3 /h) units using DIP switches 4 and 5 on SW1, and Table 2 shows the values. The units will be displayed on the optional LCD display if connected.

DIP Switch SW1 Units
4 5
ON ON
ON OFF
OFF ON
OFF OFF

Table 2: DIP switch SW1 settings for units

The default operating mode is velocity, but changes can be made, such as flow mode, via the menu system while an optional display or remote display accessory is connected. Please refer to Appendix III for a full menu flow chart.

Setting the Output Voltage Range

Voltage Output can be either 0-5 VDC or 0-10 VDC depending on the position of DIP Switch 6 ON SW1.

  • When the switch is in the ON position, the output will be 0-10 VDC.
  • When the switch is in the OFF position, the output will be 0-5 VDC.
Setting the Input / Output Action

The output will either follow the process directly (DIRECT) or inverted (REVERSED) based on the position of DIP Switch 7 on SW1.

  • When the switch is in the ON position, the output directly follows the input (i.e. output increases as the input increases).
  • When the switch is in the OFF position, the output acts in reverse of the input (i.e. output decreases as the input increases).
CALIBRATION

NOTICE There is a 5 second delay from the time the zero or span calibration buttons are released until the time that the change in calibration takes place. This delay is used to reduce vibration or disturbances of the user related to the button presses

NOTICE   The security level that is set in the Programming Menu section of the manual will determine which calibrations, if any, may be adjusted by the user.

Zero Calibration

The zero calibration can be set by covering the sensor to ensure no air flow and pressing the zero button for 3 seconds. If either the remote or local LCD is present, the display will read ZERO and then sequence back to the home display.

SPAN Calibration

The span calibration can be adjusted only after setting the zero adjustment. It must be completed within 5 minutes of the last zero calibration. The span calibration button will be ignored until the zero calibration is completed. Place the sensor in airflow that matches the maximum selected range of the transmitter. Press and hold the span button for 3 seconds. If either the remote or local LCD is present, the display will read SPAn and then sequence back to the home display. If the span calibration is attempted before adjusting the zero calibration, the FAiL error message will be displayed briefly before returning to the home display.

LCD Display

The Series AVUL can be ordered with an optional, integral LCD. It comes with a housing cover and overlay to protect the display. The display will plug into the pins as shown in Figure 5. If the display is not needed for normal operation, the transmitter can be ordered without the LCD.
LCD Display

Another option for models that do not have a display would be to use a Model A-435-A remote display tool which can plug into the connector shown in Figure 6. The remote display tool has two buttons that function identically to the buttons on the PCB.

LCD Display

Display Error Messages

= The air velocity is greater than the maximum span value causing an Over
Range Error
Display Error Messages= The air velocity is less than the minimum span value causing an Under Range Error
 = When the span or zero buttons are pressed, the air velocity value is out of the range to allow a correct setting. This may be due to a sensor failure.
= The sensor is damaged.

PROGRAMMING MENUS

Home Menu

During normal operation, the display will be in the Home Menu and will display the current measured pressure and the engineering units.

While in the Home Menu, press and hold the Zero and Span buttons simultaneously until appears on the display in order to access the other programming menus. Upon releasing the buttons, the display will indicate the current security level.
If the current security level is the security level desired (i.e. Security Level 0), press and hold the span button for 3 seconds to enter the Velocity or Air Flow Menu.
If the security level is not the desired level, the security level can be changed temporarily to a lower security level or permanently to a higher level of security by pressing the zero button. A security code will appear on the display, and it can be changed to one of the codes listed in Table 3. The span button chooses which digit and the zero button increments the value of that digit. Pressing and holding the span button will store the value. The level of access to the programming menus and the calibration is limited based on the security level. Table 3 details the level of access for each security level.

Security Level **Setting** Access
View Menu Edit Menu Span
0 000 Yes
1 111 Yes
2 222 No
3 333 No

Table 3: Security settings

Mode Selection / Digital Dampening Menu

From the home display, pressing the span and zero button simultaneously for 3 seconds will access the Menu Security Level. If the level is set to 0 or 1, pressing and holding the span button for 3 seconds, a second time, will access the Mode Selection Menu. The display will default to air velocity when first powered up. Pressing the zero button will cycle to air flow.

Once the desired mode is displayed, pressing and holding the span button for 3 seconds will save the selected mode and display the digital dampening or averaging parameter. This parameter stabilizes the output and the display by averaging the readings. There are 2.5 readings taken each second and the user can select the number of seconds that they would like to average, up to 240 seconds. The display and the output will continue to update at a rate of 2.5 updates per second, but the moving average is used for these updates.

Velocity Mode

K-Factor Adjustment
If the Velocity Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Velocity Mode and the transmitter will display the engineering unit that has been selected by the DIP switch. Pressing and holding the span button for 3 seconds will enter the K – Factor adjustment. The K – Factor can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Maximum Output Adjustment parameter.

Flow Mode

K-Factor Adjustment
If the Flow Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Flow Mode and the transmitter will display the engineering unit that has been selected by the DIP switch. Pressing and holding the span button for 3 seconds will enter the K–Factor adjustment. The K–Factor can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Area Adjustment parameter.

Area Adjustment

For flow applications, the area is multiplied by the velocity to determine the volumetric air flow. The area will be listed in either CFM or m3 /h depending on the DIP switch settings. The units will appear on the display at the time of adjustment. The area can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Maximum Output Adjustment parameter.

Maximum Output Adjustment

The maximum output can be equivalent to air velocity or air flow. After adjusting the K-Factor, the display will indicate if the adjustment is set for velocity or air flow.  Pressing the zero button will toggle between the selections. Pressing and holding thespan button for 3 seconds will enter the maximum output adjustment. The maximum output can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will save this value and go to the Security Update Menu.

Security Update / Save Changes Menu

The Security Update Menu allows the security level to be set either higher or lower than the current security level setting. This security level will be displayed the next time the Menus are accessed from the home screen. Pressing the zero button cycles through the security levels. Pressing and holding the span button for 3 seconds accepts the new security level and gives the option to save all the menu changes. Pressing the zero button will toggle between yes and no. Yes will save the changes made to all menu items and no will discard all the changes made to all menu items. If the display is set to yes, pressing and holding the span will save the menu items and return the display to the home position.

FACTORY DEFAULT PROCEDURE

In order to reset all of the menu settings back to their factory programmed values, press and hold both the span and zero buttons simultaneously for 10 seconds until FACt is displayed on the LCD. Upon releasing the buttons, the unit will be factory defaulted. Since resetting the transmitter will wipe out all changes, it is necessary to zero (and possibly span) the transmitter before taking measurements.

MAINTENANCE/REPAIR

Upon final installation of the Series AVUL Air Velocity Transmitter, no routine maintenance is required besides zeroing the transmitter occasionally. Besides routine calibration and installation of the LCD, the Series AVUL is not field serviceable, and it is not possible to repair the unit. Field repair should not be attempted and may void warranty.

WARRANTY/RETURN

Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.

APPENDIX I: Air Velocity / Air Flow Calculations

Velocity in m/s is then calculated from the equation:
Velocity (m /s) = Velocity (FPM) x 0.00508
Flow in m3 /h is then calculated using the below equation:
Flow (CFM) = Area (ft2 ) x K-Factor x Velocity (FPM)
Flow (m3 /h) = Flow (CFM) x 1.6992

APPENDIX II: Maximum Flow
Max Flow Max K Factor x Area
CFM m 3 /h
5885000 9999000
APPENDIX III: BACnet MS/TP Operation

NOTICE Wiring should comply with Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems, TIA/ EIA-485-A-1998, Telecommunications Industry Association, 1998.

NOTICE Wiring should comply with ANSI/ASHRAE Standard 135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 2010.

NOTICE Communications wiring must be in a daisy-chain fashion. Star connections are not permitted.

NOTICE Cable shield must be connected to earth ground at one location only.

Figure 7 shows how to connect the AVUL in a network containing a common power supply. Use a cable containing two twisted pairs. One pair is to be used for D1[+] and D0[-]. The other pair is to be used for power and common. This configuration is not suitable for AC supplies. Use a DC supply only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you have many devices, or have long cable runs, the local supply configuration may be a better choice.
APPENDIX III: BACnet MS/TP Operation

Figure 8 shows how to connect the AVUL in a network containing individual local supplies. Use a cable containing a twisted pair and a single conductor. The pair is to be used for D1[+] and D0[-]. The single conductor is to be used for common. Both AC and DC supplies are suitable for this configuration.
APPENDIX III: BACnet MS/TP Operation

In either configuration you must use shielded cable. The AVUL has a shield terminal for a convenient location to make connections. It is not electrically connected to the AVUL. Connect the shield to earth ground at one location only to prevent ground loops.

All devices in the network should be daisy chained. Star connections and T connections are not permitted.

The D1[+] and D0[-] lines must be terminated at both ends with a 120 Ω resistor. If the AVUL is an end device it has an on-board resistor that may be used. See BACnet MS/ TP DIP Switch Settings to enable it.

The network must be biased properly. If needed, there are bias resistors on- board the AVUL. No more than two sets of bias resistors should be enabled in the network. See BACnet DIP Switch Settings to enable them.

BACnet MS/TP DIP Switch Settings

Use the middle DIP Switch SW2 to configure the BACnet MS/TP MAC communication protocol address of the device. The LCD will show the address when the transmitter is powered on. Valid addresses range from 0 to 127. By default, the device is shipped with the address 127 (as shown in Figure 10). A valid and unused address should be set before connecting to an existing network. However, the address can be changed while the device is operational. If the address is changed, the device will stop responding to the currently configured address immediately. The device waits 15 seconds after the last switch change before applying the new address. The device will not function properly if an invalid address is set. The red LED will periodically blink once indicating an invalid address. The LCD will display A Err when the transmitter is powered on if the address is invalid. See Appendix V for setting the BACnet MS/TP MAC address of the device. Use the right DIP Switch SW3 to configure other hardware and software options.

BACnet MS/TP DIP Switch Settings

Switch On Off

1-2 – Display Units Selection 3-4 – Reserved
5 – Reset BACnet Configuration to Factory Defaults
6 – D1[+] Network Resistor
7 – D0[-] Network Resistor 8 – Terminating resistor| **** Reset settings at Power On

**** 511Ω Pull-up to 5 V 511Ω Pull-down to GND 120Ω between D0[-] and D1[+]

| **** Settings Preserved

**** Pull-up not connected Pull-down not connected Open

Table 5: DIP switch SW3 functions

APPENDIX IV: Programming Via BACnet MS/TP Communication Protocol

Supported Baud Rates Data Size Parity Stop Bits

9600

19200

38400

57600

76800

115200

| 8| None| 1

Table 6: Supported BACnet communication protocol  MS/TP configurations

Auto-Baud Serial Configuration

Auto-baud serial configuration enables the device to determine the baud rate directly from the serial traffic. This allows a device to be quickly and easily deployed after a valid BACnet Communication Protocol MS/TP address is chosen.

To activate auto-baud serial configuration, set a valid BACnet Communication Protocol MS/TP address using the left DIP switch SW2, connect the serial bus and power wires, and then apply power. The device will power up and begin examining the serial bus for communication. The Red LED will repeatedly flash twice, indicating that auto-baud serial configuration is in progress.

If the device is setup offline or away from the main network, it is necessary to generate BACnet Communication Protocol MS/TP traffic in order to configure the serial communication. Initiating a WhoIs command is a good method to generate BACnet Communication Protocol MS/TP traffic and verify the device is working properly. Note that while serial configuration is in progress, the device may not respond to requests. The device may require multiple requests to complete the serial configuration process.

The auto-baud serial configuration process will complete once a WhoIs or ReadProperty command is successfully received and processed.

The auto-baud serial configuration procedure is started after a power-cycle and after a change to the MS/TP address.

BACnet MS/TP Communication Protocol Object Overview

**Object
Type| Dynamically
Creatable| Dynamically
Deletable| Object
Identifier| ****Object Name**
---|---|---|---|---
Device Analog Input

**** Analog Value

**** Binary Value

| No
No

No

No

| No
No

No

No

| 607xxx
AI1
AI2
AI3
AI4
AV1
AV2
AV3
AV4
BV1
BV2 BV3| AVUL Velocity Velocity FPM Velocity MPS Temperature F Temperature C Flow CFM
Flow CMH
Flow Area SqFt Flow Area SqM Zero
Span
Restore Factory Pressure Values

Table 7: Supported BACnet MS/TP Communication Protocol Objects

Device Information

The default device object identifier is 607xxx, where xxx is replaced by the MS/TP MAC address set by the middle DIP switch SW2. The object identifier value will change as the MS/TP MAC address changes. However, if a specific object identifier is written via BACnet MS/TP Communication Protocol, then that value is stored and changes to the MS/TP MAC address will no longer affect the object identifier. See Appendix VI for the device object property tables.

NOTICE  Changes to Max Master and Max Info frames require a power cycle/reset to take effect.

Accessing the Measurements

The analog input object AI1 through AI4 are for viewing Air Velocity or Temperature in the desired engineering units. The object property tables for these analog input objects can be found in Appendix VI.

Analog value object AV1 through AV4 are for viewing the Air Flow or Flow Area calculated values in the desired engineering units. The object property tables for the analog value objects can be found in Appendix VI.

Zero Calibration

Zero calibration can be done either with the push buttons or using BACnet MS/TP communications. The unit should have no air flowing through it. When using BACnet MS/TP communications, the binary value object (BV1) will be used to signal the transmitter to zero the reading. The present value of this object will be set to ACTIVE (1) to initiate the re-calibration of the zero point of the sensor. The zero function will only work if the current velocity is within ±2% of the span velocity of the previous zero. If the current velocity is outside of this valid band, the zero function will fail and the present value will be changed to INACTIVE (0). The zero function takes at most 10 seconds to complete. If after this time the present value remains ACTIVE (1), then the command was executed successfully. The object property tables for the binary value objects can be found in Appendix VI .

Span Calibration

In order to adjust the span calibration, place the unit in a flow with air velocity that is associated with the maximum end of the transmitter range. The binary value object (BV2) will be used to signal the transmitter to adjust span. The present value will be set to ACTIVE (1) to initiate the span calibration. The span calibration can be adjusted only after setting the zero adjustment. It must be completed within 5 minutes of the last zero calibration. The span calibration command will fail until the zero calibration is completed and the present value will be returned to INACTIVE (0). The span function takes at most 10 seconds to complete. If after this time, the present value remains ACTIVE (1), then the command was executed successfully. The object property tables for the binary value objects can be found in Appendix VI.

Reset factory Defaults

Present values for the zero, span, and area can be restored to the factory settings using the binary value object (BV3). The present value will be set to ACTIVE (1) to initiate the factory default procedure. The factory default takes at most 10 seconds to complete. If after this time, the present value remains ACTIVE (1), then the command was executed successfully. The object property tables for the binary value objects can be found in Appendix VI.

BACnet MS/TP Communication Protocol Services

BACnet MS/TP Communication Protocol Services

This device supports the Device Communication Control Service BIBB. The optional time duration in minutes is also supported. This device is configured with a password that must be provided to successfully execute this command. The password is “Dwyer”.

Reinitialize Device Service (DM-RD-B)

This device supports the Reinitialize Device Service BIBB. The supported device states are COLDSTART and WARMSTART. All other states return error. This device is configured with a password that must be provided to successfully execute this command. The password is “Dwyer”.

APPENDIX V: Setting BACnet Communication Protocol MS/TP MAC

Address of Unit

Switch Position| 1| 2| 3| 4| 5| 6| 7| 8
---|---|---|---|---|---|---|---|---
Address Value| 128| 64| 32| 16| 8| 4| 2| 1

Table 8: Device objects

The address assignment is determined by adding the values for each of the switches that are in the ON position. The transmitter comes from the factory with all of the DIP switches, except position 1, in the ON position as shown in Figure 10. The address of the transmitter would be 127 as it would be 64+32+16+8+4+2+1 = 127. Another  example would be if the address desired was 008, the only DIP switch position in the ON position would be position 5 as shown in Figure 11.

NOTICE Though the minimum possible address would be address 0 when all the DIP switch positions were set to OFF, and the maximum possible address would be address 255 when all of the DIP switches were set to ON, but the transmitter only has valid address from 0 to 127. Any address outside of this range will give an error code.

APPENDIX VI: Property Tables
Property Default Value Property Data Type Access

ObjectIdentifier
ObjectName
Object Type
Present Value
Status Flags
Event State
ReliabilityOut Of Service Units| AI1
Velocity FPM ANALOG_INPUT (0)
Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Feet-per-minute (77)| BACnetObjectIdentifier CharacterString BACnetObjectType
Real BACnetStatusFlag
s BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 9: Analog input – Velocity FPM

Property Default Value Property Data Type Access
Object Identifier 607xxx BACnetObjectIdentifier Read/

Write

Object Name| “AVUL Velocity”| CharacterString(32)| Read/

Write

ObjectType| DEVICE(8)| BACnetObjectType| Read
System Status| Operational(0)| BACnetDeviceStatus| Read
Vendor Name| “Dwyer Instruments,

LLC”

| CharacterString| Read
Vendor

Identifier

| 607| Unsigned| Read
Model Name| “AVUL”| CharacterString| Read
Firmware

Revision

| “1.0.14”| CharacterString| Read
Application Software

Version

| “3.1.2.0”| CharacterString| Read
Location| | CharacterString(32)| Read/

Write

Description| “Thermal Anemometer”| CharacterString(32)| Read/

Write

Protocol

Version

| 1| Unsigned| Read
Protocol

Revision

| 12| Unsigned| Read
Protocol Services

Supported

| See PICS| BACnetServicesSupported| Read
Protocol Object Types

Supported

| See Table 7| BACnetObjectTypesSupported| Read
Object List| See Table 7| BACnetArray| Read
Maximum APDU Length

Accepted

| 128| Unsigned| Read
Segmentation

Supported

| NO_SEGMENTATION

(3)

| BACnetSegmentation| Read
APDU Timeout| 0| Unsigned| Read
Number of

APDU Retries

| 0| Unsigned| Read
Max Master| 127| Unsigned| Read/

Write

Max Info

Frames

| 1| Unsigned| Read/

Write

Device Address

Binding

| Empty| BACnetAddressBinding| Read
Database

Revision

| 0| Unsigned| Read
Serial Number

(1000)

| | CharacterString| Read
Sensor Serial

Number (1001)

| | CharacterString| Read
Property| Default Value| Property Data Type| Access
---|---|---|---
Object Identifier ObjectName Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AI2
Velocity MPS ANALOG_INPUT (0)
Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Meters-per-second
(74)| BACnetObjectIdentifier CharacterString BACnetObjectType
Real
BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 11: Analog input – Velocity MPS

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AI3
Temperature F ANALOG_INPUT (0)
Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)Degrees-fahrenheit
(64)| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 12: Analog input – Temperature F

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AI4
Temperature C ANALOG_INPUT (0)
Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Degrees-celsius (206)| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability **** Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
ReadRead/Write Read

Table 13: Analog input – Temperature C

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AV1

Flow CFM ANALOG_VALUE (2)
Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Cubic-feet-per-minute
(84)

| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 14: Analog value – Flow CFM

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AV2
Flow CMH ANALOG_VALUE (2)Current reading
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Cubic-meters-per-hour
(135)| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 15: Analog value – Flow CMH

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AV3
Flow Area SqFt ANALOG_VALUE (2)
1
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Square-feet (1)| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read
Read
Read
Read
Read
Read/Write Read

Table 16: Analog value – Flow area SqFt

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service Units

| AV4
Flow Area SqM ANALOG_VALUE (2)
1
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Square-meters (0)| BACnetObjectIdentifier CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability Boolean BACnetEngineeringUnits| Read
Read
Read Read/Write Read
Read
Read
Read/Write Read

Table 17: Analog value – Flow area SqM

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service

| BV1
Zero
BINARY_VALUE (5)
ACTIVE (1)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnetObjectIdentifier CharacterString
BACnetObjectType
BACnetBinaryPV
BACnetStatusFlags BACnetEventState
BACnetReliability **** Boolean| Read Read Read Read/Write Read Read Read

**** Read/Write

Table 18: Binary value – Zero

Property Default Value Property Data Type Access

Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability

**** Out Of Service

| BV2
Span
BINARY_VALUE (5)
INACTIVE (0)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnetObjectIdentifier CharacterString
BACnetObjectType
BACnetBinaryPV
BACnetStatusFlags BACnetEventStateBACnetReliability Boolean| Read
Read
Read Read/Write Read
Read
Read
Read/Write

Table 19: Binary value – Span

Property Default Value Property Data Type Access

Object Identifier Object Name

**** Object Type Present Value Status Flags Event State Reliability

**** Out Of Service

| BV3
Restore Factory Pressure Values BINARY_VALUE (5)
INACTIVE (0)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnetObjectIdentifier CharacterString

**** BACnetObjectType BACnetBinaryPV
BACnetStatusFlags BACnetEventState
BACnetReliability

**** Boolean

| Read
Read Read Read/Write Read
Read
Read
Read/Write

Table 20: Binary value – Restore factory default values

APPENDIX III: Menu Flow Chart

BUTTON PRESS LEGEND

ZERO= PRESS ZERO BUTTON
SPAN= PRESS SPAN BUTTON
ZERO= PRESS AND HOLD ZERO BUTTON
SPAN= PRESS AND HOLD SPAN BUTTON
ZERO
SPAN= PRESS AND HOLD ZERO AND SPAN BUTTONS

MENU CONVENTIONS —IN HOME POSITION:

ZERO CALIBRATE UNIT TO ZERO PRESSURE.
SPAN CALIBRATE UNIT TO SPAN PRESSURE. DISPLAY IS NOT NECESSARY

IN MENU DISPLAY:

SPAN SEQUENCES TO NEXT MAIN MENU ITEM, AND IF A MENU ITEM IS CHANGED TEMPORARILY SAVES THE SELECTION
ZERO SEQUENCES THROUGH SUB MENU SELECTIONS OR INCREMENTS DIGITS
SPAN SEQUENCE TO NEXT DIGIT. ACTIVE DIGIT WILL BLINK = BLINKING DIGIT.

Averaging Menu

Averaging Menu

Velocity Mode Menu

Velocity Mode Menu

Flow Mode Menu

Flow Mode Menu

Security Menu

Security Menu