YHDC SCT010T Aperture Split Core Current Transformer Owner’s Manual

June 11, 2024
YHDC

SCT010T
Ф10mmAperture Split core current transformer

YHDC SCT010T Aperture Split Core Current Transformer -

Characteristic

  • Safety lock buckle, easy to install
  • Built-in over-voltage protection device (TVS tube)
  • Crimping terminal output
  • Suspended type

Product application

  • Portable instrument
  • Household metering
  • Monitor motor load

Product advantage

  • Small volume,Light weight
  • Low cost
  • High turns,High precision

Installation diagram

Primary threading method(Firing line)

  1. Open the buckle

  2. Open upward

  3. Put in lead wire

  4. Fasten the buckle

Typical technical index:

  • Material of core——Ferrite
  • Working voltage——Phase voltage≤720V
  • Working temperature——-25℃~+60℃
  • Storage temperature——-30℃~+90℃
  • Frequency range——50Hz~1KHz
  • Dielectric strength——Input(bare conductor)/output AC 800V/1min 5mA 50Hz Output/Outer shell AC 3.5KV/1min 5mA 50Hz

Electrical parameters:(The following parameters are typical values and actual values will be subject to product testing)
Max. continuous input current: 120% of rated input

Model| Input
current| Output| Turns ratio| Load
resistance| Accuracy| Linearity| Weight
---|---|---|---|---|---|---|---
SCT010T| 20A| 20mA| 1:1000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 20A| 5mA| 1:4000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 50A| 0.1A| 0.388889| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 50A| 50mA| 1:1000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 50A| 16.6mA| 1:3000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 60A| 20mA| 1:3000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 80A| 80mA| 1:1000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 80A| 40mA| 1:2000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 80A| 26.6mA| 1:3000| 10Ω| 0.5%/1%| 1%| 45g
SCT010T| 10A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g
SCT010T| 20A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g
SCT010T| 30A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g
SCT010T| 50A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g
SCT010T| 60A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g
SCT010T| 80A| 0.333V| –| built-in| 0.5%/1%| 1%| 45g

*Can be customized parameters/lead length/lead specifications according to user requirements.

Wiring schematic diagram:

Built-in sampling resistance Voltage output type Secondary doesn’t allow short circuit

TVS:Transient voltage suppressor Current output type Secondary doesn’t allow open circuit