Appcon Wireless YRS-10CL Wireless Temperature Sensor User Manual
- June 11, 2024
- Appcon Wireless
Table of Contents
YRS-10CL Wireless Temperature Sensor
User Manual Wireless Temperature Sensor YL-104
Version:V1.0
Product Overview
Adopt high-performance low-power single-chip ASR6601, taking into account
sensor data acquisition and wireless data transmission.
Built-in low-power high-precision digital temperature and humidity sensor
chip, measurement and accuracy range:
Temperature: ±1°C (max) @-10 to 85°C, -40 to +125°C
Wireless data transmission uses LoRa and NB-IoT solutions:
LoRa solution (YL-104): Based on Semtech’s low-power long-distance LoRa spread
spectrum wireless data transmission scheme Sx1262, it has a sleep wireless
wake-up function with a signal coverage of 2km.
Built-in 2300mAH rechargeable lithium battery, long battery life, reusable.
The card type is ultra-thin design, small in size and easy to install.
It is widely used in communication equipment room, workshop production line,
drug warehouse, large-scale logistics warehouse, agricultural greenhouse,
greenhouse flower greenhouse, archives, museum, HVAC control and other IoT
application scenarios that require temperature and humidity monitoring and
alarming.
Sensor Specifications
Type of wireless | LoRa solution | NB-IoT solution |
---|---|---|
Frequency | 433MHz, 868MHz, 915MHz | All bands |
Range | 2 km line of sight | NB-IoT network coverage |
Power | Built-in2300mAh rechargeable lithium ba tery (high and low temperature |
battery is optional)
Port| Magnetic socket
Temperature measurement| -20-80°C (conventional lithium battery), -40-80°C
(low temperature lithium battery), -40-85 degrees (lithium battery), ±1°C;
Sleep power consumption| 10uA
Parameter configuration| UART-TTL (Mini-USB connector form) with magnetic
socket.
Sample period| Timing report, the minimum can be set for 1 minute, the longest
is 60 minutes, if not set, it will not be reported.
Alarm threshold| The temperature alann value can be set. When an alarm occurs,
it will be reported three times within 1 minute; if it is not set, it will not
be reported.
size and weight| 104.569.511.3mm, 85g (with lithium battery)
Dimemsion of YL-104.
Structure of the sensor and installation method
When installing the sensor, try to make the antenna perpendicular to the
horizontal plane, and the wireless communication is the best.
Parameter configuration
The company provides parameter setting software for this sensor (LoRa version), wireless parameters such as frequency, period, node ID, network ID, and transmission power.![Appcon Wireless YRS-10CL Wireless Temperature Sensor
- Parameter configuration](https://manuals.plus/wp-content/uploads/2023/05
/Appcon-Wireless-YRS-10CL-Wireless-Temperature-Sensor-Parameter-
configuration.png)After connecting the sensor to the computer through the USB-
TTL data cable (mini-USB connector), the sensor is in the setting state, open
the “Tool for LoRa module V1.0”, click “com”, select the com port number The
COM port, with a baud rate of 115200, No parity. The default baurate of YL-104
is 115200bps, No parity.
In the „basic config‟, There are Frequency, Period, Net ID, Node ID, Work Mode, RF-Factor, RF-Coding, RF-BW and power are necessary for the debug.
Parameter | Description |
---|---|
Frequency | 433MHz, 868MHz, 915MHz |
Protocol Ver | VI 0, V20 |
Node ID | 0-255 |
Net ID | 0-255 |
Output power | Level |
dBm | 19.5-20 |
mA | 110-120 |
Period | 0-60mins, set’O’means the YL-104 is closed. |
Work Mode | Transparent, Central, Slave |
RF-Factor | 5_32, 6_64, 7_128, 8_256, 9_512, 10_1024, 1 1_2048, 12_4096 |
RF-Coding | 4/5, 4/6, 4/7, 4/8 |
RF-BW | 62.5K, 125K, 250K, 500K |
Write | Write the parameter. |
Read | Read the parameter. |
Enter Update | Enter the upgrade mode |
FoTa | Enter the Fota upgrade the YL-104 |
Data Display | Read the temperature data of YL-104 or display the data by |
serials
After the sensor parameters are configured, disconnect the data line to put the sensor into operation.
Display the sensor data by SSCOM
The company provides the RF6610T LoRa data transmission module. Users need to set the RF6610T as Central mode, The Breath of YL-104 should be the same as the net ID, RF-Factor, RF-Coding, RF-BW of RF6610T. The Frequency and the Net ID should be the same for both YL-104 and RF6610T. After the configuration finish, RF6610T can be used as the host computer module to communicate with the sensor and display the sensor data via SSCOM. After finish the configuration, please close the serial port of RF tool.
Users configure Frequency, Net ID, work mode, RF_Factor, RF_Coding and RF_BW
for RF6610T. RF mode should be ’Central’ mode. The frequency, Net ID,
RF_Factor, Recording and RF_BW should be same for both RF6610T and YL-103.
Otherwise YL-103 and RF6610T will not communicate with each other.
Appcon wireless provides USB adapter cable, which can connect the TTL host
computer module to the computer USB interface for data acquisition. The sensor
data can display by SSCOM The computer module has dedicated parameter
configuration software, and the wireless parameters (Frequency, Breath time,
Net ID) need to be set to be consistent with YL-104.
Communication Protocol.
The transmitted data format of YL-103: ID (Net ID(1byte)+ Node ID(1byte)) +
18b20 sensor
Data(LSB+MSB) (2byte) + Bat(1byte)
The output data format of RF6610T: ID (Net ID(1byte)+ Node ID(1byte)) + 18b20
sensor
Data(LSB+MSB)(2bytes) + Bat(1byte) + RSSI(1byte)
When the RSSI value is lower than 7E, the signal is weak.
AppconWireless technology reserves the right to make corrections,
modifications, improvements and other changes to its products and services at
any time and to discontinue any product or service without notice. Customers
are expected to visit websites for getting newest product information before
placing orders. These products are not designed for use in life support
appliances, devices or other products where malfunction of these products
might result in personal injury. Customers using these products in such
applications do so at their own risk and agree to fully indemnify
AppconWireless technology for any damages resulting from improper use
APPCON WIRELESS TECHNOLOGY CO.,LTD
Add: 28#, Longjin road,Xili zone, Nanshan District Shenzhen P.R.C(518043)
TEL: +86-185 0309 2598 FAX: +86-755-83405160
Email: sales@appconwireless.com
Web: http://www.appconwireless.com
References
- Appconwireless,Professional IoT solution,LoRa radio solution,LoRaWAN solution,Radio data module
- Appconwireless,Professional IoT solution,LoRa radio solution,LoRaWAN solution,Radio data module
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>