Honeywell ST 700 Series SmartLine Transmitter User Manual
- June 11, 2024
- Honeywell
Table of Contents
- Honeywell ST 700 Series SmartLine Transmitter
- About This Document
- Telephone and Email Contacts
- Requirements
- Safety Function
- Designing with the HONEYWELL ST 800 & ST 700
- Environmental limits
- Installation with the HONEYWELL ST 800 & ST 700
- Parameter settings
- Operation and Maintenance with the HONEYWELL ST 800 & ST 700
- Calibration procedure
- Remote Parameter Configuration Verification
- Security Guidelines
- Maintenance
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell ST 700 Series SmartLine Transmitter
- The ST 800 & ST 700 SmartLine Transmitter family is a range of pressure transmitters manufactured by Honeywell Process Solutions.
- The product is covered by one or more of the following U.S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending.
- The transmitter is designed with safety features to protect against risks of damage to persons by electrical shock and other hazards, as well as fire and explosion.
- The device has hardware fault tolerance and is capable of carrying out the necessary actions to achieve or maintain a defined safe state for the equipment under its control.
- The product has undergone Failure Modes, Effects, and Diagnostic Analysis (FMEDA) Functional Safety testing to ensure Dangerous Undetected failures are minimized.
ST 800 & ST 700 SmartLine Transmitter Usage Instructions
- Before using the ST 800 & ST 700 SmartLine Transmitter, refer to the safety manual for important information on product safety and proper usage.
- For technical support and contact information, refer to the back page of the manual or visit the appropriate Honeywell Solution Support website.
- Ensure that the transmitter is installed and operated according to the manufacturer’s instructions and specifications.
- Regularly perform proof tests on the device to ensure it is functioning correctly and safely.
- If any faults or issues are detected with the device, contact technical support for assistance.
Copyrights, Notices, and Trademarks
While the information in this document is presented in good faith and believed to be accurate, Honeywell disclaims any implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in the written agreement with and for its customers. In no event is Honeywell liable to anyone for any indirect, special, or consequential damages? The information and specifications in this document are subject to change without notice. Honeywell, SFC, and SmartLine are registered trademarks of Honeywell International Inc. Other brand or product names are trademarks of their respective owners.
About This Document
Release Information
ST 800 & ST 700 SmartLine Transmitter HART® Communications Options Safety
Manual # 34-ST-25-37.
Revision | Date of Change | Details of Change |
---|---|---|
1.0 | September 2012 | New |
2.0 | January 2013 | Updated to include ST 700 |
3.0 | December 2013 | Link to Firmware downloads added, 316 SS |
4.0 | July 2014 | Test terminals for Non-SIL added |
5.0 | March 2016 | Diagnostic response time updated |
6.0 | December 2016 | Added Remote Parameter Configuration Verification section. |
Added spec sheet numbers for new ST 700 models.
7.0| January 2020| Web links updated
8.0| January 2021| Diagnostic response time changed from 14 to 15 minutes PV
update timeout changed from 5 to 7 seconds.
9.0| March 2022| Changes in proof test cover percentage
References
The following list identifies publications that may contain information
relevant to the information in this document.
- ST 800 SmartLine Pressure Transmitter User Manual, Document # 34-ST-25-35
- ST 800 SmartLine Pressure Transmitter HART/DE Option User’s Manual, 34-ST-25-38
- ST 800 FF Transmitter w/ FOUNDATION Fieldbus Option Installation & Device Ref Guide, 34-ST-25-39
- ST 700 SmartLine Pressure Transmitter User Manual, 34-ST-25-44
- ST 700 SmartLine Pressure Transmitter HART/DE Option User’s Manual, 34-ST-25-47
- ST 700 FF Transmitter w/ FOUNDATION Fieldbus Option Installation & Device Ref Guide, 34-ST-25-48
Patent Notice
The Honeywell ST 800 & ST 700 SmartLine Pressure Transmitter family is covered
by one or more of the following U. S. Patents: 5,485,753; 5,811,690;
6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending.
Support and Contact Information
For Europe, Asia Pacific, and North and South America contact details, refer
to the back page of this manual or the appropriate Honeywell Solution Support
website:
- Honeywell Corporate www.process.honeywell.com
- Honeywell Process Solutions www.process.honeywell.com/us/en/pressure-transmitters
Telephone and Email Contacts
Area | Organization | Phone Number |
---|
United States and Canada
| ****
Honeywell Inc.
| 1-800-343-0228 Customer Service
1-800-423-9883 Global Technical Support
Global Technical Support Field Product Sales| ****
Honeywell Process Solutions
| hfs-tac-support@honeywell.com
Terms and Abbreviations
1oo1 | One out of one |
---|---|
Basic Safety | The equipment must be designed and manufactured such that |
it protects against the risk of damage to persons by electrical shock and
other hazards and against resulting fire and explosion. The protection must be
effective under all conditions of the nominal operation and under single fault
condition
DU| Dangerous Undetected failures
FMEDA| Failure Modes, Effects, and Diagnostic Analysis
Functional Safety| The ability of a system to carry out the actions
necessary to achieve or to maintain a defined safe state for the
equipment/machinery/plant/apparatus under the control of the system
GTS| Global Technical Support Center
HART ®| Highway Addressable Remote Transmitter
HFT| Hardware Fault Tolerance
Low demand mode| Mode, where the frequency of demands for operation made
on a safety-related system is no greater than one per year and no greater than
twice the proof test frequency.
PFD AVG| Average Probability of Failure on Demand
Safety| Freedom from unacceptable risk of harm
Safety Assessment| The investigation is to arrive at a judgment – based
on evidence – of the safety achieved by safety-related systems. Further
definitions of terms used for safety techniques and measures and the
description of safety-related systems are given in IEC 61508-4.
SFF| The safe Failure Fraction is the fraction of the overall failure
rate of a device that results in either a safe fault or a diagnosed unsafe
fault.
SIF| A safety Instrumented Function is a set of equipment intended to
reduce the risk due to a specific hazard (a safety loop).
SIL| Safety Integrity Level, discrete level (one out of a possible four)
for specifying the safety integrity requirements of the safety functions to be
allocated to the E/E/PE safety-related systems where Safety Integrity Level 4
has the highest level of safety integrity and Safety Integrity Level 1 has the
lowest.
SIS| Safety Instrumented System – Implementation of one or more Safety
Instrumented Functions. A SIS is composed of any combination of sensor(s),
logic solver(s), and final element(s).
Requirements
Requirements for use of the manual
This section is intended for users who have our ST 800 & ST 700 Smart
Transmitter with the HART® Communication option with SIL. Any other option is
not specifically covered by this manual. IEC 61508 Ed. 2.0 compliant
hardware/software revisions for the ST 800 & ST 700 can be found in the Exida
and TÜV Certification Reports.
This document can be downloaded using the following link:
https://honeywell/public/Support/vault/support/Public/Documents/SmartLineHARTPressureFirmwareRevisions.zip.
Safety Function
Primary Safety Functions
The HONEYWELL ST 800 & ST 700 measure the (pressure gauge, differential,
absolute) of a process and reports the measurement with a safety accuracy of
2%.
Secondary Safety Functions
The HONEYWELL ST 800 & ST 700 performs automatic diagnostics to detect
internal failures and reports these failures via out-of-band signals on the 4
– 20 mA output. The transmitter needs a power cycle for recovery from this
condition.
Systematic Integrity: SIL 3 Capable
- SIL 3 Capability:
- The product has met manufacturer design process requirements of Safety Integrity Level (SIL) 3. These are intended to achieve sufficient integrity against systematic errors of design by the manufacturer. A Safety Instrumented Function (SIF) designed with this product must not be used at a SIL level higher than the statement without “prior use” justification by end user or diverse technology redundancy in the design. This is a Type B device.
Designing with the HONEYWELL ST 800 & ST 700
Diagnostic Response Time
The HONEYWELL ST 800 & ST 700 will report an internal failure within 15
minutes of fault occurrence (worst case). The transmitter will be put to
burnout current if.
- PV is not updated in 7 seconds
- The current is not as expected in 40 seconds
- An Electronics fault is found in 15 minutes
The transmitter needs a power cycle for recovery from this condition.
Logic Solver Inputs
The logic solver must be configured so that the engineering range in the
transmitter matches the expected range of the logic solver.
To take advantage of the internal diagnostics in the ST 800 & ST 700, the
logic solver must be configured to annunciate an out-of-band current reading
(greater than 20.8 mA. or less than 3.8 mA.) in standard configuration or
(greater than 20.5 mA. or less than 3.8 mA.) with Namur configuration as a
diagnostic fault. The logic solver configuration must consider the slew time
of the current signal and ensure that filtering is used to prevent a false
diagnostic failure annunciation.
Reliability data and lifetime limit
- A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is available from HONEYWELL. This report details all failure rates and failure modes, common cause factors for applications with redundant devices, and the expected lifetime of the HONEYWELL ST 800 & ST 700.
- The HONEYWELL ST 800 & ST 700 is intended for low-demand mode applications up to SIL 2 for use in a simplex (1oo1) configuration, depending on the PFDAVG calculation of the entire Safety Instrumented Function. ST 800 & ST 700 is classified as type B device according to IEC61508, having a hardware fault tolerance of 0.
- The development process of the HONEYWELL ST 800 & ST 700 is certified up to SIL3, allowing redundant use of the transmitter up to this Safety Integrity Level, depending on the PFDAVG calculation of the entire Safety Instrumented Function.
- When using the HONEYWELL ST 800 & ST 700 in a redundant configuration, a common cause factor should be included in reliability calculations. For reliability calculation details, useful lifetime, and SFF, see the FMEDA report.
- The reliability data listed in the FMEDA report is only valid for the useful lifetime of the HONEYWELL ST 800 & ST 700. The failure rates of the HONEYWELL ST 800 & ST 700 may increase sometime after this period. Reliability calculations based on the data listed in the FMEDA report for mission times beyond the lifetime may yield results that are too optimistic, i.e. the calculated Safety Integrity Level will not be achieved.
Environmental limits
The environmental limits of the HONEYWELL ST 800 & ST 700 are specified in the customer spec sheets as given in the below table.
Model | Specification |
---|---|
STF800 | 34-ST-03-82 |
STG800 | 34-ST-03-83 |
STA800 | 34-ST-03-85 |
STF800 | 34-ST-03-87 |
STR800 | 34-ST-03-88 |
STA700 Standard | 34-ST-03-100 |
STD700 Standard | 34-ST-03-101 |
STG700 Standard | 34-ST-03-102 |
STF700 Standard | 34-ST-03-103 |
STR700 Standard | 34-ST-03-104 |
STG73P Standard | 34-ST-03-108 |
STA700 Basic | 34-ST-03-120 |
STD700 Basic | 34-ST-03-121 |
STG700 Basic | 34-ST-03-122 |
STF700 Basic | 34-ST-03-123 |
STR700 Basic | 34-ST-03-124 |
STG73SP Basic | 34-ST-03-128 |
Refer to the ST 700 Series Pressure Transmitter User’s manual, 34-ST-25-44 for information on Standard and Basic transmitter types.
Application limits
The application limits of the HONEYWELL ST 800 & ST 700 are specified in the
User Manual. If the transmitter is used outside of the application limits the
reliability data provided becomes invalid.
Installation with the HONEYWELL ST 800 & ST 700
A person with knowledge of safety operations will be required to do the installation and operation. No special installation is required in addition to the standard installation practices outlined in the ST 800 & ST 700 Smart Transmitter User Manual. However please note that when the device is in safety operation the optional write protect must be set in hardware and software both so that the device is write protected and HART® devices must be disconnected. This can be done using the write protect jumper. See ST 800 & ST 700 Smart Transmitter User Manual for details concerning the write-protect jumper. The software write protect is also available in the device with a password to disable the software write protect. The default password is “0000”. It can be enabled/disabled through the HART host. IEC 61508 Ed. 2.0 compliant hardware/software revisions for the ST 800 & ST 700 can be found in the Exida and TÜV Certification Reports. This document can be downloaded using the following link:
The Test (- +) terminals may be used during the installation of the transmitter as a gross current loop check without disconnecting the current loop wiring. To use this feature, place a current meter with low resistance (~10 ohms) across the TEST (- +) terminals. As shown in Figure 4-1.
NOTE: During SIL operation, the TEST (- +) terminals should not be used to monitor the loop current.
Parameter settings
The following parameters need to be set in order to maintain the designed safety integrity:
mA Fault action (Upscale/Downscale)| The transmitter is shipped with a
default failsafe direction of upscale (21.0 mA). This is acceptable for all
high-trip applications. For low-trip applications, the fail-safe direction is
downscale (3.6 mA.). A jumper on the transmitter may be changed to accomplish
this action, see the User Manual.
---|---
Engineering Range| All engineering range parameters must be entered
to match the trip points in the safety logic solver. These parameters must be
verified during the installation and commissioning to ensure that the correct
parameters are set in the transmitter. Engineering range parameters can be
verified by reading these parameters from the local display or by checking the
actual calibration of the transmitter.
Operation and Maintenance with the HONEYWELL ST 800 & ST 700
Proof test
The objective of proof testing is to detect failures within the HONEYWELL ST 800 & ST 700 that are not detected by the automatic diagnostics of the transmitter. Of main concern are undetected failures that prevent the safety instrumented function from performing its intended function. The frequency of proof testing, or the proof test interval, is to be determined in reliability calculations for the safety instrumented functions for which the HONEYWELL ST 800 & ST 700 is applied. The Exida exSILentia® tool is recommended for these calculations. The proof tests must be performed more frequently than, or as frequently as specified in the calculation in order to maintain the required safety integrity of the safety instrumented function. The following proof test is recommended. It consists of a simple HART® driven min to max output test. The results of the proof test need to be documented and this documentation should be part of a plant safety management system. Any failures that are detected and that compromise functional safety should be reported to the Global Technical Support Center (GTS). See ST 800 & ST 700 Smart Transmitter User Manual for more details.
Step | Action |
---|---|
1 | Bypass the safety PLC or take other appropriate action to avoid a false |
trip, following Management of Change procedures.
2| Send a HART® command to the transmitter to go to the high alarm current
output and verify that the analog current reaches that value.
This procedure tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible failures.
3| Send a HART® command to the transmitter to go to the low alarm current
output and verify that the analog current reaches that value. This test checks
for possible quiescent current-related failures.
4| Use the HART® communicator to view detailed critical and non-critical
device status to ensure no alarms or warnings are present in the transmitter.
5| Verify all safety-critical configuration parameters.
6| The WP jumper state should be checked to see if it is in WP mode first, and
then changed to Enable configuration to ensure a change is detected by the
device while configuring, and then moved back to WP after the configuration is
complete. Then it should be verified again.
7| Calibrate the device as per the calibration procedure given below.
8| Restore the loop to full operation.
9| Remove the bypass from the safety PLC or otherwise restore normal
operation.
This test will detect approximately 74% of possible DU failures in the transmitter (Proof Test Coverage). An alternative proof test consisting of proof test 1 with actual three-point pressure calibration plus verification of the temperature measurement will detect approximately 99% of possible DU failures. The person(s) performing the proof test of the HONEYWELL ST 800 & ST 700 should be trained in SIS operations, including bypass procedures, transmitter maintenance, and company Management of Change procedures. The tools required are handheld communicators.
Calibration procedure
The transmitter should be taken out of service. The source for the input pressure must be very precise, and certified for correct operation.
Step | Action |
---|---|
1 | Connect the HART host and establish the communications. |
2 | Go to Online > Device Setup > Calibration > Calibration Methods menu. |
3 | Go to “D/A Trim” |
4 | The message “Warning loop should be removed from automatic control” will |
appear. Press “Ok”.
5| The message “Connect reference meter” will appear. Connect the reference
meter and press “Ok”.
6| The message “Setting fld device output to 4mA” will appear. Press “Ok”. The
message “Enter meter value (4,000mA)” will appear with a textbox to enter the
actual value observed on the meter. Enter the actual value and press “Enter”.
7| The message “Fld dev output 4,000mA equal to reference meter?” will appear
with Yes/No selection. Select “Yes” and “Enter”.
8| The message “Setting field device output to 20mA” will appear. Press “Ok”.
9| The message “Fld dev output 20,000mA equal to reference meter?” will appear
with Yes/No selection. Select “Yes” and “Enter”.
10| The message “Returning fld dev to original output” will appear. Press
“Ok”.
11| Now Double click “URV Correct” method
12| The message “WARN-Loop should be removed from automatic control” will
appear. Press “Ok”.
13| . The message “Please enter calibration date” will appear. Enter the
current date and press “Ok”.
14| The message “Please enter current calibration time in 24 hr clock format
(hour field)” will appear. Enter the current time hour and press “Ok”.
15| The message “Please enter current calibration time (min field)” will
appear. Enter the current time minutes and press “Ok”.
16| The message “Apply URV pressure” will appear.
17| Adjust the PV input to the required URV value. Press “Ok”.
18| The message “Press ok when pressure is stable” will appear. Press “Ok”
19| The correct URV operation will happen
20| The message “Loop may be returned to automatic control” will appear. Press
“Ok”.
21| Follow the same procedure for “Correct LRV” (replace URV in the above
procedure with LRV) and the “Correct LRV” operation will get executed.
Remote Parameter Configuration Verification
- When configuring the HONEYWELL ST 800 or ST 700 through a remote host, it is recommended that parameters that affect the 4-20ma analog output be verified using an alternate utility, before using the transmitter in an SIS. This helps to ensure that the parameters that are entered remotely by the host are not inadvertently changed from the user’s intended values.
- The procedure can consist of listing the parameters and their values entered in the host application. Then, using an alternative application, the same parameters are read back and noted in the same form. The form is then signed, dated, and filed for future reference. See Table 1 – Example Verification Form for an example of this form.
Note that using the same host application to verify the remotely entered values will not provide as much assurance as using an alternate application.
Table 1 – Example Verification Form
Security Guidelines
- Ensure the device has Hardware/ Software write protection enabled the device to prevent any unauthorized configuration changes.
- Physical access to the device: A malicious operation on the transmitters will result in system shutdown, starting the system expectedly or impacting process control. For maximum security, the transmitter device must be protected against unauthorized physical access.
- Be aware of any unauthorized access of a secondary master alarm present in Distributed Control System (DCS). If this is because of a secondary handheld device being connected then this can be ignored.
- Enable the Tamper alarm and monitor the Tamper Counter value for unintended changes.
How to report a security vulnerability
-
For the purpose of submission, a security vulnerability is defined as a software defect or weakness that can be exploited to reduce the operational or security capabilities of the software or device.
-
Honeywell investigates all reports of security vulnerabilities affecting Honeywell products and services.
-
To report potential security vulnerabilities against any Honeywell product, please follow the instructions at:
https://honeywell.com/pages/vulnerabilityreporting.aspx
Submit the requested information to Honeywell using one of the following methods: -
• Send an email to security@honeywell.com. or
• Contact your local Honeywell Process Solutions Customer Contact Centre (CCC) or Honeywell Technical Assistance Centre (TAC) listed in the “Support and Contact information” section of this document.
Maintenance
Repair and replacement
Any failures that are detected and that compromise functional safety should be
reported to the Global Technical Support Center (GTS). When replacing the
HONEYWELL ST 800 & ST 700 the procedures in the installation manual should be
followed.
Firmware update
The user will not be required to perform any firmware updates. If the user has
selected the firmware upgrade option, it can be done by a Honeywell service
representative.
Sales and Service
For application assistance, current specifications, pricing, or the name of
the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
- Honeywell Process Solutions, (TAC) hfs-tac- support@honeywell.com
Australia
- Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
- China – PRC – Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore
- Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033
South Korea
- Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015
EMEA
- Honeywell Process Solutions, Phone: + 80012026455 or +44 (0)1344 656000
- Email: (Sales) FP-Sales-Apps@Honeywell.com or
- (TAC) hfs-tac-support@honeywell.com
AMERICA’S
- Honeywell Process Solutions, Phone: (TAC) 1-800-423-9883 or 215/641-3610
- (Sales) 1-800-343-0228
- Email: (Sales) FP-Sales-Apps@Honeywell.com
For more information
To learn more about SmartLine Transmitters, visit www.process.honeywell.com
Or contact your Honeywell Account Manager
Process Solutions
- Honeywell
- 2101 City West Blvd
- Houston, TX 77042
- Honeywell Control Systems Ltd
- Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
- Shanghai City Centre, 100 Jungi Road Shanghai, China 20061 www.process.honeywell.com
34-ST-25-37, Rev.9 March 2022 ©2022 Honeywell International Inc.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>