SensoMAG S30 – Installation Instruction
Conventional fire alarm optical-smoke detector

ATTENTION: Read carefully this installation Instructions before installing the device!

The detector SensoMAG S30 is compatible with any conventional Fire Panel with fire alarm threshold between 10mAand 15mA(between 10mA and 30mAwith B24RD fire base).

The SensoMAG S30 can be used with 4 base types:

❶ B12L/U – Base with relay output (not covered by EN 54-7);

❷ B24 – Standard base, low profile; B24-HP – Standard base, high profile;

❸ B24D – Standard base with Schottky diode;

❹ B24RD – Standard base with Schottky diode and increased alarm state current.

  1. Choose the proper place for installation of the fire detector. Refer to the given installation instructions. Note: Do not install the detector near sources of steam, condensation or smoke, e.g. from cigarettes.

  2. If you want to “lock” the detector to the base remove the little “tooth” (with the triangle shape) and break the plastic key off the base. Keep the plastic key in safe place to be able to open the detector later.

  3. Mount the fire base on the ceiling of the protected premises using fixings according the mounting surface.

  4. Connect the detector base to the fire panel using the wiring diagram.
    ATTENTION: Disconnect the line power before installing the detector!

  5. Insert the detector into the base and rotate clockwise until it drops into place. Continue to rotate the detector until it locks to the base – a click is heard.

  6. If the detector has been locked to the base, when opening it for a scheduled maintenance service and cleaning you have to use the plastic key. Lightly press with the plastic key into the base opening and at the same time rotate the detector head counter-clockwise.
    ATTENTION: In case of removing the detector’s PCB for service maintenance, when mounting it back, find the colored dot sticker on the PCB and align it to the mark on the plastic body (visible from the outside). The hole next to the colored dot have to align with the pin on the plastic body. Gently press downwards to fix the PCB in place.

  7. Test the detector for proper operation and LED indication.

Figure 1-3

WIRING DIAGRAM

Wiring Diagram

TEST AND MAINTENANCE

  1. Apply power to the detector.
  2. Wait for 30 sec.
  3. Еxert influence on the fire detector by smoke generator ( Aerosol Dispenser ) or another device with aerosol simulator of smoke. Within 8 sec the fire detector will enter in fire condition. Both LEDs will light up.
  4. Power off the detector for 2 sec minimum. After resetting the detector will enter in duty mode and the LEDs will light off.

The service maintenance periods for the detector should be executed as follows:

  1. Inspection for visible physical damage – weekly.
  2. Operational test in real conditions – monthly.
  3. Check and clean dust contamination – six months.
  4. Check and clean base and head contacts and connections – annually.

TECHNICAL SPECIFICATIONS

Operating Voltage Range: 9 – 30 V DC (Nom. 12/24VDC)
Average current consumption in quiescent state: < 50µA
Alarm state current:

  • with base type B24, B24-HP and B24D: 20 mA / 12÷30V
  • with base type B24RD: 33 mA / 12V; 49mA/24V; 57mA/30V
  • with base type B12L/U: 18 mA / 9V; 29mA/12V; 32mA/15V

Output in alarm state at terminal RI (Towards terminals +IN /+OUT): 20mA (max)/ -3.3V
Degree of protection: IP30
Wire Gauge for terminals: 0.4mm2 ÷ 2.0mm2
Operational temperature range: -10°C ÷ +60°C
Relative humidity resistance: (93 ± 3)% @ 40°C
Dimensions (incl. base): ø102mm, h 42mm* / ø103mm, h 56mm*
Weight (incl. base): 160g
/ 170g**

* B12L/U, B24, B24D, B24RD B24-HP**

This manual is subject to change without notice!