QUBINO Smart Plug 16A ZMNHYD1 Manual

June 10, 2024
QUBINO

QUBINO

Smart Plug 16A

SKU: ZMNHYD1

Quickstart

This is a
secure
On/Off Power Switch
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
AUTOMATICALLY ADDING THE DEVICE TO A Z-WAVE NETWORK (AUTO INCLUSION)1. Enable add/remove mode on your Z-Wave gateway (hub)2. Automatic selection of secure/unsecure inclusion3. The device can be automatically added to a Z-Wave network during the first 2 minutes4. Connect the device to the power supply5. Auto-inclusion will be initiated within 5 seconds of connection to the power supply and the device will automatically enrol in your network (when the device is excluded and connected to the power supply it automatically enters the INCLUSION MODE state.)

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Smart Plug 16A controls on/off function for the connected device. It also measures power consumption of the connected device according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates energy and power from the measured signals.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

FACTORY RESET The reset is only possible the first minute after the power on Press and hold the service button S more than 6 seconds The device will be removed from your network and the led will start blinking. The device is now in its factory default state. When the S button is held more than 6 seconds after the first minute is passed, the relay should not react!By resetting the device, all custom parameters previously set on the device will return to their default values, and the owner ID will be deleted. Use this reset procedure only when the main gateway (hub) is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

AUTOMATICALLY ADDING THE DEVICE TO A Z-WAVE NETWORK (AUTO INCLUSION)1. Enable add/remove mode on your Z-Wave gateway (hub)2. Automatic selection of secure/unsecure inclusion3. The device can be automatically added to a Z-Wave network during the first 2 minutes4. Connect the device to the power supply5. Auto-inclusion will be initiated within 5 seconds of connection to the power supply and the device will automatically enrol in your network (when the device is excluded and connected to the power supply it automatically enters the INCLUSION MODE state.)

Exclusion

REMOVAL FROM A Z-WAVE NETWORK (Z-WAVE EXCLUSION)1. Connect the device to the power supply2. Make sure the device is within direct range of your Z-Wave gateway (hub) or use a hand-held Z-Wave remote to perform exclusion3. Enable add/remove mode on your Z-Wave gateway (hub)4. Press and hold the Service button S from 2 to 6 seconds (with holding the S button for the interval between 2 and 6 seconds you put the device in EXCLUSION MODE)5. The device will be removed from your network, but any custom configuration parameters will not be erased

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| Lifeline – Supports the following command classes: Device Reset Locally: triggered upon request Meter Report: triggered according to Configuration parameters 40 and 42 Notification Report: triggered on overload/overcurrent or according to Configuration parameters 70, 71 and 72 Switch Binary Report: triggered upon request or according to Configuration parameters 11 and 12
---|---|---
2| 5| Plug Status – Supports the following command classes: Basic set: triggered at change of relay state
3| 5| Plug Threshold – Supports the following command classes: Basic set: triggered at change of active power in combination with Configuration parameters 50, 51 and 52

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 11: Parameter no. 11 – Turn Smart plug 16A Off Automatically

with Timer

Parameter no. 11 – Turn Smart plug 16A Off Automatically with Timer If Smart plug 16A is ON, you can schedule it to turn OFF automatically after a period defined in this parameter. The timer is reset to zero each time the device receives an ON command, either remotely (from the gateway (hub) or associated device) or locally from the switch.Values (size is 2 byte dec):default value 00 – Auto OFF Disabled 1 – 32535 = 1 – 32535 seconds. Auto OFF timer enabled for a given number of seconds.
Size: 2 Byte, Default Value: 0

SettingDescription

0 Auto OFF Disabled
1 – 32535 1 – 32535 seconds. Auto OFF timer enabled for a given number of

seconds.

Parameter 12: Parameter no. 12 – Turn Smart plug 16A On Automatically

with Timer

If Smart plug 16A is OFF, you can schedule it to turn ON automatically after a period of time defined in this parameter. The timer is reset to zero each time the device receives an OFF command, either remotely (from the gateway (hub) or associated device) or locally from the switch.Values (size is 2 byte dec):default value 00 – Auto ON Disabled 1 – 32535 = 1 – 32535 seconds. Auto ON timer enabled- for a given amount of seconds.
Size: 2 Byte, Default Value: 0

SettingDescription

0 Auto ON Disabled
1 – 32535 1 – 32535 seconds. Auto ON timer enabled- for a given amount of

seconds.

Parameter 30: Parameter no. 30 – Restore on/off status for Smart plug 16A

after power failure

This parameter determines if on/off status is saved and restored for the Smart plug 16A after power failure.Values (size is 1 byte dec):default value 00 – Device saves last on/off status and restores it after a power failure.1 – Device does not save on/off status and does not restore it after a power failure, it remains off.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Device saves last on/off status and restores it after a power failure.
1 – 0 Device does not save on/off status and does not restore it after a

power failure, it remains off.

Parameter 40: Parameter no. 40Watt Power Consumption Reporting Threshold

for Smart plug 16A

Choose by how much power consumption needs to increase or decrease to be reported. Values correspond to percentages, so if 20 is set (by default), the device will report any power consumption changes of 20% or more compared to the last reading. Values (size is 1 byte dec):default value 20 0 – Power consumption reporting disabled 1 – 100 = 1% – 100% Power consumption reporting enabled. New value is reported only when Wattage in real time changes by more than the percentage value set in this parameter compared to the previous Wattage reading, starting at 1% (the lowest value possible).Power consumption needs to increase or decrease by at least 1 Watt to be reported, REGARDLESS of percentage set in this parameter.NOTE: When reporting Watts, module will automatically report also [V] (Voltage) and [A] (Amperes)
Size: 1 Byte, Default Value: 20

SettingDescription

0 Power consumption reporting disabled
1 – 100 1% – 100% Power consumption reporting enabled. New value is reported

only when Wattage in real time changes by more than the percentage value set in this parameter compared to the previous Wattage reading, starting at 1% (the lowest value possible).

Parameter 42: Parameter no. 42Watt Power Consumption Reporting Time

Threshold for Smart plug 16A Load

Set value refers to the time interval with which power consumption in Watts is reported (3032535 seconds).Values (size is 2 byte dec):default value 00 – Power consumption reporting on time interval disabled30 – 32535 = 30 – 32535 seconds. Power consumption reporting enabled. Report is sent according to time interval (value) set here. The device is reporting the following values (if there was a change): W, V and A.NOTE: The energy consumption (kWh) is reported regardless of the values, set in the parameters 40 and 42. The energy consumption will be reported, when it increases for at least 0,1 kWh.
Size: 2 Byte, Default Value: 0

SettingDescription

0 Power consumption reporting on time interval disabled
30 – 32535 30 – 32535 seconds. Power consumption reporting enabled. Report is

sent according to time interval (value) set here.

Parameter 50: Parameter no. 50Down value

Lower power threshold used in parameter no. 52. Values (size is 2 byte dec):default value 30 = 30 W04000 = 0W4000 W Down value cannot be higher or equal to the value specified in parameter no. 51. If the set value is higher or equal to the value in parameter 51, the set command is ignored.NOTE: if parameter no. 50 value is 100W, if measured power is lower than 100W, the association is sent.Power threshold step is 1W
Size: 2 Byte, Default Value: 30

SettingDescription

0 – 4000 0W4000 W power threshold

Parameter 51: Parameter no. 51Up value

Upper power threshold used in parameter no. 52Values (size is 2 byte dec):default value 50 = 50 W04000 = 0 W4000WUp value cannot be lower or equal to the value specified in the parameter no. 50. If the set value is lower or equal to the value in parameter 50, the set command is ignored.NOTE: If parameter no. 51 value is 200W. If measured power is higher than 200W the association is sent.Power threshold step is 1W.
Size: 2 Byte, Default Value: 50

SettingDescription

0 – 4000 0 W4000 W power threshold

Parameter 52: Parameter no. 52 – Action in case of exceeding defined

power values (parameters 50 and 51)

Parameter defines the way 3rd association group devices are controlled, depending on the current power loadValues (size is 1 byte dec):default value 60function inactive1turn the associated devices on, once the power drops below Down value (parameter no. 50)2turn the associated devices off, once the power drops below Down value (parameter no. 50)3turn the associated devices on, once the power rises above Up value (parameter no. 51)4turn the associated devices off, once the power rises above Up value (parameter no. 51)51 and 4 combined. Turn the associated devices on, once the power drops below Down value (parameter no. 50). Turn the associated devices off, once the power rises above Up value (parameter no. 51).62 and 3 combined. Turn the associated devices off, once the power drops below Down value (parameter 50). Turn the associated devices on, once the power rises above Up value (parameter no. 51).
Size: 1 Byte, Default Value: 6

SettingDescription

0 function inactive
1 – 0 turn the associated devices on, once the power drops below Down value

(parameter no. 50)
2 – 0| turn the associated devices off, once the power drops below Down value (parameter no. 50)
3 – 0| turn the associated devices on, once the power rises above Up value (parameter no. 51)
4 – 0| turn the associated devices off, once the power rises above Up value (parameter no. 51)
5 – 0| 1 and 4 combined. Turn the associated devices on, once the power drops below Down value (parameter no. 50). Turn the associated devices off, once the power rises above Up value (parameter no. 51).
6 – 0| 2 and 3 combined. Turn the associated devices off, once the power drops below Down value (parameter 50). Turn the associated devices on, once the power rises above Up value (parameter no. 51).

Parameter 70: Parameter no. 70 – Overload safety switch

_The function allows for turning off the controlled device in case of exceeding the defined power for more than 3 seconds. Controlled device can be turned back on by S-button or sending a control frame. By default this function is inactive. Values (size is 2 byte dec):default value 014000 = 1 W4000W0 = function not activeNOTE: This functionality is not an overload safety protection, please check installation note for details.In case of overload the following message will be send towards the controller:COMMAND_CLASS_NOTIFICATIONV5The Alarm V1 type field set to 0x00Notification Type 0x08 and 0x08 (Overload detected)NOTE: Regardless of the value set in this parameter the overcurrent protection is always active and can not be disabled.
Size: 2 Byte, Default Value: 0

SettingDescription

1 – 4000 1 W4000W
0 function not active

Parameter 71: Parameter no. 71Power threshold

_This functions allows setting the power threshold for triggering the Program started notification. When the threshold will be reached the notification will let the user know that the device connected to the smart plug started working.Values (size is 2 byte dec):default value 014000 = 1 W4000W0 = function not activeWhen the threshold is reached the following message will be send towards the controller:COMMAND_CLASS_NOTIFICATIONV5The Alarm V1 type field set to 0x00Notification Type 0x0C and 0x01 (Program started)
Size: 2 Byte, Default Value: 0

SettingDescription

0 function not active
1 – 4000 1 W4000W

Parameter 72: Parameter no. 72Time interval

_This function allows setting the time interval for triggering the Program completed notification. When the active power will fall below the power threshold set in parameter 71, the time interval will start and when it will expire the notification will let the user know that the device connected to the smart plug finished working. The time interval is useful for the devices that have pause intervals during operations. Values (size is 1 byte dec):default value 10125 = 0125 minutes0 = immediate sending of notification when active power drops bellow threshold set in parameter 71When the the time interval expires the following message will be send towards the controller:COMMAND_CLASS_NOTIFICATIONV5The Alarm V1 type field set to 0x00Notification Type 0x0C and 0x03 (Program completed)
Size: 1 Byte, Default Value: 1

SettingDescription

0| immediate sending of notification when active power drops bellow threshold set in parameter 71
---|---
0 – 125| 0125 minutes

Parameter 73: Parameter no. 73Turn Smart Plug OFF

This function allows turning the Smart Plug output to OFF once the time interval is expired and the Program completed notification is sent to the controller. Values (size is 1 byte dec):default value 00function disabled1turn OFF relay once the notification Program completed is sent
Size: 1 Byte, Default Value: 1

SettingDescription

0 function disabled
1 – 0 turn OFF relay once the notification Program completed is sent

Parameter 74: Parameter no. 74Enable/disable LED

This function allows enabling or disabling the Smart Plug LED. In case the user doesnt want the LED indicator he can turn it OFF with this parameter.NOTE: if an overload or overcurrent occurs the red LED will still turn ON regardless of the value set in this parameter.Values (size is 1 byte dec):default value 10LED is disabled1LED is enabled
Size: 1 Byte, Default Value: 1

SettingDescription

0 LED is disabled
1 – 0 LED is enabled

Technical Data

Hardware Platform ZM5101
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 2 FW: 3.00
Z-Wave Version 6.71.03
Certification ID ZC10-18116325
Z-Wave Product Id 0x0159.0x0002.0x0054
Firmware Updatable Updatable by Consumer via Internet
Supported Notification Types Power Management
IP (Ingress Protection) Rated ok
Supported Meter Type Electric Energy
Color White
Outdoor Use ok
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info V2
  • Association V2
  • Basic V2
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Meter V4
  • Notification V5
  • Powerlevel
  • Security
  • Security 2
  • Supervision
  • Switch Binary V2
  • Transport Service V2
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals