PENTAIR FG-2200 and FG-2200C Classic Battery Backup Systems Owner’s Manual

June 10, 2024
Pentair

PENTAIR FG-2200 and FG-2200C Classic Battery Backup Systems

Product Information: Battery Backup System

The Battery Backup System (FG-2200) is a backup sump pump designed for residential applications. It is not intended to be used as a primary sump pump. The system includes a pump, battery charger, and battery box. The pump is permanently lubricated at the factory and can only pump clear water. The battery acid is corrosive, and caution should be taken when handling it. The system should be installed following local and/or national plumbing and electrical codes. A ground fault circuit interrupter (GFCI) is recommended for use on any electrical appliance submerged in water. To avoid flooding, the pump should not be run dry.

Important Safety Instructions

It is important to follow all safety instructions during installation, operation, and maintenance of the product to avoid potential personal injury or property damage. The safety alert symbol is used throughout the manual to indicate potential hazards.
The following signal words are used:

  • Danger: indicates a hazard which, if not avoided, will result in death or serious injury.
  • Warning: indicates a hazard which, if not avoided, can result in death or serious injury.
  • Caution: indicates a hazard which, if not avoided, can or may result in minor or moderate injury.
  • Notice: addresses practices not related to personal injury.

The safety instructions include:

  • Read and follow all safety instructions in the manual and on the pump.
  • Keep safety labels in good condition and replace missing or damaged safety labels.
  • Avoid risk of serious bodily injury due to electrical shock or burns and property damage due to flooding by reading the safety instructions carefully before installing the pump.
  • Wear eye and head protection when working with battery acid and connect and disconnect DC output terminals only after removing the charger from the AC outlet.
  • Do not plug in or unplug battery charger while standing on a wet floor or in water, and be sure one hand is free when plugging in or unplugging charger.
  • Disconnect power to basement before walking on floor if basement floor is wet.
  • Do not lift pump by electrical cord as it can damage the cord.
  • Lift pump only by the discharge pipe, lifting ring, or handle on the pump.
  • Keep battery charger and battery box off of the floor and in a dry, cool, well-ventilated area.
  • If a Carbon Monoxide (CO) sensor is installed, it must be at least 15 feet away from battery charger to avoid nuisance CO alarms. Refer to your CO detector’s installation guidelines for more information.
  • Keep sparks and flame (pilot light) away from battery to avoid danger of fire or explosion.

Product Usage Instructions

The Battery Backup System is designed to be used as a backup sump pump in a residential application. It should not be used as a primary sump pump. Follow these instructions for proper usage:

  1. Install the system following local and/or national plumbing and electrical codes. A ground fault circuit interrupter (GFCI) is recommended for use on any electrical appliance submerged in water.
  2. Keep the battery charger and battery box off of the floor and in a dry, cool, well-ventilated area.
  3. Read the safety instructions carefully before installing the pump.
  4. Wear eye and head protection when working with battery acid and connect and disconnect DC output terminals only after removing the charger from the AC outlet.
  5. Do not lift pump by electrical cord as it can damage the cord. Lift pump only by the discharge pipe, lifting ring, or handle on the pump.
  6. Make sure one hand is free when plugging in or unplugging charger and do not plug in or unplug battery charger while standing on a wet floor or in water.
  7. If a Carbon Monoxide (CO) sensor is installed, it must be at least 15 feet away from battery charger to avoid nuisance CO alarms. Refer to your CO detector’s installation guidelines for more information.
  8. Keep sparks and flame (pilot light) away from battery to avoid danger of fire or explosion.
  9. The pump is permanently lubricated at the factory and can only pump clear water. Do not try to lubricate it.
  10. To avoid flooding, do not run pump dry.

Safety

Important Safety Instructions
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation, operation, and maintenance of the product.
This is the safety alert symbol. When you see this symbol on your pump or in this manual, look for one of the following signal words and be alert to the potential for personal injury!
DANGER indicates a hazard which, if not avoided, will result in death or serious injury.
WARNING indicates a hazard which, if not avoided, can result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, can or may result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Carefully read and follow all safety instructions in this manual and on pump.
Keep safety labels in good condition. Replace missing or damaged safety labels.
To avoid risk of serious bodily injury due to electrical shock or burns and property damage due to flooding, read the safety instructions carefully before installing pump.
WARNING Battery acid is corrosive. Do not spill on skin, clothing, or battery charger. Wear eye and head protection when working with battery. Connect and disconnect DC output terminals only after removing the charger from the AC outlet. Never allow the DC terminals to touch each other.
WARNING Hazardous Voltage. Can cause severe or fatal electrical shock. Do not plug in or unplug battery charger while standing on a wet floor or in water. Be sure one hand is free when plugging in or unplugging charger. If basement floor is wet, disconnect power to basement before walking on floor.
CAUTION Risk of flooding. Do not run pump dry. To do so will damage seals and can cause leaking and property damage.
Follow local and/or national plumbing and electrical codes when installing the system. A ground fault circuit interrupter (GFCI) is recommended for use on any electrical appliance submerged in water.
Use this system only for backup sump pump duty in a residential application. It is not designed as a primary sump pump.
Do not lift pump by electrical cord.

WARNING Risk of electrical shock. Do not lift the pump by the electrical cord; lift pump only by the discharge pipe, lifting ring or handle on the pump. Lifting by the cord can damage the cord.
Pump clear water only with this pump.
Pump is permanently lubricated at the factory. Do not try to lubricate it!
Keep battery charger and battery box off of the floor and in a dry, cool, well ventilated area.
NOTICE: If a Carbon Monoxide (CO) sensor is installed, it must be at least 15 feet away from battery charger in order to avoid nuisance CO alarms. Please refer to your CO detector’s installation guidelines for more information.
To avoid danger of fire or explosion, keep sparks and flame (pilot light) away from battery.
Maximum vertical pumping distance is 14 feet (4.3M) for Model FG-2200.
Make sure sump is clear of debris. Debris can damage the pump which can result in flooding.

GENERAL INFORMATION
The battery backup sump system is not a substitute for your primary sump pump. It is designed to temporarily backup your primary sump pump during a power outage or other problem which prevents normal operation of the primary pump. Do not use this system to pump flammable liquids or chemicals. Pump clear water only with this pump.
Keep the battery charger dry and protected from damage.
This system is designed to work with a deep cycle sealed maintenance free lead-acid AGM battery. It will also work with a flooded lead acid battery. Gel and Sealed flooded lead acid batteries are not recommended. In an emergency (such as an extended power outage) which depletes the system deep cycle battery, your automobile battery may be temporarily substituted. Be sure to replace the system deep cycle battery as soon as possible. Use of an automobile battery instead of a deep cycle battery in this system will significantly reduce the system’s total performance. Automobile batteries are not designed for this type of application and will be quickly ruined by the repeated charge/discharge cycling. NOTICE: This system is not designed for applications involving salt water, brine, or where fish may be present! Use with these will void warranty.

California Proposition 65 Warning
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.

Installation

BASIC TOOLS AND PARTS NEEDED (Purchase Separately)

  • Large adjustable pliers
  • Tape measure
  • Socket wrench or 5/16” nut driver
  • Side cutters
  • Hacksaw (to cut PVC pipe)
  • Medium size pliers
  • Slotted screwdriver
  • Phillips head screwdriver
  • Pencil or marker
  • PTFE pipe thread sealant tape
  • PVC glue (solvent weld)
  • PVC pipe cleaner
  • Cloth towel
  • Plastic fittings
  • Check valve(s) – 1 or 2 depending on installation
  • 38-120 Ampere-Hour Storage or Deep Cycle Battery

Required Battery Capacity:
For best results, use the following AGM Storage Batteries:

Part| Amp- Hour| Gal/Charge at 10’| Approx Run Time
---|---|---|---
BAT40| 40| 3000| 4.5 Hours
BAT75| 75| 7000| 10.3 Hours

  • Unit equipped with dual battery capability
  • Maximum amp-hour: 120

NOTICE: The charger will not fully charge batteries with excessive amp hour ratings without resetting system.
FG-2200 Performance

Head in Feet 0 5 10 13.35
Head in Meters 0 1.5 3
GPM 34 23 10 0
LPM 129 87 38 0

BATTERY BACKUP SYSTEM (BBU) INSTALLATION AND OPERATION
NOTICE:

  • Install this system during a time when the primary pump will not be needed. Gather all supplies before starting. Read all warnings and installation steps before you start.
  • Be prepared for water to leak from the coupling or piping when disassembling or cutting the discharge pipe. Protect system components, tools and supplies from getting wet. Dry any work areas that get wet.

NOTICE: Study pages 4-6 to determine which installation method will be best for you. The “Separate Discharge” (Figure 2, Page 4), installation is recommended.
NOTICE: Check your local codes and ordinances regarding waste water disposal (especially when running the pump discharge outside the house) before you start. The installation must conform to all legal requirements.
If possible, install the BBU so that the discharge goes directly outdoors (separate discharge pipe from the primary sump pump discharge pipe). If this is not a practical option, see the “Common Discharge” (Figure 3, Page 4) option.
NOTICE: For ALL installations, once the installation is complete, run both the primary sump pump and the BBU through at least one complete cycle to make sure that everything operates correctly.
Personal injury and flood hazard. Do not turn the pump on until all the fittings are glued and the glue has dried. Loose fittings can explode off of pipes and cause personal injury and flooding.
Risk of electrical shock. At the circuit breaker or fuse box, turn off the electrical power to the sump pump before beginning this installation.

Setup

  1. Locate the high water level in your sump pit (the water level at which the existing (primary) sump pump starts – see Figure 1). Turn off power to pump and mark this point on the discharge pipe with a pencil or marker.
  2. Drain the sump pit as far as possible without running the pump dry. Do this by:
    • PIGGYBACK SWITCH: Unplug the pump and switch from the outlet, then unplug the pump from the piggyback switch. Reset the circuit breaker or reinstall the fuse and plug the pump directly into the outlet. The pump will start. Drain the pit and unplug the pump. OR
    • NO PIGGYBACK SWITCH: Reset the circuit breaker or reinstall the fuse and use a non-conducting broom handle or stick to raise the float switch; the pump should start. Drain the pit and then release the switch.
  3. When the pit has drained, turn off (open) the circuit breaker or remove the fuse again to avoid electrical shock while working on the installation.

“Separate Discharge”
NOTICE: Check Valve Flapper(s) must swing AWAY and flow arrow(s) must point AWAY from pump being protected. The water level when the switch shuts off must be above the BBU pump intake.
• Supplied with the Battery Backup System.

Figure 2: Typical installation with separate discharge pipes.

Common Discharge
NOTICE:
In this installation, if the Primary Sump Pump (PSP) does not have a check valve installed below the wye, you MUST install a check valve for the PSP as shown. This prevents backflow of water into the sump from the Batter Backup Unit. Check Valve Flapper(s) must swing AWAY and flow arrow(s) must point AWAY from the pump being protected.
The water level when the switch shuts off must be above must be above the BBU pump intake.

Figure 3: Typical installation with common discharge pipe.

INSTALLATION (Typical): Separate Discharge
Risk of electrical shock. Can shock, burn, or kill. Unplug the primary sump pump before beginning this procedure.
NOTICE: Allow for overlap when cutting piping and run a trial (dry) fitting before you glue.

  1. Use PTFE pipe thread sealant tape on male ends of discharge pipe. Thread the 1-1/4” x 1-1/2” elbow (supplied) onto the discharge. When tight, the elbow must point up.

  2. If possible, install the Battery Backup Unit (BBU) on the floor of the sump; be sure that the two pumps do not touch each other and do not interfere with switch operation.
    NOTICE: If debris or gravel is present in the bottom of the sump pit that could get sucked up into the pump, set both the primary sump pump and the BBU up on bricks or cinder blocks to prevent clogging.

  3. If the sump is too small to allow both pumps to sit on the bottom of the sump, install an angle bracket on the primary sump pump’s discharge pipe with stainless steel hose clamps. Mount the backup pump on the angle bracket. See Figure 1, “Separate Discharge”.

  4. Cut a piece of 1-1/2” PVC pipe to reach from the back-up pump discharge elbow to about one (1) foot above the basement floor. This is the lower discharge pipe.

  5. To prevent airlocking the pump during operation, drill a 1/8” hole in the lower discharge pipe about 2” above the bottom of the pipe (below floor level).

  6. Install FP0026-10 check valve (purchase separately) on the upper end of the pipe. Tighten the hose clamps securely. BE SURE that the flow arrows point UP (away from the BBU). If they point down, the valve will not pass water and the pump will not work.

  7. Cut a short length of 1-1/2” PVC pipe for a riser pipe and clamp it into the top of the check valve.

  8. Install a U74-68 Hose and Clamp Assembly on the top of the riser pipe. For 1-1/2” pipe, remove and discard the short piece of 1-1/4” hose in the Hose and Clamp Assembly. Leave the hose clamps loose and slide the Assembly down below the top of the riser pipe.

  9. Determine where you want the discharge to exit the basement. At that point, drill the necessary holes (large enough to have clearance for a 1-1/2” pipe) to allow you to run the discharge pipe from above the sump to the outdoors.

  10. Install the horizontal discharge pipe. Install a 90° elbow on the inside end but do not glue.

  11. Cut another short piece of 1-1/2” PVC for the Upper Discharge Pipe to run from the top of the riser pipe up to the 90° elbow. Be sure to allow enough overlap for the glue joint in the elbow.

  12. Do a trial fit with NO GLUE, installing the 1-1/2” upper discharge pipe in the 90° elbow and the upper discharge pipe in the vertical end of the 90° elbow. The upper discharge pipe should just fit between the riser pipe and the elbow.

  13. Risk of fire and chemical inhalation. Whenever using PVC primer and PVC cement, follow the glue manufacturer’s instructions.

  14. Make sure that the BBU will clear the primary sump pump and its switch. If there isn’t room for both pumps to sit on the floor of the sump, the BBU will have to be raised (depending on your particular situation).

  15. Clean, prime and glue the upper discharge pipe into the 90º elbow. When the glue has set, slide the Hose and Clamp Assembly up to cover the joint and tighten all the hose clamps.

  16. Install the Battery Backup Switch as shown, 1” above start water level of primary pump. Fasten it to the pipe with cable ties.

  17. Tape the pump cord to the riser pipe so that the plug cannot fall into the sump.

  18. Go to “BBU WIRING AND SETUP” (Page 8) for wiring instructions.

  19. Once all wiring is complete, fill your pit with water and verify that the PSP removes the water and the BBU doesn’t run. Then, unplug your PSP and refill your pit with water. Verify that the BBU pump removes the water.

  20. Make sure that the power is on to both pumps, and your system is ready to use.

INSTALLATION (Typical): Common Discharge
Risk of electrical shock. Can shock, burn, or kill. Unplug the primary sump pump before beginning this procedure.
NOTICE: Allow for over lap when cutting piping and run a trial (dry) fitting before you glue.
NOTICE: If there is no check valve in the primary sump pump’s discharge, you will need to install one. You must also install one in the BBU’s discharge pipe (Figure 3, Page 4). Make sure that the check valve flow arrow points AWAY from the pump it is protecting.

  1. Use PTFE pipe thread sealant tape on male ends of discharge pipe. Thread the 1-1/4” x 1-1/2” elbow (supplied) onto the discharge. When tight, the elbow must point up.

  2. If possible, position the BBU on the floor of the sump; be sure that the two pumps do not touch each other and do not interfere with switch operation.
    NOTICE: If debris or gravel is present in the bottom of the sump pit that could get sucked up into the pump, set both the primary sump pump and the BBU up on bricks or cinder blocks to prevent clogging.

  3. If the sump is too small to allow both pumps to sit on the bottom of the sump, find a raised position that doesn’t interfere with the PSP switch.

  4. Cut a piece of 1-1/2” PVC pipe to reach from the back-up pump discharge elbow to about one (1) foot above the basement floor. This is the lower discharge pipe.

  5. To prevent airlocking the pump during operation, drill a 1/8” hole in the lower discharge pipe about 2” above the bottom of the pipe (below floor level).

  6. Install FP0026-10 check valve (purchase separately) on the upper end of the pipe. Tighten the hose clamps securely. BE SURE that the flow arrows point UP (away from the backup pump). If they point down, the valve will not pass water and the pump will not work.

  7. Cut the discharge pipe for the primary sump pump (PSP) above the union and check valve (if any). Make this cut about 18” above the top of the BBU’s riser pipe with the backup pump sitting as installed.

  8. If the PSP does not have a check valve installed in the discharge pipe, install one now.

  9. Cut a length of discharge pipe for the PSP to fit between the check valve and a 45° slip wye. Be sure to allow for the overlap needed for gluing joints.

  10. Install the 45° wye on the PSP’s discharge pipe.

  11.  Install a 45° elbow on the 1-1/2” BATTERY BACKUP discharge pipe.
    NOTICE: You may need to insert a piece of straight pipe between the elbow and the wye. If so, use a standard 45° elbow. If you do not need to insert a piece of straight pipe between the elbow and the wye (elbow goes directly into the wye), use a 45° slip street ell.

  12. Fit the upper discharge pipe to the upper end of the wye. NOTICE: It is good practice to cut a short length of pipe to go into the wye and install a union on the pipe. Continue the discharge pipe from the outlet side of
    the union. This will allow easier removal of the system for cleaning or service. A U74-68 Hose and Clamp Assembly can be used for this.

  13. Make sure that the BBU will clear the primary sump pump and its switch. If there isn’t room for both pumps to sit on the floor of the sump, the BBU will have to be raised (depending on your particular situation).

  14. Do a trial assembly to make sure that everything is going to fit. This may require a helper to assist in holding everything together while you check the fit without glue. Mark all joints before gluing.
    Risk of fire and chemical inhalation. Follow the glue manufacturer’s instructions regarding fire hazards and ventilation when using PVC solvents, primer, and cement.

  15. Take all the pipe apart, clean all joints, and then reassemble the system, gluing it with PVC primer and glue.

  16. Install the Battery Backup Switch as shown, 1” above start water level of primary pump. Fasten it to the pipe with the cable ties provided.

  17. Tape the pump cord to the riser pipe so that the plug cannot fall into the sump.

  18. Go to “BBU WIRING AND SETUP” (Page 8) for wiring instructions.

  19. Once all wiring is complete, fill your pit with water and verify that the PSP removes the water and the BBU doesn’t run. Then, unplug your PSP and refill your pit with water. Verify that the BBU pump removes the water.

  20. Make sure that the power is on to both pumps, and your system is ready to use.

Battery Requirements

Hazardous electric current. Can cause severe burns and start a fire if the battery terminals are short circuited. Install the battery in the battery case. To prevent accidental shorting across battery terminals, close and latch the battery case securely. Do not leave the battery uncovered.
Do not allow children to play around the battery backup system installation.
The performance of your backup sump pump depends on the battery used with it for power. We recommend using our BAT40 or BAT75. You can also use a group 24M or 27M Deep Cycle battery. They will provide acceptable performance and will stand up well to long periods of little or no use.
This system is designed to work with either a sealed lead-acid AGM battery or a flooded lead-acid battery. Use of a true Gell Cell (often confused for AGM) or
a standard automotive battery with this charger is not recommended. An automotive battery may require charging after only 1-2 hours of continuous use, and the repeated charging cycles may cause early plate failure in the battery.
Use only lead-acid batteries. This unit is not designed to use with Li-Ion, NiMh, NiCAD, Liquid Polymer, etc.
Use only the recommended battery or one of the same type and size so it will fit in the battery box (maximum size: 13” long x 7” wide x 10” tall (330.2mm x 177.8mm x 254mm) including terminals) and supply enough voltage for full performance.

BATTERY MAINTENANCE
Severe burn hazard. An acid-filled standard lead-acid battery contains sulfuric acid. Avoid contact with skin, eyes or clothing.
NOTICE: To protect the battery case from chipping and gouging, do not let the battery sit on a concrete floor. Install the battery on a shelf or protective pad (plywood, 2x4s, etc.). Always install the battery in a dry location that is protected from flooding.

Pre-Qualification Test – 1 and 2
Charger is charging at a very low level to try to bring a dead battery back to life. If the battery is taking too long, try resetting the charger once or twice (push the ‘SYSTEM TEST’ and ‘SILENCE ALARM’ buttons together to reset the charger).

Special Features:
The charger is equipped with reverse battery, short circuit, and “runaway charge” protection.

Possible Problems and Remedies

  1. Wrong Battery Voltage
    Reconnect charger to a 12 volt battery.

  2. Reversed Battery Connections
    Check all connections. The negative (black) on the battery must connect to the negative (black) on the charger, and the positive (red) on the battery must connect to the positive (red) on the charger. Reversing the battery connections will cause the ‘SYSTEM ALERT’ and ‘SILENCED AUDIBLE ALARM’ LEDs to flash.

  3. Thermal Runaway Condition
    “Thermal Runaway” is the technical term for the condition of the battery when some (or all) of the cells have deteriorated to the point that they won’t take a charge. In this case, replace the battery.

  4. Charge Time Monitor – 1 and 2
    Battery took too long to complete its charge. The
    “Charge Time Monitor” will shut down the charger after 84 hours of continuous charging.
    Possible causes are:

    • Pump ran for a long period of time during charging, or
    • Battery is too large for the charger (including several batteries connected in a parallel circuit).

Excessive Battery Drain
Pump may have run for a very long time, discharging the battery. In this case:

  1. If 115VAC power is OFF, the charger shuts down until the power comes back on, but the pump will run as long as the battery charge lasts. You may need to replace the battery afterwards.

  2. If 115VAC power is ON, the charger/controller continues to try to charge the battery at a charging rate of .5 AH until the battery charge is more
    than 20%, at which point the charger will resume charging at a rate of 2 AH.

  3. If the pump is running and the AC power is on, you may need to stop the pump to allow the battery to charge.

Follow the battery manufacturer’s recommendations for maintenance and safe use of the battery.

Wiring • Setup

BBU WIRING AND SETUP

  1. Connect the positive (+) charger/controller lead  wire (red) to the positive (+) battery terminal (red). Connect the negative (–) charger/controller lead wire (black) to the negative (–) terminal (black) on the battery. If you are using two batteries, use the set of optional terminals and connect the second battery. Use lead wires (not included) to connect the positive (+) charger/controller terminal to the positive (+) battery terminal and the negative (–) charger/controller terminal to the negative (–) battery terminal.

Figure 5: The battery input is inside the battery case. Support the case when opening it. The support must be at least 4” thick.

  1. The backup pump leads are polarity connect the positive pump lead to labeled Pump ‘+’ and the negative terminal labeled Pump ‘–’.
    NOTICE: If the leads are reversed, the pump will run backward and not pump water.

  2. The float switch leads are not polarity sensitive; connect the float switch leads to the ‘Float Switch’ tabs on the charger/controller.

  3. Test the float and the pump by lifting and holding the float. The ‘PUMP STATUS’ LED will light continuously and the buzzer will beep steadily. The pump should start after 3 seconds. If the pump does not run, check all the connections and remake them as necessary.

  4. To stop the pump, lower the float; after 25 seconds the pump should stop, the ‘PUMP STATUS’ LED should flash, and the buzzer should beep.

  5. With the pump operating, test the ‘SILENCED ALARM’ button; hold for one second; release.
    The ‘SILENCED AUDIBLE ALARM’ LED should illuminate and the buzzer should stop sounding. To reset the buzzer (allow it to sound) and extinguish the ‘SILENCED AUDIBLE ALARM’ LED, press the ‘SILENCE ALARM’ button again for one second. Depress the ‘SYSTEM TEST’ button; hold it for one second; release. The ‘PUMP STATUS’ LED should stop flashing. NOTICE: During normal operation, the flashing ‘PUMP STATUS’ LED indicates that the pump has run in your absence.

  6. Press and hold ‘SYSTEM TEST’ button. All LEDs will light up, pump will run and buzzer will sound. Release the button and LEDs should go off, pump should stop, buzzer should stop.

  7. The ‘BATTERY STATUS’ LED indicates the battery capacity when the A.C. power is off.

  8. Continuously ON – the battery voltage is above 10.9 Volts Direct Current (10.9VDC) and capacity is above 20%.

  9. Slow Beep/Slow LED Flash – the battery’s capacity is between 0 and 20%.

  10. Fast Beep/Fast LED Flash – the battery is severely discharged. The battery will continue to charge (as long as the 115V AC power to the charger is on) at the rate of .5 AH until the battery’s charge is above 20%.
    When the first warning occurs (slow beep/slow flash), you will have approximately 2 hours (or less) of pump operation left. The actual time of operation will depend on the condition of the battery and may be as little as 15 minutes.

  11. Connect the Power Supply cable (supplied) to the Charger/Controller’s Power Input jack.

LED Display and Control Buttons

PENTAIR-FG-2200-Classic-Battery-Backup-Systems-8

NOTICE: When the unit is first plugged in, or when it first receives power from the battery, the ‘BATTERY STATUS’ LED will flash for 3 seconds.
NOTICE: To activate any Control Button, press and hold it for 1 second.

LED Display

TABLE II – Operating Code Displays (LEDs Lighted Continuously or Flashing)

PENTAIR-FG-2200-Classic-Battery-Backup-Systems-9

NOTICE: All of the situations listed above indicate normal system operation; no action is required. However, if the BBIJ pump is running or has run, check the primary pump and actively monitor the charger status for battery life. Always reset the charger after the pump runs. During normal system operation, the ‘SYSTEM ALERT’ LED does not light up. The “AC POWER” LED is lighted as long as the system is plugged in to an operating AC power circuit.

Control LED:| Continuous Illumination Indicates Normal Operation:
---|---
AC Power| AC power is present.
Pump Status| The float switch has been activated. The LED remains on (flashing) after the pump has stopped. Depress the ‘SYSTEM TEST’ button to reset it.
Silenced Audible Alarm| Audible Alarm has been silenced. Press and release the ‘SILENCE ALARM’ button to reset (activate) the audible alarm and turn OFF the LED.
Charging| Indicates that the battery is charging – see Table II, above.
Battery Status| A. Continuous ON – the battery voltage is above 10.9 Volts DC and capacity is above 20%.
B. Slow Beep/Slow LED Flash – the battery’s capacity is below 20%, and voltage is between 8.2VDC and 10.9VDC.
C. Fast Beep/Fast LED Flash – the battery has been discharged to less than 8.2VDC.
System Alert| Flashing (in unison with the buzzer) indicates that the charger has entered ‘Failure Mode’. Press the ‘SYSTEM TEST’ and ‘SILENCE ALARM’ buttons to reset it.

NOTICE : If the source of the failure is not corrected, the charger will reenter “Failure Mode”. See Table IV for error code information.

TABLE IV – Error Code Displays (LEDs Flashing)

PENTAIR-FG-2200-Classic-Battery-Backup-Systems-10

Control Button: Result of Pushing Button:
System Test Pump starts and all LEDs light up.

Will reset the ‘PUMP STATUS’ LED.
When pushed with the ‘SILENCE ALARM’ button, the Charger/Controller microprocessor resets and error code resets.
Silence Alarm| Toggle; Prevents the audible alarm sounding. Press and release to reset.
Light| Toggles the flood light on the Charger/Controller on and off.
System Reset| Press and release ‘SYSTEM TEST’ and ‘SILENCE ALARM’ to reset system.

Troubleshooting

Pump won’t run: Check all the wiring connections.

Check for a low or defective battery.
Check that the automatic switch is free to move up and down.
Press the circuit breaker reset button on the control panel.
Motor hums but pump won’t run:| Check for low or defective battery.
Pump runs but pumps very little or no water:| Make sure a check valve is installed and functioning between the primary pump discharge and the Battery Backup wye.
Check for an obstruction in the discharge pipe.
The discharge pipe length and/or height exceeds the capacity of the pump. See Table VI, Page 11, for pump capacity.
Check for a low or defective battery.
The Positive (+) and negative (–) pump wires are reversed. Disconnect them and reconnect correctly.
Pump cycles too frequently:| The check valve located between the discharge of the primary pump and the Battery Backup wye is not installed or is not working properly. Install an auxiliary check valve (see Pages 5 and 6) or replace the existing check valve as required.

Repair Parts

Key No. Part Description Part Number
1 DC Backup Pump PS17-118
2 1-1/4 FNPT x 1-1/2 Slip Elbow U78-1012
3 Float Switch PS17-2003
4 Charger/Controller PS217-1521
5 Battery Case (Complete) PS17-1512
6 AC Adaptor PS17-2008
7 11” x .14” Plastic Cable Tie *
  • Purchase separately.
    ** If pump fails, replace entire system.

Optional Batteries
*Sold Separately

Key No. Part Description Part Number
X AGM 75A-Hour BAT75
X AGM 40A-Hour BAT40

Warranty

Retain Original Receipt for Warranty Eligibility

Limited Warranty
Hydromatic® warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free from defects in material and workmanship for the Warranty Period shown below.

Product Warranty Period

whichever occurs first:

  • Submersible utility pumps and related accessories 12 months from date of original installation, or 18 months from date of manufacture

  • Sump/Sewage/Effluent Products 12 months from date of original installation, or 36 months from date of manufacture

  • Battery Backup Units
    FG-2200, FG-2200C
    FG-3100, FG-3100C
    12 months from date of original installation,
    or 18 months from date of manufacture
    24 months from date of original installation,
    or 30 months from date of manufacture

  • Wastewater Solids Handling Pumps 12 months from date of shipment from factory or 18 months from date of manufacture

Our warranty applies only where such products are used in compliance with the requirements of the applicable product catalog and/or manuals. For additional information, please refer to the applicable standard limited warranty featured in the product manual.
Our warranty will not apply to any product that, in our sole judgement, has been subject to negligence, misapplication, improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single phase power through a phase converter will void the warranty. Note also that three phase motors must be protected by three-leg, ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void.
Your only remedy, and HYDROMATIC’s only duty, is that HYDROMATIC repair or replace defective products (at HYDROMATIC’s choice). You must pay all labor and shipping charges associated with this warranty and must request warranty service through the installing dealer as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has expired. This warranty is not transferable.
HYDROMATIC SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER.
THE FOREGOING LIMITED WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE. THE FOREGOING LIMITED WARRANTIES SHALL NOT EXTEND BEYOND THE DURATION PROVIDED HEREIN.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on the duration of an implied warranty, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You may also have other rights which vary from state to state.
This Limited Warranty is effective May 12, 2014 and replaces all undated warranties and warranties dated after May 12, 2014.
HYDROMATIC
293 Wright Street, Delavan, WI 53115
Phone: 888-957-8677 • Fax: 800-426-9446www.hydromatic.com
In Canada: 490 Pinebush Road, Unit 4, Cambridge, Ontario N1T 0A5
Phone: 800-363-7867 • Fax: 888-606-5484

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Pentair User Manuals

Related Manuals