BD SENSORS PA 440 Digital Field Display User Manual
- June 10, 2024
- BD SENSORS
Table of Contents
- BD SENSORS PA 440 Digital Field Display
- Pressure Transmitter PA 440
- Intended Use
- Package Contents
- UL-Approval
- Usage Instructions
- General information
- Product identification
- Mechanical installation
- Special regulations for IS-Areas
- Initial start-up
- Operation
- Warranty terms
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BD SENSORS PA 440 Digital Field Display
Pressure Transmitter PA 440
Operating Manual
The Digital Field Display PA 440 is designed for use in IS-areas and is supplied by the analogue current loop to show the measured value on the display. The PA 440 can monitor limit values with up to two PNP open collector contacts. The device is equipped with an LC-display as standard, but a LED- display is also available upon request.
The configuration of the device is menu-driven via two push buttons located on the front. The user can configure parameters such as decimal point, zero point, end point, switch-on and switch-off points, etc. These parameters are stored in an EEPROM and will be kept even in case of power breakdown. Limit exceeding in both directions can be displayed as a message. Additionally, an access protection feature is provided.
The field display PA 440 is intended for use in IS-areas and has an explosion protection approval if specified in the purchase order and confirmed in the order confirmation. It is the operator’s responsibility to check and verify the suitability of the device for the intended application. Technical data listed in the current data sheet must be complied with.
Intended Use
The field display PA 440 is intended to be used to display measured values for pressure transmitters in IS-areas. It is not intended for any other use.
Safety Technical Maximum Values
AX15-PA440
IBExU08ATEX1126 X / IECEx IBE21.0023X zone 1: II 2G Ex ia IIB T4 Gb
Package Contents
Please verify that all listed parts are undamaged and included in the delivery:
- Field display PA 440
- Sheet of unit labels
- Operating manual
UL-Approval
Note the following points to ensure the device fulfills the demands of UL approval:
- Only indoor use
- Maximum operating voltage: see technical data
- The transmitter shall be supplied by Limited Energy Source (per UL 61010) or NEC Class 2 Power Source.
Product Identification
The device can be identified by its manufacturing label, which provides the most important data. The programme version of the firmware will appear for about 1 second in the display after starting up the device. Please hold it ready for inquiry calls.
Usage Instructions
Before using the field display PA 440, please ensure that all parts are included and undamaged.
- Connect the field display PA 440 to the analogue current loop.
- Turn on the device using the power button.
- Use the two push buttons on the front to navigate the menu and configure parameters such as decimal point, zero point, end point, switch-on and switch-off points, etc.
- The configured parameters will be stored in an EEPROM and will be kept even in case of power breakdown.
- If limit values are to be monitored, connect up to two PNP open collector contacts.
- The field display will show measured values and can display limit exceeding in both directions as a message.
- The device has an access protection feature for added security.
- Refer to the operating manual for technical data and to ensure proper usage in IS areas.
General information
Information on the operating manual
This operating manual contains important information on proper usage of the
device. Read this operating manual carefully before installing and starting up
the pressure measuring device.
Adhere to the safety notes and operating instructions which are given in the
operating manual. Additionally applicable regulations regarding occupational
safety, accident prevention as well as national installation standards and
engineering rules must be complied with!
For the installation, maintenance, and cleaning of the device, you must
absolutely observe the relevant regulations and stipulations on explosion
protection (VDE 0160, VDE 0165 and/or EN 60079-14) as well as the occupational
safety provisions.
The device was designed by applying the following standards:
EN IEC 60079-0:2018
EN 60079-11:2012
IEC 60079-0:2017 Edition:7.0
IEC 60079-11:2011 Edition:6.0
This operating manual is part of the device, must be kept nearest its
location, always accessible to all employees.
This operating manual is copyrighted. The contents of this operating manual
reflect the version available at the time of printing. It has been issued to
our best knowledge.
BD SENSORS is not liable for any incorrect statements and their effects.
Technical modifications reserved
Symbols used
DANGER! – dangerous situation, which may result in death or serious injuries
WARNING! – potentially dangerous situation, which may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may result in minor injuries
! CAUTION! – potentially dangerous situation, which may result in physical damage
NOTE – tips and information to ensure a failure-free operation
Target group
WARNING! To avoid operator hazards and damages of the device, the
following instructions have to be worked out by qualified technical personnel.
Limitation of liability
By non-observance of the operating manual, inappropriate use, modification or
damage, no liability is assumed, and warranty claims will be excluded.
Intended use
-
The field display PA 440 is supplied by the analogue current loop and shows the measured value on the display.
For monitoring the limit values optionally up to two PNP open collector contacts are available. As standard the PA 440 is equipped with a LC display, optionally a LED-display is deliverable. -
The configuration is menu-driven via two push buttons
located in the front. Following parameters could be configured: decimal point, zero point, endpoint, switch-on and switch-off points, etc. Those parameters are being stored in an EEPROM and, thus, are being kept also in case of power breakdown. Limit exceeding in both directions can be displayed as a message. Furthermore, an access protection is provided. -
This operating manual applies to devices with explosion protection approval and is intended for the use in ISareas.
A device has an explosion protection approval if this has been specified in the purchase order and confirmed in our order confirmation. In addition, the manufacturing label contains the -symbol. -
It is the operator’s responsibility to check and verify the suitability of the device for the intended application. If any doubts remain, please contact our sales department in order to ensure proper usage. BD SENSORS is not liable for any incorrect selections and their effects!
-
The technical data listed in the current data sheet are engaging and must be complied with. If the data sheet is not available, please order or download it from our homepage. (http://www.bdsensors.de/products/download/datasheets)
WARNING! Danger through improper usage!
Safety technical maximum values
AX15-PA440
IBExU08ATEX1126 X / IECEx IBE21.0023X
zone 1: II 2G Ex ia IIB T4 Gb
permissible temperatures for environment: -20 … 70 °C
Ui = 28 V, Ii = 93 mA, Pi = 660 mW, Ci = 0 nF, Li = 0 μH
Package contents
Please verify that all listed parts are undamaged included in the delivery and
check for consistency specified in your order:
- field display PA 440
- sheet of unit labels
- this operating manual
UL-Approval
The UL – Approval was done with respect to U.S. standards norms which also
correspond with the applicable Canadian standards norms for safety.
Note the following points, so that devices fulfils the demands of UL approval:
- only indoor use
- maximum operating voltage: see technical data
- The transmitter shall be supplied by Limited Energy Source (per UL 61010) or NEC Class 2 Power Source.
Product identification
The device can be identified by its manufacturing label. It provides the most important data. By the ordering code the product can be clearly identified. The programme version of the firmware, (e. g. P06) will appear for about 1 second in the display after starting up the device. Please hold it ready for inquiry calls.
The manufacturing label must not be removed from the device!
Mechanical installation
Mounting and safety instructions
WARNING! Install the device only when current less!
WARNING! This device may only be installed by qualified technical personnel who has read and understood the operating manual! DANGER! Caused by the explosion hazard following instructions have to be complied with:
-
The technical data listed in the EC type-examination certificate are. If the certificate is not available, please order or download it from our homepage: http://www.bdsensors.de/products/download/certificates
-
Working on supplied (active) parts, except for intrinsically safe circuits, is principally prohibited during an explosion hazard.
-
Make sure that an equipotential bonding is in place for the entire course of the line, both inside and outside the intrinsic area.
-
In case of increased danger of lightning strike or damage by overvoltage, a stronger lightning protection should be planned.
-
Observe the limiting values specified in the EC type-examination certificate. (Capacitance and inductance of the connection cable are not included in the values.)
-
Make sure that the entire interconnection of intrinsically safe components remains intrinsically safe.
The operator is responsible for the intrinsic safety of the overall system (installation of intrinsic parts). -
The external circuit must prevent an external power flow to the contacts. Suitable signal-separating devices which fulfil this demand have to be used.
Handle this high-sensitive electronic precision measuring device with care, both in packed and unpacked condition!
- There are no modifications/changes to be made on the device.
- Do not throw the package/device!
- Remove packaging only directly before starting up the device to avoid any damage!
- Do not use any force when installing the device to prevent damage of the device and the transmitter!
General installation steps
- Carefully remove the pressure measuring device from the package and dispose of the package properly.
- Next the field display has to be mount stationary on a suitable fixing location via two appropriate fastening screws.
Lead in the transmitter cable
- Lead in the connecting cable of the transmitter through the cable gland on the left side. The cable length inside the terminal box has to be long enough for connecting the cords with the terminal clamps on the left (SENSOR).
- Then tighten the cable gland by hand. Take care that the cable is strain-relieved.
- Pay attention that the PTFE-filter on the gauge reference of BD SENSORS-transmitters may not be damaged or removed.
Lead in the supply line
- Lead the supply line through the cable gland on the right side. The cable length inside the terminal box has to be long enough for connecting the cords with the terminal clamps on the right (SUPPLY).
- Then tighten the cable gland by hand. Take care that the cable is strain-relieved.
Special regulations for IS-Areas
Protection against electrostatic charge hazards
Different types of devices partially consist of chargeable plastic components.
These are, in particular, the carrying and connection cables, terminal boxes
as well as housing enclosures.
A potential electrostatic charge presents the danger of spark generation and
ignition. An electrostatic charge must therefore be absolutely prevented.
- Generally, a shielded cable must be used.
- Avoid friction on the plastic surfaces!
- Do not clean the device dry! Use, for example, a damp cloth.
The following warning sign is, if applicable, attached to the transmitter. It points once more to the hazard of electrostatic charging.
! The warning sign must not be removed from the device!
Overvoltage protection
If the device is used as electrical equipment of category 2 G,a suitable
overvoltage protection device must be connected in series (attend the valid
regulations for operating safety as well as EN60079-14).
Exemplary circuit description
The operation of an intrinsically safe device in intrinsic safe areas requires
special care when selecting the necessary Zener barrier or transmitter
repeater devices to be able to use the device’s characteristics to the full
extent. The following diagram shows a typical arrangement of power
supply,Zener barrier and device.
Exemplary circuit description
The supply voltage of e. g. 24 VDC provided by the power supply is led across
the Zener barrier. The Zener barrier contains series resistances and Zener
diodes as protective components. Subsequently, the operating voltage is
applied to the device and, depending on the pressure, a particular signal
current will flow.
Functional selection criteria for Zener barriers and galvanic power
supply
The minimum supply voltage VS min of the device must not fall short since a
correct function of the device can otherwise not be guaranteed. The minimum
supply voltage has been defined in the respective product-specific data sheet
under “Output signal/supply”.
When using a galvanically insulated amplifier with a linear bonding, please
attend that the terminal voltage of the device will decrease like it does with
a Zener barrier. Furthermore, it has to be attended that the supply of the
device will also decrease with an optionally used signal amplifier.
Test criteria for the selection of the Zener barrier
In order not to fall below VS min it is important to verify which minimum
supply voltage is available at full level control of the device.
The technical data of the barrier will usually provide you with the
information needed for the selection of the Zener barrier.
However, the value can also be calculated. If a minimum sup-ply of 16 V is
assumed, then – according to Ohm’s law – a particular voltage drop will result
on the series resistance of the Zener barrier. If, for a device with PNP
contact, the contact is also activated, the additional current flowing from
the contact to the load resistor will also flow through the Zener barrier or
the output of a transmitter repeater. The higher the load current, the lower
the available minimum operating voltage. In the diagram shown, the maximum
current can be calculated from the voltage difference (Vab Barriere max)
between input and output of the Zener barrier divided by the series resistance
of the Zener barrier.
The maximum signal current must be subtracted from this value. If the
available residual current is smaller than the current required at the
contact, either a different barrier or a higher sup-ply voltage before the
barrier should be chosen.
When selecting the power supply, the maximum operating conditions according to
the EC type-examination certificate must be observed. When assessing the power
supply, please refer to their current data sheets to ensure that the entire
interconnection of intrinsically safe components will remain intrinsically
safe.
Electrical Installation
WARNING! Install the device only when currentless!
The supply must correspond to the safety class II (protective insulation)!
The transmitter shall be supplied by Limited Energy Source (per UL 61010) or
NEC Class 2 Power Source!
Open the top cover; establish the electrical connection of the device
according to the following table and the wiring diagram. Screw the top cover
onto the box again.
Pin configuration:
__
De- sign- ation
| __
__
Terminal block
| Electrical connection (cable colours of BD SENSORS
transmitters)
| __
has to be connected with
---|---|---|---
__
GND
| __
SENSOR
| Potential refer- ence clamp (yellow/green )| cable shield of transmitter
VS-| SENSOR| Supply – (brown)| neg. connecting cable of transmitter
VS+| SENSOR| Supply + (white)| pos. connecting cable of transmitter
SP2| SP| Contact 1| connecting cable of transmitter for contact 1
SP1| SP| Contact 2| connecting cable of transmitter for contact 2
VS+| SUPPLY| Supply +| pos. connecting cable for pressure signal
VS-| SUPPLY| Supply –| neg. connecting cable for pressure signal
GND| SUPPLY| Potential reference clamp| cable shield of supply line
For the electrical connection a shielded and twisted multicore cable is recommended.
The ground wires of all components have to be connected when installing!
Pin configuration:
Supply:
The supply created by the electronics of the device is approx.
5.5 VDC. Please take this into consideration when planning your power supply.
The tolerances for the power supply can be calculated as follows:
- Minimum supply: VSmin = VminTR + 6.5V
- Maximum supply: VSmax = VmaxTR + 6.5V
- Vmin TR = minimum supply of the used 2-wire transmitter
- VmaxTR = maximum supply of the used 2-wire transmitter
Initial start-up
WARNING! Before the initial start-up, the user has to check that the
device has been properly installed and make sure that it does not have any
visible defects.
WARNING! The device must only be started up by qualified technical
personnel that has read and understand the operating manual!
WARNING! The device must only be used within the technical specifications
(compare the data in the data sheet and the EC type-examination certificate)!
Operation
Configuration
The menu system is a closed system allowing you to scroll both forward and
backward through the individual set-up menus to navigate to the desired
setting item. All settings are permanently stored in an EEPROM and therefore
available again even after disconnecting from the supply voltage. The
structure of the menu system is the same for all types of devices, regardless
of the number of contacts. However, they only differ by the number of menus.
Following figure and the menu list shows all possible menus.
Please follow the manual meticulously and remember that changes of the
adjustable parameters (switch-on point, switch-off point, etc.) become only
effective after pushing both buttons simultaneously and leaving the menu item.
Password system
To avoid a configuration by unauthorized persons, the possibility is given to
lock the device by an access protection.
More information is given in menu 1 of the menu list.
Unit
The unit of the values to be measured is determined on ordering. But it is
also possible to change the unit later by using one of the enclosed unit
labels.
Description of hysteresis and compare mode
To invert the respective modes, you have to exchange the values for the
switch-on and switch-off points.
Structure of the menu system
Menu list
- ▲-button: move in the menu system (forward) or increase the displayed value
- ▼-button: move in the menu system (backward) or decrease the displayed value
- both buttons simultaneously: confirm the menu items and set values or change between display and configuration mode to increase the counting speed, when setting the values: keeping the respective button pushed for more than 5 seconds
Execution of configuration:
- set the desired menu item by pushing the ▲- or ▼-button
- activate the set menu item by pushing both buttons simultaneously
- set the desired value or select one of the offered settings by using the ▲- or ▼-button
- store the set value / selected setting and exit the menu by pushing both buttons simultaneously
| menu 1 – access protection
PAon è password active è to deactivate: set password PAof è password inactive è to activate: set password
default setting for the password is “0005”; modification of the password is described in special menu 4
---|---
| menu 2 – set decimal point position
For devices with LC display – in case no decimal point shall be displayed – the colon between digit 3 +4 is displayed in the selection menu “dP”.
| menus 3 and 4 – set zero point / end point
the device has been configured correctly before delivery, so a later setting of a 2-wire device is only necessary, if a differing displayed value is desired (e. g. 0 … 100 %)
| menu 5 – set damping
this function allows getting a constant display value although the measuring values may vary considerably; the time constant for a simulated low-pass filter can be set (0.3 up to 30 sec permissible)
| menu 6 – exceeding message
set “on” or “off”
| menus 7 and 9 – set switch-on points
set the particular values, for the activation of contact 1 (S1on) up to 2 (S2on)
| menus 8 and 10 – set switch-off points
set the particular values, for the deactivation of contact 1 (S1oF) up to 2 (S2oF)
| menus 11 and 12 – select hysteresis or compare mode
select the hysteresis mode (HY 1 up to HY 2) or compare mode (CP 1 up to CP 2) for the contacts 1 up to 2 (no. corresponds to the contact)
compare “7.4. Description of hysteresis and compare mode”
| menus 13 and 15 – set switch-on delay
set the particular value of the switch-on delay after reaching contact 1 (d1on) up to 2 (d2on) (0 up to 100 sec permissible)
| menus 14 and 16 – set switch-of delay
set the particular value of the delay after reaching the switch-off point 1 (d1of) up to 2 (d2of) (0 up to 100 sec permissible)
| menus 17 and 18 – maximum / minimum pressure display
view high pressure (HIPr) or low pressure (LoPr) during the measurement process (the value will not remain stored if the power supply is interrupted)
to erase: push both buttons again within one second
special menus
(to access a special menu, select the menu item “PAof” with the ▲- or ▼-button and confirm it; “1” appears in the display)
| special menu 1 – full scale compensation
for full scale compensation, which is necessary if the indicated value for full scale differs from the real full scale value in the application (a compensation is only possible with a respective reference source, if the deviation of the measured value is within defined limits); set “0238”; confirm with both buttons; “FS S” will appear in the display; now it is necessary to place the device under pressure (the pressure must correspond to the end point of the pressure measuring range); push both buttons, to store the signal being emitted from the device as full scale; in the display the set end point will appear although the full scale sensor signal is displaced
the analogue output signal (for devices with analogue output) is not affected by this change
| special menu 2 – offset compensation / position correction
set “0247”;
| special menu 3 – load defaults
set “0729
| special menu 4 – set password
set “0835”; confirm with both buttons; “SEtP” appears in the display; set the password using the ▲- or ▼-button (0 … 9999 are permissible, the code numbers 0238, 0247, 0729, 0835 are exempt); confirm the password by pushing both buttons simultaneously
Placing out of service
WARNING! Disassemble the device only in current and pressure less condition!
Maintenance
DANGER! The operator is obligated to observe the information concerning
operation and maintenance work on the warning signs possibly affixed to the
device.
In principle, this device is maintenance-free. If desired, the housing of the
device can be cleaned using a damp cloth and non-aggressive cleaning
solutions, in switched-off state.
Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it has to be cleaned carefully and
packed shatter-proofed. You have to enclose a notice of return with detailed
defect description when sending the device. If your device came in contact
with harmful substances, a declaration of decontamination is additionally
required. Appropriate forms can be downloaded from our homepage
www.bdsensors.de. Should you dispatch a device without a declaration of
decontamination and if there are any doubts in our service department
regarding the used medium, repair will not be started until an acceptable
declaration is sent.
If the device came in contact with hazardous substances, certain precautions
have to be complied with for purification!
Disposal
The device must be disposed of according to the European Directive 2012/19/EU
(waste electrical and electronic equipment). Waste equipment must not be
disposed of in household waste!
Dispose of the device properly!
Warranty terms
The warranty terms are subject to the legal warranty period of 24 months, valid from the date of delivery. If the device is used improperly, modified, or damaged, we will rule out any warranty claim. A damaged diaphragm will not be accepted as a warranty case. Likewise, there shall be no entitlement to services or parts provided under warranty if the defects have arisen due to normal wear and tear.
Declaration of Conformity / CE
The delivered device fulfils all legal requirements. The applied directives,
harmonised standards and documents are listed in the EC declaration of
conformity, which is available online at: http://www.bdsensors.de.
Additionally, the operational safety is confirmed by the CE sign on the
manufacturing label.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>