Autonics KN-2211W Digital Panel Meter Instruction Manual

June 10, 2024
Autonics

Autonics logo 1-Channel Digital Temperature Indicators
KN-2000W Series
TCD210154AC
INSTRUCTION MANUAL

KN-2211W Digital Panel Meter

Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for product improvement Some models may be discontinued without notice.
Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • symbol indicates caution due to special circumstances in which hazards may occur.

Warning Failure to follow instructions may result in serious injury or death

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.

  2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.

  3. Install on a device panel to use.
    Failure to follow this instruction may result in fire or electric shock.

  4. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire or electric shock.

  5. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.

  6. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire or electric shock.

Caution Failure to follow instructions may result in injury or product damage

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage

  2. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.

  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

  4. Check the polarity of the measurement input before wiring.
    Failure to follow this instruction may result in explosion or fire.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
  • For connecting the power, use the crimp terminal (M3.5, max. 7.2 mm)
  • 24 VDC ****power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
  • Keep away from high voltage lines or power lines to prevent inductive noise. Do not use near the equipment which generates strong magnetic force or high frequency noise.
  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
  • Use twisted pair wire for communication line.
  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in ‘Specifications’)
    – Altitude Max. 2,000 m
    – Pollution degree 2
    – Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .Autonics KN-
2211W Digital Panel Meter -

  1. Alarm output
    0: No ( Option output: Transmission is not available)
    2: 2 alarm
    4: 2 alarm

  2. Option Output
    0: No
    1: PV transmission
    4: Communication
    5: PV transmission + Communication

  3. Power supply
    0: 100-240 VAC ∼ 50/60 Hz
    1: 24 VDC ****

Product Components

  • Product
  • Instruction manual
  • Bracket ×2

Software
Download the installation file and the manuals from the Autonics website.
■ DAQMaster
DAQMaster is comprehensive device management program. It is available for parameter setting, monitoring.

Specifications

Series KN-2000W Series
AC voltage DC voltage
Power supply 100 – 240 VAC- 50/60 Hz
Power consumption ≤ 8 VA
Sampling period • Thermocouple, RTD: 250 ms • Analog: 100 ms
Input specification Refer to ‘Input Type and Using Range’.
Digital input Contact
Non contact • Residual voltage: ≤ 1.0 V • Leakage current: ≤ 0.03 mA
Outflow current ≈ 0.2 mA
Option output Alarm

VAC ∼ 1A la
PV Transmission| ISOLATED DC 4-20 mA (Load resistance: 600 Ω)
RS485 comm.| Modbus RTU
Display type| 7 Segment (Red, Green, Yellow), LED type
Alarm output Hysteresis| 1 to 999 digit
Relay life cycle| Mechanical| · 2 point: ≥ 10,000,000 operations
· 4 point: ≥ 20,000,000 operations
Electrical| · 2 point: ≥ 100,000 operations(Load resistance: 250 VAC ∼ 3 A)
· 4 point: ≥ 500,000 operations (Load resistance: 250 VAC ∼ 1 A)
Dielectric strength| Between input terminal and power terminal: 2,000 VAC ∼ 50/60 Hz for 1 min
Vibration| 0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X, Y, Z direction for 2 hours
Insulation resistance| ≥ 100 MΩ (500 VDC ****megger)
Noise immunity| ±2 kV square shaped noise (pulse width 1 μs) by noise simulator
Memory retention| ≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature| -10 to 50 °C, storage: -20 to 60 °C (no freezing or condensation)
Ambient humidity| 35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Approval|
Unit weight (packaged)| ≈ 200 g (≈ 332 g)

Communication Interface
■ RS485

Comm. protocol Modbus 1.1 RTU
Maximum connection 32 units
Synchronous method Asynchronous
Comm. method Two-wire half duplex
Comm. effective range ≤ 1,200 m (≤ 700 m recommended)
Comm. speed 1,200 / 2,400 / 4,800 / 9,600 (default) / 19,200 bps (parameter)
Data bit 8 bit (fixed)
Parity bit None (fixed)
Stop bit 1 bit (fixed)

Input Type and Using Range

Input type Display Using range (°C) Using range (°F)
Thermo- couple K (CA) – 200.0 to 1350.0
J (IC) – 200.0 to 800.0 – 328.0 to 1472.0
E (CR) – 200.0 to 800.0 – 328.0 to 1472.0
T (CC) – 200.0 to 400.0 – 328.0 to 752.0
R (PR) 0.0 to 1750.0 32 to 3182
B (PR)* 400.0 to 1800.0 752 to 3272
S (PR)* 0.0 to 1750.0 32 to 3182
N (NN)* – 200.0 to 1300.0 – 328 to 237 2
C (W5)* 0 to 2300 32 to 4172
L (IC)* – 200.0 to 900.0 – 328.0 to 1652.0
U (CC)* – 200.0 to 400.0 – 328.0 to 752.0
Platinel II* 0.0 to 1390.0 32 to 2534
RTD Cu500* – 200.0 to 200.0
Cul000* – 200.0 to 200.0 – 328.0 to 392.0
J Pt100 0 -200.0 to 600.0 -328.0 to 1112.0
DPt50 0 – 200.0 to 600.0 – 328.0 to 1112.0
DPt100 0 – 200.0 to 850.0 – 328.0 to 1530.0
Analog Current 0.00 – 20.00 mA

(Display range is variable according to decimal point position.)
4.00 – 20.00 mA
Voltage| – 50.00 – 50.00mV
-200.0 – 200.0mV
1.0000 – 1.0000V
– 1.000 – 10.000V

  • Above input types which have the * mark are not displayed. To display the above input types, supply the power with pressing the [M] key.

■ Display accuracy

Input type Using temperature Display accuracy
Thermocouple RTD At room temperature (25 °C ±5 °C) PV ±0.2% F.S. ±1 digit

• Thermocouple below -100 °C: (PV ±0.4% F.S.) ± ldigit
Out of room temperature range| PV ±0.3% F.S. ±1 digit

  • In case of TC-T, TC-U, ±2.0 ℃ will be added to the degree standard.

Unit Descriptions

Autonics KN-2211W Digital Panel Meter - fig 3

  1. Display part(Red)
    Run mode: Displays PV (Present value).
    Setting mode: Displays parameter and setting value.

  2. Unit Indicator
    Displays the set unit.

  3. Alarm output indicator
    Turns ON when the alarm is ON

  4. [MODE] key
    Used to enter parameter set mode, move to parameters, save SV and return to RUN mode.

  5. [◀], [▲], [▼] key
    Used to enter and change parameter setting value.

  6. Selection switch for input specification

Autonics KN-2211W Digital Panel Meter - fig 4

  • The setting of input type selection switch and the setting value of input type parameter should be same and it can display the proper measurement value.

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.

Autonics KN-2211W Digital Panel Meter - Autonics KN-2211W Digital Panel
Meter

■ Bracket

Autonics KN-2211W Digital Panel Meter - fig 1

■ Panel cut-out

Autonics KN-2211W Digital Panel Meter - fig 2

Connections

Autonics KN-2211W Digital Panel Meter - fig 5

Errors

Display Description Troubleshooting
Flashes when input sensor is disconnected or sensor is not connected.

Check input sensor status.
| Flashes when PV is higher than input range.| When input is within the rated input range, this display
disappears.
| Flashes when PV is lower than input range.
| Flashes when there is an error of setting value| Check the setting condition and reset.
| Flashes when parameter and selection switch setting for input specification are inconsistent| Check input specification.

Mode Setting

Autonics KN-2211W Digital Panel Meter - mood setting

Parameter Setting

  • Some parameters are activated/deactivated depending on the model or setting of other parameters. Refer to the descriptions of each item.
  • [MODE] key: Move to next item after saving / Return to RUN mode after saving (≥ 3 sec)
  • [◀] key: Select parameter / Move digits
  • [▲], [▼] key: Select parameter / Change setting value
  • Return to the upper level without saving when there is no key input for more than 30 seconds.

■ Monitoring mode

Parameter Display Default Setting range Condition
1-1 AL1 alarm temperature Within input range

AL-1/2/3/4 alarm
operation: AT1, AT2
1-2| AL2 alarm temperature| |
1-3| AL3 alarm temperature| | | [4 alarm output model] Same as 1-1/2 AL1/2 alarm temperature
1-4| AL4 alarm temperature| |
1-5| High peak display| | | Check only (not available to set)
Displays high/low peak (Max./Min. input) value
• Initial high/low peak is saved after 2 sec from supplying the power.
• Value reset: [▲] + [▼] key over 3 sec in 1-5/6 High/Low peak display parameter| –
1-6| Low peak display| |

■ Program mode

Parameter| Parameter| Display| Default| Setting range| Condition
---|---|---|---|---|---
2-1| Input specification| | | Refer to ‘Input Type and Using Range’.| –
2-2| Temperature
unit| | | ℃, ℉| 2-1 Input
specification:
Thermocouple, RTD
2-3| Display unit| | | %, OFF, ℃, ℉| 2-1 Input
specification: Analog
2-4| Low limit Input| | | Within input range,
L-RG + 20% of F.S. ≤ H-RG
2-5| High limit Input| |
2-6| Decimal point| | | 0.0, 0.00, 0.000, 0
2-7| Low limit scale| | | -19,999 to 19,999
2-8| High limit scale| | | -19,999 to 19,999
2-9| 4 mA output scale| | | [PV transmission output model] • Input: Thermocouple, RTD: Within input range
• Input: Analog
L-SC ≤ L.OUT + 10% of F.S. ≤ H.OUT ≤ H-SC| –
2-10| 20 mA output scale| |
2-11| Input and transmission output extension 01)| | | [PV transmission output model]

| Setting
value| Input range| Transmission
output range
---|---|---
0P| no extension| 4 – 20 mA
5P| ±5% extension| 3.2 – 20.8 mA
10P| ±10% extension| 2.4 – 21.6 mA
2-1 Input
specification: Analog
2-12| AL1 alarm operation| | | [Alarm output model] □□□
AT0: Off
AT1: Absolute high limit alarm
AT2: Absolute low limit alarm
SBA: Sensor break alarm| –
2-13| AL1 alarm option| A: Standard alarm
C: Standby sequence
B: Alarm latch
D: Alarm latch and standby sequence
• Enter to option setting: Press [◀] key in 2-15 AL-1 alarm operation.| –
2-14| AL2 alarm operation| | | [Alarm output model] Same as 2-12/13 AL1 alarm operation/option| –
2-15| AL2 alarm option
2-16| AL3 alarm operation| | | [4 alarm output model] Same as 2-12/13 AL1 alarm operation/option| –
2-17| AL3 alarm option
2-18| AL4 alarm operation| |
2-19| AL4 alarm option
2-20| Alarm output
hysteresis| | | 001 to 999| 2-12/14/16/18
AL-1/2/3/4
alarm operation: AT1, AT2
2-21| Input special
function| | | LIN: Linear, ROOT: Root, SQAR: Square,
TUF: Two unit function| –
2-22| Input correction| | | -999 to 999| –
2-23| Input digital filter| | | 01 (OFF) to 16| –
2-24| Digital input Terminal| | | HOLD: Hold, ZERO: Zero-point adjustment,
AL.RE: Alarm reset [Alarm output model]| –
2-25| Digital input key| |
2-26| Display color| | | Tabile| –
2-27| Alarm display color 02)| | | [Alarm output model] Select each digit separately.
R: Red, G: Green, Y: Yellow
Autonics KN-2211W Digital Panel Meter - icon 76| –
2-28| Sensor break alarm output| | | [Transmission output model] OFF: 4 mA – 5%, ON: 20 mA + 5%| –
2-29| Comm.
Address| | | [Communication output model] 01to99| –
2-30| Comm. speed| | | [Communication output model] 1.2K: 1200, 2.4K: 2400, 4.8K: 4800,
9.6K: 9600, 19.2K: 19200 bps| –
2-31| Comm. write| | | [Communication output model] EN.A: Enable, DIS.A: Disable| –
2-32| Lock| | | OFF
LOC1: Program mode lock (check only)
Monitoring mode unlock
LOC2: Checking and setting program mode lock
Monitoring mode setting lock (check only)| –

  1. Extension is not allowed below 0 mA and 0 V. ±1 V and 10 V Inputs cannot be set to 10P.
  2. When alarm is cleared, or two alarms operate at the same time, the latest alarm’s color is applied.
    When error occurs during alarm, the set color of ‘Display color’ parameter is applied.

Communication Parameter Setting

  • Read Input Status (Func: 2, R/W: R)
Address Parameter Output range Condition
100001 (0000) AL1 indicator 0: OFF, 1: ON
100002 (0001) AL2 indicator
100003 (0002) AL3 indicator
100004 (0003) AL4 indicator
100005 (0004) °F indicator
100006 (0005) °C indicator
100007 (0006) % indicator

Read Input Register (Func: 4, R/W: R)

Address Parameter Output range Condition
300001 (0000) Present value -19999 – 19999
300002 (0001) Input specification Refer to ‘Input specification parameter
setting/output value’
300003 (0002) Decimal point 0004H: .0000, 0003H: 0.000, 0002H: 0.00, 0001H:
0.0, 0000H: 0 2-1 Input

specification:
Analog
300004 (0003)| PWM OUT| 0 – 20000| –
300005 (0004)| X (MSB)| |
0/0 indicator| 0: OFF, 1: ON| –
°C indicator
°F indicator
AL4 indicator
AL3 indicator
AL2 indicator
AL1 indicator
(LSB)

Program mode setting group (Func: 03/06/16, R/W: R/W)

Address Parameter Display Setting range Condition
400001 (0000) Input specification Refer to ‘Input specification parameter
setting/output value’ Sameas each parameter setting condition
400002 (0001) Temperature unit 0: °C, 1: °F
400003 (0002) Display unit 0: °C, 1: °F, 2: %, 3: OFF
400004 (0003) High limit Input Same as parameter setting range
400005 (0004) Low limit Input
400006 (0005) High limit scale Same as parameter setting range
400007 (0006) Low limit scale
400008 (0007) Input correction Same as parameter setting range
400009 (0008) Input digital filter Same as parameter setting range
400010 (0009) ALl alarm operation 1:Absolute high limit alarm

2:Absolute low limit alarm
3:Sensor break alarm
4:No alarm
400011 (000A)| AL2 alarm operation
400012 (000B)| AL3 alarm operation
400013 (000C)| AL4 alarm operation
400014 (000D)| ALl alarm option| 10:Standard alarm
11:Alarm latch
1Z Standby sequence
13: Alarm latch and standby sequence
400015 (000E)| AL2 alarm option
400016 (000F)| AL3 alarm option
400017 (0010)| AL4 alarm option
400018 (0011)| Alarm output hysteresis| | Same as parameter setting range
400019 (0012)| 20 mA output scale| | Same as parameter setting range
400020 (0013)| 4 mA output scale|
400021 (0014)| Decimal point| | 0004H: .0000, 0003H: 0.000, 0002H: 0.00, 0001H: 0.0, 0000H: 0
400022 (0015)| Input and transmission output extension| | 0: 0%,1: 5%, 2: 10%
400023 (0016)| Digital input Terminal| | 0: Alarm reset, E Hold,
Z Zero-point adjustment
400024 (0017)| Digital input key|
400025 (0018)| Inputspecial function| | 0: Linear, L. Root, Z Square, 3: Two Unit Function
400026 (0019)| Sensor break alarm output| | 0: ON, 1: OFF
400027 (001A)| Lock| | 0: OFF, 1: LOCK1, 2: LOCK2
400028 (001B)| Display color| | 0: Red, E Green, Z Yellow, 3: Red-Green, 4: Green-Red
400029 (001C)| ALl display color| | 0: Red, L Green, 2: Yellow
400030 (001D)| AL2 display color
400031 (001E)| AL3 display color
400032 (001F)| AL4 display color
400033 (0020)| Comm. address| | Same as parameter setting range
400034 (0021)| Comm. speed| | 0: 192000,1: 9600, 2: 4800,
3: 2400, 4: 1200
400035 (0022)| Comm. write| | 0: Disable, E Enable

  • Func : Read Holding Register/Preset Single Register/Preset Multiple Register

Monitoring mode setting group (Func: 03/06/16, R/W: R/W)

Address Parameter Display Setting range Condition
400051 (0032) ALl alarm temperature Same as parameter setting range Same

as each
parameter setting
condition
400052 (0033)| AL2 alarm temperature|
400053 (0034)| AL3 alarm temperature|
400054 (0035)| AL4 alarm temperature|
400055 (0036)| High peak display| | Same as parameter setting range
400056 (0037)| Low peak display|

■ Input specification parameter setting/output value

Input spec. Display Value
Thermocouple 1

2
3
4
5
6
7
8
9
10
11
RTD| | 12
13
14
15
16
Analog| Current| 17
18
Voltage| 19
20
21