REMCO INDUSTRIES 3300 Series Pumps Installation Guide
- June 10, 2024
- REMCO INDUSTRIES
Table of Contents
REMCO INDUSTRIES 3300 Series Pumps
Product Information
The 3300 Series Pumps are designed to operate in a variety of applications that require the transfer of liquids. These pumps are equipped with either a pressure-sensing demand switch, a bypass relief valve, or both which controls the maximum safe operating pressure. The pump can be mounted horizontally or vertically, and flexible tubing with proper pressure rating is recommended for plumbing. It is important to note that the pump should not be operated above the pressure limitations specified on the data label and should not be used with gasoline or other flammable liquids.
Cautions
- Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained in accordance with Federal, State, and local codes.
- Do not operate the pump above the pressure limitations specified on the data label.
- Never operate the pump in a harsh environment or hazardous atmosphere, since the motor brush and switch may cause electrical arcing.
- Do not pump gasoline or other flammable liquids. Do not use petroleum products.
- Do not assume fluid compatibility. If the fluid is improperly matched to the pumps’ elastomers, a leak may occur.
- As long as there is inlet water pressure, the pump will not stop the forward flow of water even if the motor is turned off. Be sure the system has positive means of shutting off the water supply.
- Always consider electrical shock hazards when working with and handling electrical equipment. If uncertain, consult an Electrician. Electrical wiring should only be done by a qualified Electrician per Local and State Electrical Codes.
Product Usage Instructions
- Read the Operational and Installation Guidelines carefully before starting to install the pump. Consult the Factory if there is any question.
- Determine the optimum location for your pump before proceeding.
- Turn off the fluid supply.
- Cut the flexible tubing in a sufficient length to avoid any stress on the tubing or hose where it connects to the pump or the fitting on any accessory or hose.
- Insert tubing or hose into pump ports. If compression fittings with threaded nuts are used, insert the tubing until it bottoms out in the port and hand tighten the compression nut until the connection is tight. Then use a wrench to tighten the nut 1/2 turn clockwise or follow the wrench tightening instructions provided by the fitting manufacturer.
- The pump should always be mounted prior to any components which could introduce particles to the liquid; thus, preventing them from entering the pump chambers and possibly causing clogging.
- If a power supply is used with the system and the supply is not furnished by REMCO, it will need to be reviewed for correct application and approval by REMCO.
Safety Information
Please read these Operational and Installation Guidelines before installing the 3300 Series Pumps. If additional help is needed, please consult the Factory.
CAUTIONS
-
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained in accordance with Federal, State, and local codes.
-
Do not operate the pump above the pressure limitations specified on the data label.
-
Never operate the pump in a harsh environment or hazardous atmosphere, since the motor brush and switch may cause electrical arcing.
-
Do not pump gasoline or other flammable liquids. Do not use petroleum products.
Do not assume fluid compatibility. If the fluid is improperly matched to the pumps’ elastomers, a leak may occur -
As long as there is inlet water pressure, the pump will not stop the forward flow of water even if the motor is turned off. Be sure the system has positive means of shutting off the water supply.
-
Always consider electrical shock hazards when working with and handling electrical equipment. If uncertain, consult an Electrician. Electrical wiring should only be done by a qualified Electrician per Local and State Electrical Codes.
MOUNTING
- The pump should be mounted in a dry place and away from any source of heat. If an enclosure is used, special instructions for cooling the motor may be necessary. Consult the Factory.
- Do not subject the pump to extremely high or low (freezing) temperatures while in operation. (Operating ambient temperature range is 32ºF to 115ºF).
- The pump may be mounted horizontally with the outlet port on the right when viewed from the pump end or with the pump above the mount; or vertically with the pump above or below the motor.
PLUMBING
- The pump is equipped with either a pressure-sensing demand switch, a bypass relief valve, or both which controls the maximum safe operating pressure.
- We recommend the use of flexible tubing with proper pressure rating.
- The pump will prime only if all pressure is relieved from the outlet port.
- It is recommended that debris-free liquid be pumped or an in-line sediment filter (50 mesh) be installed at the inlet side to keep foreign debris out of the system.
- The pump should always be mounted prior to any components which could introduce particles to the liquid; thus, preventing them from entering the pump chambers and possibly causing clogging.
- Avoid any sharp bends which may crimp tubing and restrict flow. Use 90º elbow fittings if necessary. REMCO provides pumps with different kinds of fittings. Please consult Factory for your needs.
ELECTRICAL
- The 3300 Series Pumps are designed for intermittent duty but may run continuously if the motor temperature does not exceed the recommended limit. Some 3300 Series Pumps are equipped with thermally protected motors and in case motor temperature exceeds the thermal cut-out rating, the pump will shut down and will not restart until the motor cools down to a specified temperature. Please consult the appropriate Data Sheet for continuous running parameters, noting the effect of rapid On/Off Cycling (See section below).
- If a power supply is used with the system and the supply is not furnished by REMCO, it will need to be reviewed for correct application and approval by REMCO.
Installation Procedure
The basic demand pump is controlled by a built-in pressure-sensing demand switch. When a faucet or valve is opened downstream of the pump, line pressure drops, thus starting the pump automatically. Conversely, when the valve shuts, the line pressure increases turning the pump off automatically. The pressure switch actuates in response to the pump outlet pressure at a predetermined and preset pressure. The pump label indicates the pre-set OFF pressures. Typically, the OFF pressure is accurately set at the FACTORY and the ON pressure is within an allowable range below that value. In response to the characteristics of the system in which the pump is installed, such as the flexibility and length of the tubing, the faucet or valves, and the duration that they are open, these pressure settings may vary. Therefore, change in pressure settings is expected with use and over time. If the pump does not have an integral pressure sensing demand switch (i.e. pump is operated with external control), the pump will be equipped with a bypass relief valve (bypass is factory preset).
Read the OPERATIONAL AND INSTALLATION GUIDELINES on the other side carefully before starting to install the pump. Consult the Factory if there is any question.
Determine the optimum location for your pump before proceeding.
-
Turn off the fluid supply.
-
Cut the flexible tubing in a sufficient length to avoid any stress on the tubing or hose where it connects to the pump or the fitting on any accessory or hose.
-
Insert tubing or hose into pump ports. If compression fittings with threaded nuts are used, insert the tubing until it bottoms out in the port and hand tighten the compression nut until the connection is tight. Then use a wrench to tighten the nut 1/2 turn clockwise or follow the wrench tightening instructions provided by the fitting manufacturer.
-
The 3300 Series pump is now ready for operation. Open the inlet valve if any to allow fluid to flow to the pump.
-
If the power source is a transformer, plug the appropriate REMCO-supplied or approved transformer into the receptacle and connect the pump to the transformer. If the power source is not a transformer,
connect the pump to the appropriate power source. Open the discharge or dispensing valve. Allow water to circulate, purging any entrapped air. -
The pump will now start building pressure. Operating pressure will vary with flow rate, flow valve, feed-water pressure, and line voltage. Check for fitting leaks.
-
If compression fittings with threaded nuts are used, observe any leaks after the pump has run for approximately 15 minutes. Further, tighten
compression nuts approximately 1/8 to 1/4 of a turn on all fittings in the system. Wait 15 minutes and repeat the leak check.
NOTE: Further adjustments should not be necessary although it may take several days of operation before all the air has been purged and the system is stabilized. -
Rapid On/Off Cycling must be limited to no more than 6 times per minute, even if the pump is operating in the Continuous Duty zone. Cycling could cause the motor to heat beyond the recommended maximum temperature, and reduce the operational life of the pump and pressure-sensing switch.
Troubleshooting Guidelines
IF THE PUMP WILL NOT START CHECK:
- Correct voltage (±10%) and electrical connections
- Fuse or breaker
- Pressure switch operation and correct voltage at the switch
- Rectifier or motor for open or grounded circuit
IF THE PUMP WILL NOT PRIME (NO DISCHARGE WITH THE MOTOR RUNNING) CHECK:
- Debris in strainer
- Restriction (kinks) in inlet/outlet tubes
- Debris in inlet/outlet
- Air leaking in from inlet
IF THE PUMP WILL NOT SHUT OFF (OUTPUT LINE CLOSED AND NO LEADS) CHECK:
- Air trapped in outlet line or pump head
- Correct voltage to the pump
- Debris in pump inlet/outlet valves
- Loose drive assembly or pump head screws
- Pressure switch operations/adjustments
- Leaks
IF THE PUMP LEAKS FROM THE PUMP HEAD OR SWITCH CHECK:
- Loose screws at the switch or pump head
- Switch diaphragm ruptured or pinched
- Punctured diaphragm if fluid is present
Warranty
REMCO warrants its products to be free from defects in material and workmanship on all products sold by REMCO for resale or for use in purchasers’ own business or original equipment manufacturer. Under normal use, maintenance, and service (rental use excluded) the following terms apply: For all REMCO products, the warranty will last for a period of one year from the date of manufacture, or (1) year of use with proof of purchase, not to exceed (2) years in any event. REMCO’s obligation under this warranty shall be limited to replacing or repairing at REMCO’s discretion, any such product or part which must be returned to REMCO’s factory with a Return Material Authorization Number (RMA), transportation charges approved by REMCO or prepaid, and which upon examination, is found to REMCO’s satisfaction to have been defective under the terms of this warranty. No credit will be allowed against future purchases for items returned as defective under the terms of REMCO’s warranty.
This warranty does not extend to any products, which have been altered or modified outside the REMCO factory, to any products that have not been properly maintained, nor does it apply to units that are returned in an unassembled condition. Furthermore, the warranty does not extend to pumps that are non-compliance with REMCO’s Engineering Standards. This includes but is not limited to, pumps ordered without an integral pressure control mechanism. The warranty guarantees that products will perform to REMCO’s flow and pressure specifications throughout the life of the warranty. The warranty does not cover wear, appearance, misuse, abuse, misapplication or external water damage. If the returned product is found not to be defective under the conditions of this warranty, a charge will be made for repair or replacement.
Brush wear may be limited to 1000 hours or less.
This is a Limited Warranty. It covers the product only and the extent of the coverage is limited to the cost of the product. As the manufacturer has no control over shipping, handling, and installation, the warranty cannot cover water damage, or any other damage, caused by a leak or other malfunction.
THIS WARRANTY IS IN LIEU OF ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING IMPLIED WARRANTIES OR WARRANTIES OF MERCHANTABILITY AND/OR FITNESS FOR A PARTICULAR PURPOSE. NO PERSON IS AUTHORIZED TO GIVE ANY OTHER WARRANTY OR ASSUME OBLIGATION OR LIABILITY ON REMCO’S BEHALF. REMCO SHALL NOT BE LIABLE FOR ANY INDIRECT, INCIDENTAL, PUNITIVE OR CONSEQUENTIAL DAMAGES OF ANY KIND INCURRED BY THE REASON OF THE USE OR SALE OF ANY DEFECTIVE PRODUCT AND PART. THIS WARRANTY SHALL BE GOVERNED BY THE LAWS OF THE STATE OF MINNESOTA, WITH ANY DISPUTE OR CLAIM VENUED OR HEARD IN THE STATE OF MINNESOTA.
WARNING:
Cancer and Reproductive Harm
www.P65WARNINGS.CA.GOV.
Replacement Parts
-
Lower Housing Assembly**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
LHA7860-7F77| 1.2GPM| DEMAND OR BYPASS, SANTOPRENE
LHA7863-7F77| 2.2GPM| DEMAND OR BYPASS, SANTOPRENE
LHA78LUBE-2X77| 2.2GPM| DEMAND OR BYPASS, GEOLAST -
Valve Housing Assembly**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
VHA7863-7F77| 1.2-2.2GPM| DEMAND OR BYPASS, VITON VALVES -
Upper Housing Assembly**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
UHA7880-7F77| 1.2-2.2GPM| 3/8” THREADED W/PRESSURE SWITCH
UHA7880-8F77| 1.2-2.2GPM| 3/8” THREADED W/BYPASS
UHA7863-7F77| 1.2-2.2GPM| 5/8” QUICK ATTACH W/PRESSURE SWITCH
UHA7863-8F77| 1.2-2.2GPM| 5/8” QUICK ATTACH W/BYPASS
UHA7803-7F77| 1.2-2.2GPM| 3/4” QUICK ATTACH W/PRESSURE SWITCH
UHA7803-8F77| 1.2-2.2GPM| 3/4” QUICK ATTACH W/BYPASS -
Mounting Bolt Kit**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
3300-SK| 1.2-2.2GPM| 7 MOUNTING BOLTS W/WASHERS -
Pressure Switch Assembly**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
3300-PSW| 1.2-2.2GPM| 60PSI PRESSURE SWITCH -
Complete Pumphead Assembly**
PART NUMBER| GPM| DESCRIPTION**
---|---|---
7880-7F777| 1.2GPM| 3/8” THREADED W/PRESSURE SWITCH
7880-8F77| 1.2GPM| 3/8” THREADED W/BYPASS
7883-7F77| 2.2GPM| 3/8” THREADED W/PRESSURE SWITCH
7883-8F77| 2.2GPM| 3/8” THREADED W/BYPASS
7860-7F77| 1.2GPM| 5/8” QUICK ATTACH W/PRESSURE
7860-8F77| 1.2GPM| 5/8” QUICK ATTACH W/BYPASS
7863-7F77| 2.2GPM| 5/8” QUICK ATTACH W/PRESSURE SWITCH
7863-8F77| 2.2GPM| 5/8” QUICK ATTACH W/BYPASS
7803-7F77| 2.2GPM| 3/4” QUICK ATTACH W/PRESSURE SWITCH
7803-8F77| 2.2GPM| 3/4” QUICK ATTACH W/BYPASS -
Motor****
PART NUMBER | GPM | DESCRIPTION |
---|---|---|
M382-S | 1.2-2.2GPM | SEALED DEMAND MOTOR W/2 PIN CONNECTOR |
M382B-S | 1.2-2.2GPM | SEALED BYPASS MOTOR W/2 PIN CONNECTOR |
Servicing
EVERY USE
Run clean water through the pump and system.
EVERY YEAR
Check the system against operating standards. If continuous duty, replace
lower housing assembly
EVERY OTHER YEAR
Check against operating standards. If continuous duty, replace motor
EVERY FIFTH YEAR
Replace valves
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>