Hydro Pro R410A Swimming Pool Heat Pump Unit Instruction Manual

June 10, 2024
Hydro Pro

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-logo

Hydro Pro R410A Swimming Pool Heat Pump Unit

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-product-
image

PREFACE

  • In order to provide our customers with quality, reliability and versatility, this product has been made to strict production standards. This manual includes all the necessary information about installation, debugging, discharging and maintenance. Please read this manual carefully before you open or maintain the unit. The manufacture of this product will not be held responsible if someone is injured or the unit is damaged, as a result of improper installation, debugging, or unnecessary maintenance. It is vital that the instructions within this manual are adhered to at all times. The unit must be installed by qualified personnel.

  • The unit can only be repaired by qualified installer center , personnel or an authorized dealer.

  • Maintenance and operation must be carried out according to the recommended time and frequency, as stated in this manual.

  • Use genuine standard spare parts only.
    Failure to comply with these recommendations will invalidate the warranty.

  • Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant. For split type unit, The indoor unit can be Discretely hidden or semi-hidden to suit a luxury house.

Our heat pump has following characteristics:

  1. Durable
    The heat exchanger is made of PVC & Titanium tube which can withstand prolonged exposure to swimming pool water.

  2. Installation flexibility
    The unit can be installed outdoors or indoors.

  3. Quiet operation
    The unit comprises an efficient rotary/ scroll compressor and a low-noise fan motor, which guarantees its quiet operation.

  4. Advanced controlling
    The unit includes micro-computer controlling, allowing all operation parameters to be set. Operation status can be displayed on the color screen wire controller. Remote controller can be chosen as future option.

SPECIFICATION

Performance data of Swimming Pool Heat Pump Unit

***REFRIGERANT: R41 QA

Model PC130/R410A
Heating capacity °(27/24.3 C) kW 34.4~129
Btu/h 118000~440000
Heating Power Input kW 2.76~23.3
COP 12.4~5.54
Heating capacity ° (15/12 C) kW 23.2~103.9
Btu/h 79200~351000
Heating Power Input kW 2.44~25.4
COP 9.5~4.1
Heating capacity ° (10/6.8 C) kW 18.6~93.5
Btu/h 63500~319000
Heating Power Input kW 2.1~27.5
COP 8.6~3.4
Power Supply 380V/3N~/50Hz
Compressor Quantity 1
Compressor Scroll
Fan Number 2
Noise(1Om) dB(A) 60~64
Water Connection mm 63
Water Flow Volume m3/h 45.9
Water Pressure Drop(max) kPa 25
Unit Net Dimensions(L/W/H) mm See the drawing of the units
Unit Ship Dimensions(L/W/H) mm See package lable
Net Weight kg see nameplate
Shipping Weight kg see package label

Heating: Outdoor air temp: 27 C/24.3C, Inlet water temp:26C
Outdoor air temp: 15C/12C, Inlet water temp:26C
Outdoor air temp: 10’C/6.8’C, Inlet water temp:26C

Operating range:

  • Ambient temperature: -15-43C
  • Water temperature: 9-40C

The dimensions for Swimming Pool Heat Pump Unit
Model: PC130/R41 QA
unit: mm

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-01

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-02

INSTALLATION AND CONNECTION

Installation illustration

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-03

Installation items:
The factory only provides the main unit and the water unit; the other items in the illustration are necessary spare parts for the water system ,that provided by users or the installer.

Attention:
Please follow these steps when using for the first time

  1. open valve and charge water.
  2. Make sure that the pump and the water-in pipe have been filled with water.
  3. Close the valve and start the unit.

ATTN: It is necessary that the water-in pipe is higher than the pool surface.

The schematic diagram is for reference only. Please check the water inlet/outlet label on the heat pump while plumbing installation.

Swimming Pool Heat Pumps Location
The unit will perform well in any outdoor location provided that the following three factors are presented:

  1. Fresh Air – 2. Electricity – 3. Pool filter piping

The unit may be installed virtually anywhere outdoors. For indoor pools please consult the supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area.

DO NOT place the unit in an enclosed area with a limited air volume, where the units discharge air will be re-circulated.

DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery.

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-04

How Close To Your Pool?
Normally, the pool heat pump is installed within 7 .5 meters of the pool. The longer the distance from the pool, the greater the heat loss from the piping. For the most part ,the piping is buried. Therefore, the heat loss is minimal for runs of up to15 meters(15 meters to and from the pump= 30 meters total), unless the ground is wet or the water table is high. A very rough estimate of heat loss per 30 meters is 0.6 kW-hour,(2000BTU) for every 5 °C difference in temperature between the pool water and the ground surrounding the pipe, which translates to about 3% to 5% increase in run time.

Swimming Pool Heat Pumps Plumbing
The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no special plumbing arrangements except bypass(please set the flow rate according to the nameplate). The water pressure drop is less than 1 0kPa at max. Flow rate. Since there is no residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC pipe can be run straight into the unit.
Location: Connect the unit in the pool pump discharge (return) line downstream of all filter and pool pumps, and upstream of any chlorinators, ozonates or chemical pumps.

Standard model have slip glue fittings which accept 40mm NB PVC pipe for connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 50NB PVC piping

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required.

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-05

Condensation: Since the Heat pump cools down the air about 4 -5 C, water may condense on  the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could be as much as several liseran hour. The water will run down the fins into the baseman and drain out through the barbed plastic condensation drain fitting on the side of the baseman. This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the unit.

NB: A quick way to verify that the water is condensation is to shut off the unit and keep the pool pump running. If the water stops running out of the base pan, it is condensation. AN EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE – if the is no chlorine present, then it’s condensation.

Swimming Pool Heat Pumps Electrical Wiring
NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it simply prevents the flow of electricity to or from the pool water. Grounding the unit is still required to protect you against short circuits inside the unit. Bonding is also required.
The unit has a separate molded-in junction box with a standard electrical conduit nipple already in place. Just remove the screws and the front panel, feed your supply lines in through the conduit nipple and wire-nut the electric supply wires to the three connections already in the junction box (four connections if three phase). To complete electrical hookup, connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as permitted by local electrical authorities) to a dedicated AC power supply branch circuit equipped with the proper circuit breaker, disconnect or time delay fuse protection.

Disconnect -A disconnect means (circuit breaker , fused or un-fused switch) should be located within sight of and readily accessible from the unit, This is common practice on commercial and residential air conditioners and heat pumps. It prevents remotely-energizing unattended equipment and permits turning off power at the unit while the unit is being serviced.

Initial startup of the Unit
NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to circulate water through the heat exchanger.

Start up Procedure -After installation is completed, you should follow these steps:

  1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
  2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire controller, It should start in several seconds.
  3. After running a few minutes make sure the air leaving the top(side) of the unit is cooler(Between 5-10 ‘C)
  4. With the unit operating turn the filter pump off. The unit should also turn off automatically,
  5. Allow the unit and pool pump to run 24 hours per day until desired pool water temperature is reached. When the water-in temperature reach setting, The unit just shuts off. The unit will now automatically restart (as long as your pool pump is running)when the pool temperature drops more than 2’Cbelow set temperature.

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter. This time delay will automatically restart the unit approximately 3 minutes after each control circuit interruption. Even a brief power interruption will activate the solid state 3 minute restart delay and prevent the unit from starting until the 5 minute countdown is completed. Power interruptions during the delay period will have no effect on the 3 minute countdown.

USAGE AND OPERATION

Color screen wire controller interface introduction

  1. Main interface
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-06

  2. Button Description
    NO.| Name| The button function
    ---|---|---
    G)| ON/OFF| Press to start /shut off the unit
    @| Parameter| Click this button to view the unit state and the parameter
    @| CLOCK| Press to set the clock, the timer on or timer off. When the timer was starting. the button is green
    ©| Fault display| Click to view fault history
    ®| Silent setting| Click to turn on/off silent function and to set timing Low speed function.
    ®| MODE| Click to enter mode setting and the target temp. Setting interface
    (J)| Temp. curve| Click to view the temp. and power curve
    ®| Water Inlet Temp.| Click to enter mode setting and the target temp. Setting interface
    ®| LOCK| Click to lock the screen , Input “22” to unlock the screen by press the “lock button”

Color screen wire controller function introduction

  1. Booting and shutdown
    As shown in figure 1.1:
    In shutdown status, press G) then the unit will be booted
    In booting status, press G) then the unit will be shut down.

  2. Mode switch and target temperature Setting

  3. Mode switch
    In the main screen, click mode button or inlet water temperature setting button, interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-07Click the refrigeration mode button G), automatic mode button@ or heating mode button @then you can select the corresponding mode
    Note: when the unit is designed for single automatic mode or single thermal mode, the mode can not be switched.

  4. Target temp setting
    Click the temperature set button @, you can set the target temperature.

  5. (3) Clock setting
    In the main interface, click on the clock Settings button, interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-08

  6. The operation of time setting
    Click on the time Settings button G) , interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-09Click the value to set time directly, the click confirm button to save the Settings.
    For example: setup time: the 30-11-2016 16:00:00, input 30 11 16 16 00 00 , the time change then click confirm button.
    Note: if the input format is not correct, the wrong time will be saved by clicking confirm button.
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-10 NO.| Name| Button color| Button function
    ---|---|---|---
    CD| Timing stat button| Start: green End: gray| Click this button to start or end timing start setting function
    @| Timing on setting| | Click to set start time of the timing
    ®| Timing end button| Open: red End: gray| Click this button to start or end timing end setting function
    ©| Timing off setting| | Click to set end time of the timing

Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-11When the timer was starting, the clock button is green in the main interface

  1. Silent setting and silent timing setting
    Click the silent setting button ,and the interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-12

  2. The silent button
    Click the silent button 1, the unit will enter the silent mode, and interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-13Click the silent button 1 again, to exit the silent mode.

  3. Timing silent function setting
    Click timing silent button 2 , and interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-13 NO.| Name| Color| Function
    ---|---|---|---
    G)| Timing silent off| Used: red Unused: gray| Click to use or unused timing off function
    @| Timing silent on| Use: green Unused: gray| Click to use or unused timing on function
    @| Timing silent start time| | Click this button to set the timing silent start time
    @| Timing silent end time| | Click this button to set the timing silent end time

Start time and end time setting value must be among the range of 0:00-23:00,and setting value can be precise to hour digit.
For example above, click “ON”to use timing silent,
the unit will start the silent at 0:00 points and end at 4:00;
click “OFF” to unused the timing silent, but if the unit is in timing silent mode, it will exit silent timing immediately.

  1. History of the fault
    In the main screen click fault display key, interface displays as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-15If no failure, main interface displays static” ”
    When fault occurs, the fault icon will flash between the “ ” ” the failure interface will record time, code, name of the fault. After troubleshooting, if you do not check the failure record, the main interface will display static ” “: if you check the failure record, the main interface will displays static ” ”
    Failure record is in reverse order, according to the happening time.
    Press the “Clean” key, you can delete the fault record.

  2. Color Display Calibration
    Keep click quickly at the blank area on any interface till you hear a long beep. Then you will enter the calibration interface. Click “+” to start calibration. When you hear the beep again, you will finish calibration and exit. Remark: the wire controller can display the temperature unit as “”F” or”C” accardina to the unit madelvou hauaht

  3. Temperature curve
    In the main interface, click the curve display button, interface displays as follows:

  4. Temperature recording curve is as follows:
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-16

  5. The average power curve
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-18Temperature curve automatically updates every one hour, and the curve record can be stored for 60 days;
    Start from the latest curve saved time, if power is off and curve data collecting time is less than one hour, the data in this period will not be saved;

  6. Parameter list and breakdown table

  • Electronic control fault table
    Can be judged according to the remote controller failure code and troubleshootingProtect/fault| Fault display| Reason| Elimination methods
    ---|---|---|---
    Inlet Temp. Sensor Fault| P01| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Outlet Temp. Sensor Fault| P02| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Ambient Temp. Sensor Fault| P04| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Coil 1 Temp. Sensor Fault| P05| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Coil 2 Temp. Sensor Fault| P15| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Suction Temp. Sensor Fault| PO?| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Discharge Temp. Sensor Fault| P081| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
    Exhaust Air over Temp Prat.| P082| The compressor is overload| Check whether the system of the compressor running normally
    Antifreeze Temp. Sensor Fault| P09| Antifreeze temp sensor is broken or short circuited| check and replace this temp sensor
    Pressure sensor Fault| pp| The pressure Sensor is broken| Check or change the pressure Sensor or pressure
    High Pressure Prat.| E01| The high-preesure switch is broken| Check the pressure switch and cold circuit
    Low Pressure Prat.| E02| Low pressure1 protection| Check the pressure switch and cold circuit
    Flow Switch Prat.| E03| No water/little water in water system| Check the pipe water flow and water pump
    Waterway Anti-freezing Prat.| E05| Water temp.or ambient temp. is too low|
    Inlet and outlet temp. too big| E06| Water flow is not enough and low differential pressure| Check the pipe water flow and whether water system is jammed or not
    Anti-freezing Pro!.| E07| Water flow is not enough| Check the pipe water flow and whether water system is jammed or not
    Primary Anti-freezing Prat.| E19| The ambient temp. Is low|
    Secondary Anti-freezing Prat.| E29| The ambient temp. Is low|
    Comp. Overcurrent Prat.| E051| The compressor is overload| Check whether the system of the compressor running normally
    Communication Fault| E08| Communication failure between

wire controller and mainboard

| Check the wire connection between remote wire controller and main board
Communication Fault

(speed control module)

| E081| Speed control module and main

board communication fail

| Check the communication connection
Lowe Protection| TP| Ambient temp is too low|
EC fan feedback Fault| F051| There is something wrong with fan motor and fan motor stops running| Check whether fan motor is broken or locked or not
Fan Motor1 Fault| ****

F031

| 1. Motor is in locked-rotor state 2.The wire connection between DC-fan motor module and fan motor is in bad contact| 1. Change a new fan motor

2. Check the wire connection and make sure they are in good contact

Fan Motor2 Fault| F032| 1. Motor is in locked-rotor state 2.The wire connection between DC-fan motor module and fan motor is in bad contact|

1. Change a new fan motor
2. Check the wire connection and make sure they are in good contact  

---|---|---|---

Frequency conversion board fault table:

Protection/taut Fault display F01 Reason Elimination methods
Drv1 MOP alarm MOP drive alarm Recovery after the 150s
Inverter offline F02 Frequency conversion board and main board communication
failure Check the communication connection
1PM protection F03 1PM modular protection Recovery after the 150s
Comp. Driver Failure F04 Lack of phase, step or drive hardware damage Check

the measuring voltage check frequency conversion board hardware
DC Fan Fault| F05| Motor current feedback open circuit or short circuit| Check whether current return wires connected motor
1PM Overcurrent| F06| 1PM Input current is large| Check and adjust the current measurement
Inv. DC Overvoltage| F07| DC bus voltage>Dc bus over-voltage protection value| Check the input voltage measurement
Inv. DC Less voltage| F08| DC bus Volta e<Dc bus over-voltage protection value| Check the input voltage measurement
Inv. Input Lescot.| F09| The input voltage is low, causing the input current is high| Check the input voltage measurement

Inv. Input Overvolt.

| F10| The input voltage. e is too high, more than outage protection current RMS| Check the input It age   measurement

Inv. Sampling Volt.

| F11| The input voltage sampling fault| Check and adjust the current measurement
Comm. Err DSP-PFC| F12| DSP and PFC connect fault| Check the communication connection
Input Over Cur.| F26| The equipment load is too large|
PFC fault| F27| The PFC circuit protection| Check the PFC switch tube short circuit or not
1PM Overheating| F15| The 1PM module is overheat| Check and adjust the current measurement
Weak Magnetic Warn| F16| Compressor magnetic force is not enough|
Inv. Input Out Phase| F17| The input voltage lost phase| Check and measure the voltage adjustment
1PM Sampling Cur.| F18| 1PM sampling electricity is fault| Check and adjust the current measurement
Inv. Temp. Probe Fail| F19| Sensor is short circuit or open circuit| Inspect and replace the sensor
Inverter Overheating| F20| The transducer is overheat| Check and adjust the current measurement
Inv. Overheating Warn|  F22| Transducer temperature is too high| Check and adjust the current measurement
Comp. Over Cur. Warn| F23|  Compressor electricity is large| The compressor over-current protection
Input Over Cur. Warn| F24| Input current is too large| Check and adjust the current measure men
EEPROM Error Warn| F25| MCU error I| Check whether the chip is damaged Replace the chip I
V15V over/under voltage fault| F28| The V15V is overload or under voltage Check the V15V input voltage in range 13.5v-16.5v or not

  • Parameter list
    Meaning| Default| Remarks
    ---|---|---
    Refrigeration target temperature set point| 27°C| Adjustable
    Heating the target temperature set point| 27°C| Adjustable
    Automatic target temperature set point| 21°c| Adjustable

Interface drawing

  1. Wire control interface diagram and definition
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-21Sign| Meaning
    ---|---
    V| 12V ( power+ )
    R| No use
    T| No use
    A| 485A
    B| 485B
    G| GND (power-)
  2. Controller interface diagram and definition
    Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-19 Hydro-Pro-R410A-Swimming-Pool-Heat-Pump-Unit-20

Main board of the input and output interface instructions below

Number Sign Meaning
01 OUT1 Compressor ( output 220-230VAC )
02 OUT2 Water pump ( output 220-230VAC )
03 OUT3 4-way valve ( output 220-230VAC )
04 OUT4 High speed of fan ( output 220-230VAC)
05 OUT5 Low speed of fan (output 220-230VAC)
06 AC-L Live wire ( input 220-230VAC )
07 AC-N Neutral wire ( input 220-230VAC )
08 AI/DI01 Emergency switch ( input)
09 AI/DI02 Water flow switch ( input)
10 AI/DI03 System low pressure ( input)
11 AI/DI04 System high pressure ( input)
12 AI/DI05 System suction temperature ( input)
13 AI/DI06 Water input temperature ( input)
14 AI/DI07 Water output temperature (input)
15 AI/DI08 System fan coil 1 temperature ( input)
16 AI/DI09 Ambient temperature ( input)
17 AI/DI10 Mode switch /System fan coil 2 temperature ( input)
18 Al/DI11 Master-slave machine switch/ Antifreeze temperature ( input)
19 Al 12(50K) System Exhaust temperature ( input)
20 0_5V_IN Compressor current detection/Pressure sensor(input)
21 PWM_IN Master-slave machine switch/ Feedback signal of EC fan (input)
22 PWM_OUT AC fan control (output)
23 O_10V_OUT EC fan control (output)
24 +5V +5V (output)
25 +12V +12V (output)
26 CN2 Frequency conversion board communications
27 CN8 Color line controller communication
28 CN9 Electronic expansion valve
29 CN13 The port for centralized control

MAINTENANCE AND INSPECTION

  • Check the water supply device and the release often. You should avoid the condition of no water or air entering into system, as this will influence unit’s performance and reliability. You should clear the pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.

  • The area around the unit should be dry, clean and well ventilated. Clean the side heating exchanger regularly to maintain good heat exchange as conserve energy .

  • The operation pressure of the refrigerant system should only be serviced by a certified technician
    Check the power supply and cable connection often,. Should the unit begin to operate abnormally, switch it off and contact the qualified technician.

  • Discharge all water in the water pump and water system ,so that freezing of the water in the pump or water system does not occur. You should discharge the water at the bottom of water pump if the unit will not be used for an extended period of time. You should check the unit thoroughly and fill the system with water fully before using it for the first time after a prolonged period of no usage.

APPENDIX

Caution & Warning

  1. The unit can only be repaired by qualified installer center personnel or an authorized dealer(for Europe market).

  2. This appliance can used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved(for Europe market).
    Children shall not play with the appliance .Cleaning and user maintenance shall not be made by children without supervision.

  3. Please make sure that the unit and power connection have good earthing, otherwise may cause electrical shock.

  4. If the supply cord is damaged, it must be replaced by the manufacturer or our service agent or similarly qualified person in order to avoid a hazard.

  5. Directive 2002/96/EC (WEEE):
    The symbol depicting a crossed-out waste bin that is underneath the appliance indicates that this product, at the end of its useful life, must be handled separately from domestic waste, must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance.

  6. Directive 2002/95/EC (RoHs): This product is compliant with directive 2002/95/EC (RoHs) concerning restrictions for the use of harmful substances in electric and electronic devices.

  7. The unit CANNOT be installed near the flammable gas. Once there is any leakage of the gas , fire can be occur.

  8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire.

  9. The heat pump located inside the unit is equipped with an over-load protection system. It does not allow for the unit to start for at least 3 minutes from a previous stoppage.

  10. The unit can only be repaired by the qualified personnel of an installer center or an authorized dealer(for North America market).

  11. Installation must be performed in accordance with the NEC/CEC by authorized person only (for North America market).

  12. Use supply wires suitable for 75 C.

  13. Caution: Single wall heat exchanger is not suitable for potable water connection.

  14. The appliance shall be installed in accordance with national wiring regulations.

  15. The appliance must be fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category 111 conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules.

  16. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.

Cable specification
  1.  Single phase unit
    Nam_ elate maximum current| Phase line| Earth line| MCB| Creepage protector| Signal line
    ---|---|---|---|---|---
    No more than 1OA| 2X 1.5mm2| 1.5mm2| 20A| 30mA less than 0.1 sec| nX0.5mm2
    10~16A| 2X2.5mm2| 2.5mm2| 32A| 30mA less than 0.1 sec
    16~25A| 2X4mm2| 4mm2| 40A| 30mA less than 0.1 sec
    25~32A| 2X6mm2| 6mm2| 40A| 30mA less than 0.1 sec
    32~40A| 2X10mm2| 10mm2| 63A| 30mA less than 0.1 sec
    40~63A| 2X16mm2| 16mm2| 80A| 30mA less than 0.1 sec
    63~75A| 2X25mm2| 25mm2| 100A| 30mA less than 0.1 sec
    75~101A| 2X25mm2| 25mm2| 125A| 30mA less than 0.1 sec
    101~123A| 2X35mm2| 35mm2| 160A| 30mA less than 0.1 sec
    123~148A| 2X50mm2| 50mm2| 225A| 30mA less than 0.1 sec
    148~186A| 2X70mm2| 70mm2| 250A| 30mA less than 0.1 sec
    186~224A| 2X95mm2| 95mm2| 280A| 30mA less than 0.1 sec
  2. Three phase unit
    Nam_ elate maximum current| Phase line| Earth line| MCB| Creepage protector| Signal line
    ---|---|---|---|---|---
    No more

than 1OA

| 3X 1.5mm2| 1.5mm2| 20A| 30mA less than 0.1 sec| nX0.5mm2
10~16A| 3X2.5mm2| 2.5mm2| 32A| 30mA less than 0.1 sec
16~25A| 3X4mm2| 4mm2| 40A| 30mA less than 0.1 sec
25~32A| 3X6mm2| 6mm2| 40A| 30mA less than 0.1 sec
32~40A| 3X10mm2| 10mm2| 63A| 30mA less than 0.1 sec
40~63A| 3X16mm2| 16mm2| 80A| 30mA less than 0.1 sec
63~75A| 3X25mm2| 25mm2| 100A| 30mA less than 0.1 sec
75~101A| 3X25mm2| 25mm2| 125A| 30mA less than 0.1 sec
101~123A| 3X35mm2| 35mm2| 160A| 30mA less than 0.1 sec
123~148A| 3X50mm2| 50mm2| 225A| 30mA less than 0.1 sec
148~186A| 3X70mm2| 70mm2| 250A| 30mA less than 0.1 sec
186~224A| 3X95mm2| 95mm2| 280A| 30mA less than 0.1 sec

When the unit will be installed at outdoor, please use the cable which can against UV.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals