niko 25020N Swiss Garde 360 Presence KNX UP Instruction Manual
- June 4, 2024
- niko
Table of Contents
Instruction Manual
Swiss Garde 360 Presence KNX UP
JAN | Model | EAN |
---|---|---|
3505100250319 | SG360P KNX UP | 3.5051E+12 |
3505100250203 | SG360P KNX UP | 3.5051E+12 |
Presence detectors 360° KNX for ceiling flush-mounting
The family of Swiss Garde 360 Presence KNX UP presence detectors is
characterized by the following outstanding features:
- 1 light output for switching, dimming, or scenery selection.
- 1 HVAC channel controls heating, ventilation, and air conditioning. This output can be used for presence detection. Additionally, alarm systems with parametrizable switch-on delay can be implemented.
- 1 Threshold switch in lux with hysteresis setting
- 1 brightness output in lux (2 Byte)
- 4 Pyro detectors and 4 PIR sensors with a 360° detection area can be activated individually or in groups.
Important notice
The presence detectors Swiss Garde 360 Presence KNX UP is suitable for
ceiling mounting indoors only (IP20, class II). In case of errors such as
continuous light, uncontrolled switching, etc., please consult page 7
„troubleshooting“.
Function
The presence detector Swiss Garde 360 Presence KNX UP reacts to heat radiation
of moving bodies. A person approaching the monitored area automatically
triggers the connected light. If no motion is detected again, the light will
automatically switch off after a delay time configured in ETS. In case of
activated standby, the light will stay on at reduced intensity during the set
time period (mode dimming complete/ constant light control).
Installation
Connect the presence detector as follows: red wire (+) to be connected to the red terminal black wire (-) to be connected to the grey terminal
Application notes
A detailed description of the communication objects and all parametrizable
functions can be found in the following separate document:
Swiss Garde 360 Presence KNX UP
APPLICATION NOTES
SG360P KNX UP (351- 25031, 25020N)
Frontal view
Rearview
PIR sensors numbering
The PIR sensors 1 2 3 4 can be activated via ETS individually or in groups,
using the above numbering scheme.
After KNX/EIB bus connection: the detector takes approx. 1 min. to reach a
stable working condition!
Detection range
The 360° omnidirectional detection range as well as the dense detection area
allow for an optimal function. The range depends on the mounting height as
well as the angle of approach (high sensitivity when crossing a switching
segment). Since the device registers the temperature differences between the
source of heat and the ambient temperature, the detection range may vary
depending on site conditions (floor heating, etc.).
Troubleshooting
Error | Cause/remedies |
---|---|
load doesn`t switch ON | • twilight value set to high |
• check light/luminaire/fuses
Detector triggers ON and off without reason or the light never turns OFF:| •
check the detection area for potential causes of false triggering: animals,
heating, etc. may all doing faulty switching
• check distances to lamps (heat- reflection or direct light influence)
• detector is too sensitive, reduce the detection range sensitivity (1…10) via
ETS.
Turns the ON during day- time:| • twilight adjustment set to high: set
to a lower value via ETS (menu light)
Device dimensions
Technical data
nominal voltage: | 24V DC (21 – 30V DC) |
---|---|
power consumption: | 0,4 W |
PIR- sensors: | 4 Pyro detectors |
sensitivity: | adjustable via ETS in 10 steps brightness sensor with linear |
output
light measuring:| value readable (5 – 2000lux, 2 Byte)
lux value:| motion and brightness
switching criteria:| 360°, ceiling mounted
detection range:| Ø7m presence, Ø16m motion
range height= 3m:| *(Ø10m presence), Ø22m motion
range height= 8m:| 2m – 8m
recom. mounting height:| ceiling mounting
mounting:| AP- housing
available accessory:| IP 20, indoor mounting, class II
protection rating:| – 20°C bis +40 °C
temperature range: dimensions:| 88 x 88 x 35 mm
* maximum values
Warnings regarding installation
The installation of products that will permanently be part of the electrical installation and which include dangerous voltages should be carried out by a qualified installer and in accordance with the applicable regulations. This user manual must be presented to the user. It should be included in the electrical installation file and it should be passed on to any new owners. Additional copies are available on the Niko website or via Niko customer services.
CE marking
**** This product complies with all of the relevant European guidelines and
regulations. For radio equipment, Niko LLC declares that the radio equipment
in this manual conforms with the 2014/53/ EU directive. The full text of the
EU declaration of conformity is available at www.niko.eu
under the product reference, if applicable.
Environment
This product and/or the batteries provided cannot be disposed of in the non-
recyclable waste. Take your discarded product to a recognized collection
point. Just like producers and importers, you too play an important role in
the promotion of sorting, recycling, and reuse of discarded electrical and
electronic equipment. To finance rubbish collection and waste treatment, the
government levies recycling charges in certain cases (included in the price of
this product).
PM25020NR21503_EN
Documents / Resources
| niko
25020N Swiss Garde 360 Presence KNX
UP
[pdf] Instruction Manual
25020N, Swiss Garde 360 Presence KNX UP, 25020N Swiss Garde 360 Presence KNX
UP
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>