BA/ZPM-SR-AT-D-BB Standard Range ZPM – Zone Pressure Sensor in a BAPI-Box
Enclosure
Product Information
ZPM Zone Pressure Sensor in a BAPI-Box Enclosure
The ZPM Zone Pressure Sensor is a field-installable device designed for easy and quick installation. It comes with output, range, units, and directionality that can be easily set in the field without the need for powering the unit. It features an optional LCD display that can show the actual pressure, regardless of the selected pressure range, which can help in troubleshooting. The device has three LEDs on its face that indicate whether the pressure is Out of Range Low, In Range, or Out of Range High for the selected range. The appropriate LED will flash when out of range. The ZPM comes with a bulkhead fitting, static probe, cover latch, conduit for static probe, foam plug, mounting screws, and deadhead tubing.
PRODUCT Switch Setup – Outputs, Ranges, Units/Response
The following steps should be followed to set up the switch:
- Select OUTPUT
- Select RANGE; if the unit is ordered with a Custom Range, then the switch must be set to R6.
- Choose DIRECTION; Bidirectional is a plus/minus range so choosing 5 range is -5 to +5 Bidirectional and 0 to +5Unidirectional
- Choose UNITS – Inches WC or PASCALS
- Choose RESPONSE TIME; Fast Response = 1/2 second Slow Response = 4 seconds
Note: Always follow the Auto-Zero procedure after changing settings.
PRODUCT Mounting
The ZPM sensor should be attached to its mounting surface with four self- tapping #10×3/4 sheet metal screws through the holes in the mounting feet. The preferred mounting orientation is with the pressure ports facing down. The two cover latch screws must be installed to achieve IP66 rating.
Output Termination
BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty. To ensure that all wires are properly terminated, twist the stripped ends of each wire together before inserting into the terminals. Gently tug on the wire after insertion to ensure a secure connection.
Product Usage Instructions
- Set up the switch as per the instructions above.
- Mount the ZPM sensor on its surface using four self-tapping #10×3/4 sheet metal screws through the holes in the mounting feet.
- Make sure that the pressure ports face down for preferred mounting orientation.
- Install the two cover latch screws to achieve IP66 rating.
- Perform an Auto-Zero procedure after changing settings.
- Ensure that all wires are properly terminated, twist the stripped ends of each wire together before inserting into the terminals. Gently tug on the wire after insertion to ensure a secure connection.
Identification and Overview
BAPI’s ZPM is designed for quick and easy field installation. The outputs, ranges, units, and directionality, are all easily set in the field without powering the unit. The optional LCD display helps with troubleshooting because it displays the actual pressure regardless of the selected pressure range. Three LEDs on the face of the unit indicate when the pressure is “Out of Range Low”, “In Range” or “Out of Range High” for the selected range. The appropriate LED will flash when out of range.
Switch Setup – Outputs, Ranges, Units/Response
NOTE: Always follow the Auto-Zero procedure after changing settings.
Mounting
Attach the unit to its mounting surface with the four self-tapping #10×3/4” sheet metal screws through the holes in the mounting feet. The preferred mounting orientation is with the pressure ports facing down. The two cover latch screws must be installed to achieve IP66 rating. After Auto-Zeroing, remove the deadhead tubing and push the system tubing onto the port nipple without creating any kinks or holes. See for an actual size mounting template for the unit.
Mounting Template
Output Termination
STOP: BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty.
To ensure that all wires are properly terminated, twist the stripped ends of each wire together before inserting into the terminals. Gently tug on the wire after inserting into the terminal to verify a good connection.
Table 1: ZPM Termination
Output Signal| PWR Terminal| GND Terminal| OUT Terminal
4 to 20 mA| 7 to 40 VDC| 4 to 20 mA Signal To Controller Analog Input| Not
Used
0 to 5 or 1 to 5 VDC| 7 to 40 VDC
or 18 to 32 VAC
| To Controller Ground| VDC Signal To Controller
Analog Input
0 to 10 or 2 to 10 VDC| 13 to 40 VDC
or 18 to 32 VAC
| To Controller Ground| VDC Signal To Controller
Analog Input
Auto-Zero and Status LED Operation
AUTO-ZERO OPERATION
Auto-Zeroing must be done after the initial setup, changing mounting orientation or changing any settings. For most applications, perform an auto- zero whenever it appears that the sensor has drifted. For critical applications, the unit should be zeroed 2-3 times a year.
- Power must be on.
- Detach system tubing and deadhead ports using the supplied tubing or other short length of tubing. Do not kink tubing.
- Press and hold the Auto-Zero button for 1-2 seconds. The Status LED will stop flashing when completed.
- Remove deadhead tubing and reattach system tubing.
AUTO-ZERO OPERATION (Units w/ Attached Tube)
- Power must be on.
- Disconnect system tubing from the Low Pressure brass fitting and attach the supplied 6” deadhead tubing to the brass fitting.
- Disconnect the short clear tubing from the 90° black Attached Tube fitting with your fingers (Fig. 9). A pliers may cut the tubing.
- Connect the clear tubing to the supplied, straight black fitting on the 6” tubing (Fig. 9). Do not kink the tubing.
- Press and hold the Auto-Zero button for 1-2 seconds. The Status LED will stop flashing when completed.
- Disconnect the deadhead tubing and reattach the clear tubing and system tubing. Confirm that the clear tubing is pressed all of the way onto the fitting and that it is not kinked.
STATUS LED OPERATION
- LED Off: No power is applied or the unit is in 4 to 20 mA Mode
- LED Solid (On): LED is on when power is applied and a VDC output is selected. When 4 to 20 mA output is selected, the light is on for 2 seconds at power up then goes off.
- LED Flashing: Auto-Zero. The LED will flash for about 20 seconds.
Typical Applications
NOTE: Best practice is to form a drip loop in the tubing to prevent condensation from reaching the unit.
Diagnostics
POSSIBLE PROBLEMS/ POSSIBLE SOLUTIONS
- Status LED does not light: Check power connections for proper power
- Sensor is set to 4 to 20mA output
- Status LED is flashing: The unit is performing an auto-zero. Wait 20 seconds and check again.
- Output stuck (high or low): Remove pressure from ports and perform auto-zero procedure
- Output not tracking pressure properly: Check rotary switch for proper pressure range selection
- Check rotary switch for proper output range selection
Specifications
- Power: 7 to 40 VDC (4 to 20 mA Output)
- 7 to 40 VDC or 18 to 32 VAC (0 to 5 or 1 to 5 VDC Output)
- 13 to 40 VDC or 18 to 32 VAC (0 to 10 or 2 to 10 VDC Output)
- Power Consumption: 20 mA max, DC only at 4 to 20 mA Output
- 5.2 mA max DC at 0 to 5 or 0 to 10 VDC Output
- 0.12 VA max AC at 0 to 5 or 0 to 10 VDC Output
- Load Resistance: 4 to 20 mA Output 850 Ω Maximum @ 24 VDC
- 0 to 5 or 0 to 10 VDC Output 6KΩ Minimum
- Accuracy: ±0.25% FS at 72°F (22°C) for All Units
- Standard Range Unit: ±0.025” WC (±6.22 Pa)
- Stability: ±0.25% FS per year
- Overpressure: Proof 300” WC (74 kPa)
- Media: Clean, dry, non-corrosive gases
- Compensated Temperature Range: 32 to 122°F (0 to 50°C)
- Environmental Operating Range: -4 to 140°F (-20 to 60°C)
- Storage Temperature: -40 to 185°F (-40 to 85°C)
- Humidity: 0 to 95% RH, non-condensing
- Wiring: 2 wires (4 to 20mA Current loop)
- 3 wires (AC or DC powered, VDC output)
- Port Size: 1/4” barb
- Enclosure Material: UV-resistant Polycarbonate, UL94, V-0
- Enclosure Rating: IP66, NEMA 4
- Agency: CE EN 61326-1:2013 EMC (Industrial Electromagnetic Environment), UL, RoHS
Selectable Standard Ranges
Inches WC /Pascals
- 0 to 1.00………………………… 0 to 250
- 0 to 2.00………………………… 0 to 300
- 0 to 2.50………………………… 0 to 500
- 0 to 3.00……………………… 0 to 1,000
- 0 to 5.00……………………… 0 to 1,250
- -1.00 to 1.00………………. -250 to 250
- -2.00 to 2.00………………. -300 to 300
- -2.50 to 2.50………………. -500 to 500
- -3.00 to 3.00…………. -1,000 to 1,000
- -5.00 to 5.00…………. -1,250 to 1,250
Specifications subject to change without notice.
CONTACT
- Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
- Tel: +1-608-735-4800
- Fax: +1-608-735-4804
- E-mail:sales@bapihvac.com
- Web:www.bapihvac.com