CEL-MAR ADA-11040 RF Converter User Manual
- June 9, 2024
- CEL-MAR
Table of Contents
- GENERAL INFORMATION
- INSTALLATION
- ASSEMBLING
- WIRELESS RF NETWORK CONNECTION
- EXTENSIONS RS485/RS422 BUS
- EXTENSIONS OF FEW RS485/RS422 BUSES
- COMPUTER CONNECTION
- RS485/RS422 NETWORK CONNECTION
- RS422 (4W) BUS CONNECTION
- RS485 (4W) BUS CONNECTION
- RS485 (2W) BUS CONNECTION
- GND TERMINALS CONNECTION
- LINE TERMINATION Rt OF RS485 BUS
- POWER SUPPLY CONNECTION
- ACTIVATION
- CONFIGURATION
- TROUBLESHOOTING
- VERSIONS
- SPECIFICATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CEL-MAR ADA-11040 RF Converter User Manual
GENERAL INFORMATION
Thank you for your purchase of CEL-MAR Company product. This product has been completely tested and is covered by a two year warranty on parts and operation from date of sale. If any questions or problems arise during installation or use of this product, please do not hesitate to contact Technical Support at +48 41 362-12-46 or e-mail support@cel- mar.pl
WARRANTED INFORMATION
ADA-11040 converter is covered by a two year warranty from date of sale.
In case of being damaged it will be repair or the damaged b component will be
replace. The warranty does not cover damage caused from improper use,
materials consumption or any unauthorized changes. If the product does not
function (is damaged), or not operate in accordance with the instructions,
will be repaired or replaced. All warranty and no warranty repairs must be
returned with paid transport and insuring to the CEL-MAR Company.
CEL-MAR Company under no circumstances won’t be responsible for ensuing
damage from improper using the product or as a result of random causes: the
lightning discharge, the flood, the fire and the like.
CEL-MAR Company is not be held responsible for damages and loss
including: loss of profits, loss of data, pecuniary losses ensuing from using
or the impossibility of using this product. In specific cases CEL-MAR
Company discontinue all warranties and in particular do not follow the user
manual and do not accept terms of warranty by the user.
GENERAL CONDITIONS FOR SAFE USE
The device should be installed in a safe and stable places (eg,
electroinstallation cabinet), the powering cable should be arranged so
as not to be exposed to trampling, attaching, or pulling out of the circuit.
Do not put device on the wet surface.
Do not connect devices for nondescript powering sources,
Do not damage or crush powering wires.
Do not make connection with wet hands.
Do not adapt, open or make holes in casings of the device!
Do not immerse device in water or no other liquid.
Do not put the fire opened on device sources: candles, an oil lamps and
the like. Complete disable from the supply network is only after disconnecting
the power supply circuit voltage.
Do not carry out the assembly or dis-assembly of the device if it is
enabled. This may result to short circuit and damage the device. The device
can not be used for applications that determine human life and health (eg.
Medical).
CE LABEL
The CE symbol on the device CEL-MAR means compatibility with Radio Directive 2014/53/UE, electromagnetic compatibility Electromagnetic Compatibility Directive EMC 2014/30/WE. Declaration of Conformity is delivered with purchased converter.
ENVIRONMENTAL PRESERVATION
This sign on the device inform about putting expended device with other waste materials. Device should send to the recycling. (In accordance with the act about the Electronic Appliance Expended from day 29 of July 2005).
SERVICE AND MAINTENANCE
ADA-11040 converter does not require the servicing and maintenance. Technical support is available at number +48 41 362-12-46 in 8.00-16.00, from Monday to Friday or e-mail support@cel-mar.pl.
PACK CONTENTS
ADA-11040 converter, User Manual, CE declaration, Antenna, CD with ADARF software.
PRODUCT INFORMATION
Attention!
Class A device designed for installation in environments commercial and light
industrial. In residential environment may cause harmful interference radio-
electric, in which case the user will have to take appropriate steps to
eliminate them.
PROPERTIES
- Work on wireless network in ISM 868/433/470/915 MHz band, globally without a license,
- FSK modulation, 2-way half duplex communication, strong protection against interference,
- Wireless network baud rate 1200 – 115200 bps,
- Maximum output power of transmitter 100mW (20dBm), adjustable in the range 1-20dBm,
- Receiver sensitivity: -117dBm,
- RSSI function,
- SMA connector for connection of antenna,
- Operating on 2 or 4 wire RS485 bus and on 2 or 4 wire RS422,
- RS485/RS422 baud rate (bps): 1200, 1800, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200,
- RS485/RS422 data format: data bit: 8; parity: None; stop bits: 1,
- Power supply 10 – 30 VDC stable min. 2W,
- ~3kV= optoisolation in signal channel between RF and RS485/422 interfaces,
- 1kV= or 3kV= galvanic isolation between RF & RS485/422 interfaces and power supply (depend on version)
- Connection RS485/RS422 network via screw terminal block 2.5 mm2 .
- Implemented short circuit protection and over-voltage protection on RS485 / RS422 network,
- Implemented protection against power supply reverse connection,
- Cover compatible with DIN 43880 standard– mounting in typical electro-installation unit,
- Cover adapt to rail mounting according to DIN35 / TS35 standard,
- Cover dimensions (W x D x H) 53mm x 62mm x 90mm,
- Antenna dimensions: length 110mm, diameter 9mm.
DESCRIPTION
ADA-11040 converter is a device used for connection together devices with RS485/RS422 interface via wireless RF network. The converter transmits data with baud rate from 1200bps to 115200 bps via RS485/RS422 interface, and steady data format: 8 data bits, None parity bit, One stop bit (8N1). ADA-11040 converter has screw terminals blocks for connection of RS485/RS422 , power supply and SMA connector for RF antenna. The converters work in the same radio channel, create wireless RF network. ADA 11040 uses signals: RX+, RX-, TX+/A, TX-/B of RS485/RS422 for operation. To RS485 bus, constructed on the base of ADA 11040, can be connect 32 devices operating in half duplex mode to RS485(2W) bus to RS485(4W) bus. The converter is adapted to supply an external voltage source from 10V to 30V and power 2W. Has implemented protection against opposite polarization of power supply and over-voltage protection on RS485/RS422 bus. ADA-11040 has galvanic isolation between power supply and RF and RS485/RS422 interfaces, has also optoisolation between RF and RS485/RS422 interface.
Transmission range in wireless RF network:
- in buildings – from 30m to 300m
- in an open area up to 1000m,
The transmission range can be enlarged by use the additional direction antennas.
Fig 1. ADA-11040 view.
ISOLATION
Converter ADA-11040 has 3-way galvanic isolation on the levels 1kV= or 3kV=, depend on version described in section VERSIONS.
Fig 2. Isolation structure
INSTALLATION
This chapter will show how to use and connect ADA-11040 to RS485,RS422 bus and RF network and power supply. In the purpose of minimization of disruptions from environment is being recommended to:
- apply multipair type shielded cables, which shield can be connected to the earthing on one end of the cable,
- arrange signal cables in the distance not shorter than 25 cm from powering cables.
- apply cable of adequate cross-section due to voltage drops for converter powering,
- use suppression filters for powering converters that are installed within a single object.
- not supply converter from power circuit device that generates large impulse interference such as transmitters, contactors.
ASSEMBLING
The cover of ADA-11040 converter is adapted to assembly on TS-35 (DIN35) rail. To install the converter, should be mounted on the rail upper part of the cover then press bottom part to hear characteristic „Click” sound.
ATTENTION!
THE DISTANCE BETWEEN RF DEVICES HAS TO BE LARGER THAN 20CM. DO NOT INSTALL,
SET RF DEVICES IN LESS DISTANCE.
WIRELESS RF NETWORK CONNECTION
Using ADA-11040 converter, can be connected devices with RS485/422 interfaces to wireless RF network.
EXTENSIONS RS485/RS422 BUS
On the drawing below was shown, the using of ADA-11040 as extender of RS485/422 bus above obstacle terrain.
ATTENTION !
THE CONFIGURATION OF RF PARAMETERS HAVE TO BE THE SAME FOR BOTH CONVERTERS,
IN PURPOSE OF PROPER WORK WIRELESS CONNECTION.
EXTENSIONS OF FEW RS485/RS422 BUSES
On the drawing below was shown, connection of two RS485 buses and MASTER device by the use of wireless RF network.
ATTENTION !
THE CONFIGURATION OF RF PARAMETERS HAVE TO BE THE SAME FOR BOTH
CONVERTERS, IN PURPOSE OF PROPER WORK WIRELESS CONNECTION.
CONNECTION MANY RS485/RS422 DEVICES VIA WIRELESS RF NETWORK.
On the drawing below was shown, connection of many RS485/RS422 devices by the use of wireless RF network.
ATTENTION !
THE CONFIGURATION OF RF PARAMETERS HAVE TO BE THE SAME FOR BOTH CONVERTERS, IN
PURPOSE OF PROPER WORK WIRELESS CONNECTION.
COMPUTER CONNECTION
To connect ADA-11040 to USB computer port, is needed additional converter USB to RS485 eg. ADAI9141, connected to RS485/422 port of ADA-11040 converter. Typical connections of ADA- 4040PC1 to PC are shown bellow.
Fig 3. 4-wires connection of ADA-11040 to PC by the use of USB to
RS485/RS422 converter ADA-I9141.
Fig 4. 2-wires connection of ADA-11040 to PC by the use of USB to
RS485/RS422 converter ADA-I9141.
RS485/RS422 NETWORK CONNECTION
RS485/RS422 interface in ADA-11040 converter is described as: Tx+/A, Tx-/B, Rx+, Rx-, GND. ADA-11040 lets work on RS485 bus & RS422 bus. Both buses need correct cabling.
RS422 (4W) BUS CONNECTION
Before connection 4-wire RS422 bus, should be setted MODE switch to RS422 mode, located on the front panel of ADA-11040. Then connect bus wires to connectors TX+/A, TX-/B, RX+, RX – as shown bellow.
Fig 5. Example connection of RS422 devices to ADA-11040
RS485 (4W) BUS CONNECTION
Before connection 4-wire RS485 bus, should be setted MODE switch to RS485 mode, located on the front panel of ADA-11040. Then connect bus wires to connectors TX+/A, TX-/B, RX+, RX – as shown bellow.
Fig 6. Example connection of RS485 (4W) devices to ADA-11040
RS485 (2W) BUS CONNECTION
Most of device with RS485 interface use 2-wire bus for transmission. Before connection 2-wire RS485 bus, should be setted MODE switch to RS485 mode, located on the front panel of ADA-11040. Then connect bus wires to connectors TX+/A, TX-/B, – as shown bellow.
Fig 7. Example connection of RS485 (2W) devices to ADA-11040
GND TERMINALS CONNECTION
Connection of GND terminals of RS485/422 interfaces, devices connected to RS485/422 bus, should be done in the case of a potential difference RS485 / RS422 interfaces, which prevents proper data transmission.
ATTENTION!
CANNOT CONNECT TO THE GND TERMINAL – CABLES SCREENS, PE CIRCUIT OF ELECTRICAL
INSTALLATION, SIGNALS GROUNDS OF OTHER DEVICES.
LINE TERMINATION Rt OF RS485 BUS
The application of Line Termination (terminator) Rt = 120 ohms on the ends of
the bus, will reduce electrical reflection in long data line at high baud
rate. It is not needed below 9600Bd. For over 1000m @ 9600Bd or 700m @ 19200Bd
the line termination can be used, if there are problems with proper
transmission.
Example connection of Rt are shown on figures above. The resistor Rt = 120 W .
ADA-11040 converter has two implemented terminators, connected to terminals
Tx+/A – Tx-/B and Rx+ – Rx-, by the use SW1 microswitch (see table below).
SW1 | Description |
---|---|
SW1-1 | ON – enable the terminator 120 W to terminals Tx+/A and Tx-/B OFF |
– disable the terminator 120 W to terminals Tx+/A and Tx-/B
SW1-2| ON – enable the terminator 120 W to terminals Rx+ and Rx- OFF –
disable the terminator 120 W to terminals Rx+ and Rx-
POWER SUPPLY CONNECTION
To connect power supply to the converter, should have DC power supplies (regulated) output voltage from 10 V= to 30V=, min. nominal power 2W, e.g. HDR-15-24. Power cable from DC power supplies to device can not be longer than 3m. Should connect positive (+) end of DC power supplies to V+ device terminal and negative (-) end to V- on terminal block. ADA- 11040 has protection against power supply reverse connection.
ACTIVATION
If connection was made properly a green LED PWR on front panel of converter should lit after power on, if not check polarization of connected power. When data is transmitted via the converter, RX, TX LED’s on front panel and LED’s on the module of RF interface should blink.
This LED are described below:
LED | Description |
---|
Power
PWR| Signalling of Power Supply.
RS485/RS422 interface
RX| Signalling of data receiving by ADA-11040 from RS485/RS422 port.
TX| Signalling of data transmitting from ADA-11040 via RS485/RS422 port.
CONFIGURATION
For correct work of ADA-11040 converter, is needed the configuration of settings wireless RF network and RS485/RS422 serial port.
OPERATION MODE
ADA-11040 converter can operates in two modes:
- RUN,
- configuration,
Those modes are setted by use of CONFIG jumper, located by SMA connector. To set mode, should remove terminal cover, marked as CFG and put on or remove the jumper.
All available adjusting of the CONFIG jumper, are shown in table below.
Converter operation modes
CONFIG jumper | Operation mode |
---|---|
OFF – open | RUN |
ON – close | Device configuration |
CONFIGURATION BY USING ADARF
ADARF INSTALLATION
The configuration of setting wireless RF network ADA-11040, can be made by the use of ADARF Software – selling with converter. The installation is automatically after insert the CD (compact disc) to an optical drive. If the autorun doesn’t start, should run the file setup.exe located in main CD catalogue. After installation the ADARF software is available in menu **Start=
Programs=>CEL-MAR=>ADARf.**
CONFIGURATION THE WIRELESS NETWORK SETTINGS
Set ADA-11040 converter in configuration mode, then connect the converter to PC according to point ‘COMPUTER CONNECTION’, run ADARF software. Then follow the steps:
-
select COM port.
-
select baud rate of RS485/RS422 serial port.
-
open COM port, by button [Open COM].
-
read configuration parameters of the converter by button [ Read Setting ]
-
read out configuration parameters are copied to edit boxes of section [RF Settings], by button [<<],
-
in the edit boxes, change RF configuration parameters,
-
press button [Send] to send the parameter to the converter
BAUD RATE CONFIGURATION OF RS485/RS422 PORT
After read out the configuration parameters, change baud rate of RS485/422
serial port in section [UART Setting]:
select baud r?ate, press button [Change] to send the parameter to the
converter.
FACTORY DEFAULT
Converter reset to factory default can be done by: [10] button [Reset Module], but first has to be read the setting, by button [Read Setting]
Factory default.
Parameter | Value |
---|
Wireless RF
Operate frequency| 869 [MHz]
Baud rate| 9600 [bps]
Frequency deviation| 35 [kHz]
Transmission power| 20 [dBm]
bandwidth reception| 105 [kHz]
RS485/RS422 serial port
Baud rate| 9600 [bps]
Data bits| 8
Parity| Non
Stop bits| 1
TROUBLESHOOTING
Problem | Solution |
---|
I forgot what the transmission speed of the serial port is and I can not read the configuration parameters.| You can only select next baud rates, open COM port [Open COM] and readout the settings by button [Read Setting], until it succeeds.
VERSIONS
Order example:
Product Symbol: ADA-11040-1-23 1 – basic version of electronic 23 – galvanic isolation 1kV= (3-way),
SPECIFICATION
TECHNICAL DATA
Transmission Parameters
Interfaces| RF| RS485/RS422
Connector| SMA-Plug + Antenna| Screw terminal block – max. Ø 2,5mm2
Max. number of connected device| Unlimited| 32
Max. baud rate| From 1200 bps to 115200 bps| From 1200 bps to 115200 bps
Data format: 8N1
Standards| ISAM 869/433/470/915 MHz| EIA-485, CCITT V.11
Transmission range / Max. Line length| – in buildings – from 30m to
300m- in an open area up to 1000m,| 1200 m
Transmission lineRS485/RS422| 2-pair twisted cable, UTP Nx2x0,5 (24AWG),
shield inside large interferences STP Nx2x0,5(24AWG).
Transmission type| Asyn chronism half duplex.
Optical Signalization| • PWD – green LED, power supply,• RX – red LED,
data receiving on RS485/RS422,• TX – yellow LED, data transmission via
RS485/RS422.
Electrical Parameters
Power requirements| 10 – 24 – 30 V DC
Power Cable| Recommended length – up to 3m
Power| 2W
Protection from reverse power polarization| Yes
Galvanic Isolation| 1kVDC or 3kVDC (3-WAY) depending on the version.
Optoisolation| ~3kV DC between RF and RS485/RS422 interfaces
Electromagnetic compatibility| According to the PN-EN55024 norm PN-ETSI
EN 301 489-1 V2.1.1:2017-08PN-ETSI EN 300 220-2 V3.2.1:2018-12
Safety requiring| According to the PN- EN60950 norm
Environment| Commercial and light industrial. Device A class.
Environmental Parameters
Operating temperature| -30 ÷ 50 °C
Humidity| 5 ÷ 95% – non-condensing
Storage temperature| -40 ÷ 70°C
Casing
Dimensions| 53 x 90 x 62mm
Material| PC/ABS
Degree of casing protection| IP40
Degree of terminal protection| IP20
Weight| 0,10 kg
According to standards| DIN EN50022, DIN EN43880
Location during work| Free
Mounting| Rail mounting according to DIN35 standard / TS35.
Dear Customer,
Thank you for purchasing CEL-MAR Company product. We hope that this user manual helped connect and start up the ADA-11040 Converter. We also wish to inform you that we are a manufacturer of the widest selections of data communications products in the world such as: data transmission converters with interface RS232, RS485, RS422, USB, Ethernet, Wi-Fi, Current Loop, Fibre- Optic Converters and the other. Please contact us to tell how you like our products and how we can satisfy you present and future expectation.
CEL-MAR sp.j.
Computers Science and Electronic Factory str Sciegiennego 219C 25-116 Kielce,
POLAND
Tel…… : +48 41 362-12-46
Tel/fax….. +48 41 361-07-70
Web……: http://www.cel-mar.pl
Office….. offi@cel-mar.pl
Sales department……. : sales@cel-mar.pl
Technical information …. : support@cel-mar.pl
References
- Oferta sprzedaży domeny mar.pl (mar)
- CEL-MAR | Producent konwerterów i separatorów interfejsów: RS232 RS485 RS422 USB ETHERNET WI-FI 1-WIRE ...
- CEL-MAR | Producent konwerterów i separatorów interfejsów: RS232 RS485 RS422 USB ETHERNET WI-FI 1-WIRE ...
Read User Manual Online (PDF format)