TYLO Sense Combi Elite Electric Sauna Heater User Guide

June 9, 2024
TYLO

Sense Combi Elite Electric Sauna Heater

error
{
“error”: {
“message”: “You exceeded your current quota, please check your plan and billing details.”,
“type”: “insufficient_quota”,
“param”: null,
“code”: null
}
}

the following is the text from the user manual / instructions:
SENSE COMBI ELITE Quick-Start Tip Sheet
This page to be used in conjuction with Tylo Full Manual included
2900 5264 2020-05-XX
CONNECTION/WIRING DIAGRAM
208 V 1 Phase
240 V 1 Phase
Model
Amperage Output
Amps
kW
Wire Size AWG
Amps/ Breaker
Output kW
Wire Size AWG
Sense Combi-U 7
26
5.3
10
30/40
7.0
8
Sense Combi-U 8
30
6.3
8
35/50
8.3
8
Note: Heating elements do not change for voltage changes. The heater output will change based on the voltage applied to heater. Most North American homes are 240v.
1234 5 6789
11
40 41 B B
120 V~
Connect Sensor cable (round) to
Connect Control cable (flat) to
jack 6 on circuit board.
jack 9 on circuit board.
14
16 15 14 10
13 12
3 x 14 AWG RJ10 4P4C RJ10 4P4C
RJ10 4P4C ***
RJ10 4P4C
thrCeeoncfoirpmper conectors installed
5.3-8.3 kW 208/240 V~
G
14 AWG Max. 6 Amp.

  • max 75 feet – Combi Elite
    Figure 19: Wiring Diagram
    Use List Below to Identify Components in Figure 19: Wiring Diagram (Above)
    x3x 3
    Humidity Sensor Installation Tip
    1. N/A 2. External Switch (Optional) (jack # 2) 3. Door jumper pre-installed (jack # 3) 4. N/A 5. N/A 6. Sensor (combination humidity and temperature,
    jack # 6) 7. N/A 8. N/A 9. Elite Control 10. Heater 11. Terminal for connection of electrical cable 12. Control panel (jack # 9) 13. Sensor – Combi Elite (jack # 6) 14. Light/terminal for connection of light 15. Door Switch is not required for N. America 16. External On/Off Switch (option)
    12 11 A B
    Black White
    Red Green
    12 11 A B
    Combi Elite humidity- and temperature sensor
    R=Red, G=Green, W=White, B=Black
    14 AWG Max. 6 Amp. In order for
    control to operate light,
    a separate 120V supply
    must be provided and connected to
    heater
    Combi Elite Sensor
    2
    2 3
    1
    4 in.
    8
    3 in. 4
    3
    Sensor Location:
    3 from heater,
    1 down from ceiling
    5 1 in.
    3
    6
    7
    9 10
    1. Minimum distance from side wall: 4 (100 mm) 2. Sensor position alt 1: 3 (75 mm) from heater 3. Sensor
    4. Sensor position alt 2: 3 (75 mm) from heater front 5. Sensor position: 1 (25 mm) from ceiling 6. Minimum distance from ceiling: 44 (1100 mm) 7. Minimum distance from heater guard: 4 (100 mm) 8. Minimum ceiling height: 75 (1900 mm)
  1. Minimum distance: 1 (25 mm) 10. Minimum distance from heater guard: 2 (50 mm) 11. Distance from floor: 7 (175 mm)
    11 7 in. ** Combi Elite Control distance to heater is max 75 feet
    Figure 3: Position the sensor according the picture.
    462 mm 24-3/8
    4 mm 1-9/16
    43 mm
    17 18.5 mm
    7-5/16
    28 mm 11
    49 mm 19-5/16
    sensor location:
    1 down from ceiling 3 to front or side of heater; not in corner.
    Figure 14: Fitting the cover for the water reservoir, herb grille and fragrance holder/air humidifier
    Main Power Switch: On/Off Knob comes packed inside rock tray. Field install. Turn knob to turn on heater.
    2
    1
    Fig. 9: Resetting the temperature cut-out 1. Temperature cut-out water reservoir 2. Temperature cut-out sauna heater
    Elite Control Installation Instructions The control panel can be installed inside or outside the sauna room. If the control is installed inside the room, install no higher than 3′ (90 cm) above the floor. No closer than 12 (30 cm) to heater.
    Installation without Mounting Bracket Cut a 1-3/16 (3 cm) hole through the wall big enough for the control panel connector.

SENSE COMBI ELITE Quick-Start Tip Sheet
This page to be used in conjuction with Tylo Full Manual included

2900 5264 2020-05-XX

CONNECTION/WIRING DIAGRAM

208 V 1 Phase

240 V 1 Phase

Model

Amperage Output

Amps

kW

Wire Size AWG

Amps/ Breaker

Output kW

Wire Size AWG

Sense Combi-U 7

26

5.3

10

30/40

7.0

8

Sense Combi-U 8

30

6.3

8

35/50

8.3

8

Note: Heating elements do not change for voltage changes. The heater output will change based on the voltage applied to heater. Most North American homes are 240v.

1234 5 6789

11

40 41 B B
120 V~

Connect Sensor cable (round) to

Connect Control cable (flat) to

jack 6 on circuit board.

jack 9 on circuit board.

14

16 15 14 10

13 12

3 x 14 AWG RJ10 4P4C RJ10 4P4C

RJ10 4P4C ***
RJ10 4P4C

thrCeeoncfoirpmper conectors installed

5.3-8.3 kW 208/240 V~
G

14 AWG Max. 6 Amp.

  • max 75 feet – Combi Elite
    Figure 19: Wiring Diagram
    Use List Below to Identify Components in Figure 19: Wiring Diagram (Above)

x3x 3
Humidity Sensor Installation Tip

1. N/A 2. External Switch (Optional) (jack # 2) 3. Door jumper pre-installed (jack # 3) 4. N/A 5. N/A 6. Sensor (combination humidity and temperature,
jack # 6) 7. N/A 8. N/A 9. Elite Control 10. Heater 11. Terminal for connection of electrical cable 12. Control panel (jack # 9) 13. Sensor – Combi Elite (jack # 6) 14. Light/terminal for connection of light 15. Door Switch is not required for N. America 16. External On/Off Switch (option)

12 11 A B

Black White

Red Green

12 11 A B
Combi Elite humidity- and temperature sensor

R=Red, G=Green, W=White, B=Black

14 AWG Max. 6 Amp. In order for
control to operate light,
a separate 120V supply
must be provided and connected to
heater
Combi Elite Sensor

2
1. CAUTION: Heater junction box can be a tight fit. Make sure no bare wires come in to contact with circuit board, on/off switch or any other heater components. Extra care should be taken when closing junction box cover to ensure wires are not being pushed out of position. 2. Some prefer or are required to make a weather-proof connection. If so, you may use Liquid tight conduit for the wire exposed within the sauna. For more flexibility, you can install weather proof junction box inside sauna below heater and use flexible SOOW wire to connect to heater

2 3

1

4 in.

8

3 in. 4

3

Sensor Location:

3″ from heater,

1″ down from ceiling

5 1 in.

3

6

7

9 10

1. Minimum distance from side wall: 4″ (100 mm) 2. Sensor position alt 1: 3″ (75 mm) from heater 3. Sensor
4. Sensor position alt 2: 3″ (75 mm) from heater front 5. Sensor position: 1″ (25 mm) from ceiling 6. Minimum distance from ceiling: 44″ (1100 mm) 7. Minimum distance from heater guard: 4″ (100 mm) 8. Minimum ceiling height: 75″ (1900 mm) 9. Minimum distance: 1″ (25 mm) 10. Minimum distance from heater guard: 2″ (50 mm) 11. Distance from floor: 7″ (175 mm)

11 7 in. ** Combi Elite Control distance to heater is max 75 feet

Figure 3: Position the sensor according the picture.

462 mm 24-3/8 ”

4 mm 1-9/16 ”

43 mm
17 ” 18.5 mm
7-5/16″

28 mm 11″
49 mm 19-5/16 ”

sensor location:
1″ down from ceiling 3″ to front or side of heater; not in corner.

Figure 14: Fitting the cover for the water reservoir, herb grille and fragrance holder/air humidifier

Main Power Switch: On/Off Knob comes packed inside rock tray. Field install. Turn knob to turn on heater.

2

1

Fig. 9: Resetting the temperature cut-out 1. Temperature cut-out water reservoir 2. Temperature cut-out sauna heater

Elite Control Installation Instructions The control panel can be installed inside or outside the sauna room. If the control is installed inside the room, install no higher than 3′ (90 cm) above the floor. No closer than 12″ (30 cm) to heater.

Installation without Mounting Bracket Cut a 1-3/16″ (3 cm) hole through the wall big enough for the control panel connector.

Elite Control Location The control panel can be installed inside or outside
of the sauna room. (Outside is Typical)

Attach the double-sided adhesive to the control panel. Before applying the control to the wall, connect it to the heater and electrically test everything first. Clean the surface where the control will be applied to remove all dust. Remove the protective backing from the adhesive. Silicone sealant can be applied in the groove on the back of the panel as an extra seal. Connect the control wire, push the excess wire through the hole in the wall and press the control panel firmly to the wall.
Installation with Bracket Use the mounting bracket as a template to mark screws holes on the wall. Tighten the screws a little until the bracket is nearly secured.
Remove the bracket from the wall. Use adhesive to mount the control to the bracket. Remember to position the switch according to the picture.

Installation without Bracket

Installation with Bracket

Control stuck directly to the wall. Generally only used when control wire is surface Control cable in the stud cavity. mounted; i.e. solid log style outdoor sauna.

To prevent build up of lime-scale and higher salt/mineral levels, empty the reservoir after each use. If this is not done and water is added each time you take a sauna, foam build-up could occur which can cause the level sensor to detect a higher water level than usual. There is a risk the heating element may break.

6(16(&20%,86$/Elite

2016-10-1

EN ISH
,167$//$7,2186(5*8,'(

2900 5260

2 ,167$//$7,218,'(
%()25(,167$//$7,21 arts …………………………………………………………….. 3
Installation re uirements …………………………………. 3 Installation tools ………………………………………………3 Installation planning ……………………………………….. 3 ,167$//$7,21 Sauna heater installation ………………………………….6 External ON/OFF switch (option) ……………………… &211(&7,21:,5,1
Description of cabling/modular contacts ……………..10 6(/),163(&7,212)7+(,167$//$7,21 ‘,0(16,216
WARNING!

+SHUWKHUPLDoccurs when the internal temperature of the body reaches a level several degrees above the normal temperature of 98.6° F. The symptoms of hypothermia include an increase in the internal temperature of the body, dizziness, lethargy, drowsiness and fainting. The eect of hyperthermia include: a) Failure to perceive heat; b) Failure to recognize the need of exit the room; c) Unawareness of impending hazard; d) Fatal damage of pregnant women; e) Physical inability to exit the room; and f) Unconsciousness
Do not take a sauna if using alcohol, drugs or medications.
regnant women or persons with poor health should consult their physician before using any sauna.
Caution fire ha ard: Do not use the sauna room for drying clothes, bathing suits, etc. Do not hang towels above heater or place any object other than the rocks supplied on the heater. If any darkening of the wall around the heater is noticed discontinue sauna use immediately.
Inspect sauna regularly for re uired maintenance to heater, control and benches. eplace wood surfaces which show any signs of deterioration.
The heater gets extremely hot during operation and should not be touched or burns may result.
Minors should be ade uately supervised whenever near a hot or warming sauna.
Fire sprinkler systems used inside any sauna room should be properly rated for sauna room temperatures.
Do not pour chlorinated pool or spa water on heater. Excessive water use on heater may cause damage and void warranty.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

86(58,'(
(1(5$/,1)250$7,21 35,257286(
The first time you use the heater ……………………….12 rior to each use ……………………………………………. 12
86( The control panel in general……………………………… 13 Water reservoir……………………………………………….. 13 Other functions……………………………………………….. 13
(;7(51$/212))6:,7&+237,21 $)7(586(
Empty the reservoir…………………………………………. 14 Switch off main power switch……………………………. 14 0$,17(1$1&( Descaling the water reservoir……………………………. 15 Cleaning the fragrance holder/air humidifier and herb bowl……………………………………………………….. 15 Check the stone compartment …………………………. 15 7528%/(6+227,1 Troubleshooting the control panel …………………….. 15 Troubleshooting the sauna heater…………………….. 16 63$5(3$576/,67 52+65(675,&7,212)+$=$5’28668%67$1&(6 +($7(5:,5,1’,$*5$0
Electric Shock Ha ard – High voltage exists within this e uipment. There are no user serviceable parts in this e uipment. All installation and service to this e uipment should be performed by ualified licensed personnel in accordance with local and national codes.
Do not construct sauna room so as to restrict air flow through the bottom of the heater.
acking the rocks too tightly may cause the heater high limit switch to trip.
Maintain minimum clearance from heater to wooden surfaces (benches, side walls, heater fence etc.). Mounting brackets supplied. rovides proper clearance from wall behind heater.
Use only copper wire of the si e and type indicated in the Heater Specification Chart and the temperature rating indicated on the heater junction box.
A guardrail or fence is re uired around the heater to prevent burns from accidental contact.
All heaters and controls must be grounded per NEC to prevent electrical shock in case of unit failure.
Electrical outlets or receptacle must not be installed in a sauna room.
Do not locate benches over heater.
For household only.
eep this user guide In the event of any problems, please contact the retailer where you purchased the e uipment.
This publication may not be reproduced, in part or in whole, without the written permission of Tyl . Tyl reserves the right to make changes in materials, construction and design.

,167$//$7,21*8,'(
%()25(,167$//$7,21
3DUWV Check that the following parts are included in the packaging:

3

2

4

12

14 15 16

13

17

1
6 5

1

19

20

Elite

WiFi

21

22 23

24

25

7 9 10 26

3 Contact your dealer if anything is missing.

Control panel ure is supplied with Sense Combi ure. Control panel Elite WiFi is supplied with Sense Combi Elite. See separate guides.

,QVWDOODWLRQUHTXLUHPHQWV To ensure safe use of the heater, check that the following criteria are met:
Electrical wiring should be installed in accordance with NEC and all state and local codes. Fuse si e (A) and power cable si e (AW ) must be suitable for the heater (see The section called Connection/wiring diagram, age 9. The sauna ventilation must comply with the instructions in this manual (see The section called ositioning the inlet vent,
age 5, The section called ositioning the outlet vent, age 5). The position of the sauna heater, control panel, and sensors must comply with the instructions in this manual. The heater output (kW) must be suitable for the sauna volume (cu.ft.) (See Table 1, age 3). The minimum and maximum volumes must not be exceeded. NOTE: A FCI device is not re uired by ET . A FCI may be installed if re uired by local codes. However, FCI devices will tend to nuisance trip during use of the product.

Table 1: Voltage and sauna volume

Model

oltage Sauna volume Sauna volume

min. cu.ft.

max. cu.ft.

Sense Combi-U 7 20

175

265

SCU7

240

175

320

Sense Combi-U

20

250

360

SCU

240

250

440

27
Figure 1: Sauna heater/control panel parts
1. Sauna heater 2. Herb bowl/air humidifier 3. Herb bowl 4. rackets 5. Warning and Caution plates for the room in multiple languages 6. Screws 4 x 6.5 x 6 for Warning and Caution plates 7. Connectors x 3
. Spacers x 4 9. Screws x 4 10. racket screws x 2
12. Screw 4×6,5 (x 1 Combi ure) (x 2 Combi Elite) 13. Sensor cover (Combi ure) 14. Clips TC (3-5) x 10 pieces 15. lastic plugs 25×5 x 2 pcs 16. Screws 6×25 x 2 pcs 17. Humidity- and temperature sensor with cover (Combi Elite) 1 . Cable between heater and humidity- and temperature sensor,
10 4 4C, cable length 4 m x 1 pce (Combi Elite) 19. Control panel (Elite Wifi) 20. Cable between heater and control panel, 10 4 4C, cable
length 5 m x 1 pce 21. Cable tie 22. Clips C 3×5 x 10 pieces 23. Modular plug 4, 4/4 10 x 2 24. lastic plugs 25×5 x 3 pcs 25. Screws 6×25 x 3 pcs 26. ock guard 27. rotection hose 14×150 mm x 3 pcs, for 10 cables (sen-
sor, control panel, door switch)

,QVWDOODWLRQWRROV The following tools and materials are needed for installation and connection:
level tape measure electric drill screw drivers
,QVWDOODWLRQSODQQLQJ efore starting to install your sauna heater: lan the sauna heater positioning (see the Heater positioning – normal installation section, page 4). lan the control panel positioning (see the attached instructions for the control panel for allowable positioning). lan the sensor positioning (see Figure 3, page 4). osition the air intake vent (see the Air intake vent positioning section, page 5). osition the air exhaust vent (see the Air exhaust vent positioning section, page 5). lan the electrical installation (see the Connection/wiring diagram section, page 9).

4

3RVLWLRQLQJWKHFRQWUROSDQHO

34

The control panel can be installed inside or outside of the sauna

room.

The control panel must be correctly positioned with regard to

2

safety distances below when installed inside the sauna room

4

2

1 3
1

Figure 2: Schematic diagram of installation
1. Sauna heater 2. Control panel 3. Sensor 4. External on/off switch (option, door contact needed for func-
tion)
DANGER! No more than one heater may be installed in the same sauna cabin.

Figure 4: Safety distance, control panel
1. Heater 2. Control panel 3. Max. 36 in 4. Min. 12 in

3RVLWLRQLQJWKHKHDWHUQRUPDOLQVWDOODWLRQ osition the sauna heater: on the same wall as the door (or the side wall if very close to the door wall). osition the heater at a safe distance from the floor, side walls and interior fittings (see Figure 3).
osition the sensor according the picture (see Figure 3).

5

2

3

6

7
1 8

4 3

9 10 11

Figure 3: Positioning the heater – normal installation
1. Minimum distance from side wall: 4 in 2. Sensor position alt 1: 3 in from heater 3. Sensor 4. Sensor position alt 2: 3 in from heater front 5. Sensor position: 1 in from ceiling 6. Minimum distance from ceiling: 44 in 7. Minimum distance from interior fittings: 4 in
. Minimum ceiling height: 75 in 9. Minimum distance: 1 in 10. Minimum distance from interior fittings: 2 in 11. Distance from floor: 7 in

Figure 5: Warning/Caution plate

6DXQDURRPYHQWLODWLRQ In a sauna, the air should be changed about 6 times an hour. See
Figure 6.

It is recommended that ventilation openings meet the re uire-

ments of U Specification 75. The minimum opening should be

determined using one of the following formulas:

For

31,

9 .3

For

31,

0.3

5 5HPRYLQJWKH5RFN*XDUG Unscrew the two screws on the side of the heater and lift the rock guard upwards, see Figure 7. (This is necessary when filling the stone compartment or cleaning the fragrance holder and air humidifier).

where

the floor area of the room in s uare feet and the minimum vent si e in s uare inches

Example enting Calculation: oom is 54 s .ft.(9 ft. by 6 ft.) 54 is larger than 31.
Multiple 54 x 0.3 16.2 s . in. ent si e opening should be 4 in x 4 in.

3RVLWLRQLQJWKHLQOHWYHQW Install the inlet vent straight through the wall under the centerline
of the heater.

1

2

3

4

Figure 6: Positioning the air intake and exhaust vents
1. Inlet vent position. 2. Outlet vent position through the sauna wall. 3. Outlet vent position through the cavity. 4. Outlet vent position via duct.
3RVLWLRQLQJWKHRXWOHWYHQW
osition the outlet vent at the maximum possible distance from the air intake vent, e.g. diagonally (see Figure 6). high on the wall or in the ceiling (see Figure 6). so that it vents into the space that the door and air intake vent open into.

Figure 7: Removing the Rock Guard
5RRPFRQVWUXFWLRQ For safety and reliability, the following rules must be addressed.
The enclosed WA NIN : educe the risk of overheating warning plate must be mounted on or alongside the door
outside the sauna room at about eye level. Use the supplied screws. The enclosed CAUTION: educe the risk of fire caution plate must be mounted on the interior wall above the heater. Use the supplied screws. No permanent locking or latch system is to be used on the sauna door. Acceptable door fittings are: magnetic catches, friction catches, spring or gravity loaded closures. The door must always open outwards. No shower may be installed in a sauna room. No electrical receptacle shall be installed inside the sauna room. The heater should not be operated without its container properly filled with rocks and the rock guard in place. If an intercom speaker is installed, it should be away from the heater and as close to the floor as possible. If a room light is installed, it should be a surface mounted bracket type. Wall mounted lights should be about 70″ above the floor. Ceiling mounted lights should be of an approved type with a junction box that is remote to the fixture itself. Use only a fixture that uses A.F. or fixture type internal wiring. A 60 watt bulb should provide su cient lighting. Fire sprinkler systems installed inside any sauna room should be properly rated for sauna room temperatures. Always mount the heater according to these installation instructions.

The outlet vent must have the same area as the inlet vent. Ensure that the outlet vent is open. Mechanical ventilation is not recommended due to the risk of poor air exchange, which can negatively affect the heater temperature cut- out.

6 7SLFDOZDOOFRQVWUXFWLRQ

Figure 8: Typical wall construction ,167$//$7,21 6DXQDKHDWHULQVWDOODWLRQ 1. Attach the bracket and spacers to the wall following the speci-
fied dimensioning (see Figure 9). –
3

Figure 10: Opening/closing the cover
Connect the heater using standard wiring (Fk or E ) approved for fixed installation. Any single wires (Fk) must be protected in electrical conduits ( ) to the heater.
4. Connect the main supply electrical cable (1) to the terminal (2) (see Figure 11) according to the wiring diagram (see the Connection/wiring diagram section, page 9).

4

2

3

11 5

6

4

9 3

1 10

7

1

2

Figure 9: Bracket with screws and spacers
1. 26.3 in 2. 11.0 in 3. 7.3 in 4. 9.0 in (minimum distance)
It is easiest to prepare for installation with the heater lying down. To install the heater: 2. emove the cover to the water reservoir and lay the heater
down with the front facing upwards (see Figure 10). 3. Undo the screws and open the cover (see Figure 10).
WARNING! Always check that the heater is connected to the correct main/phase voltage!

Figure 11: Circuit board

7. ight cable (if connected)

1. Electrical cable

. Terminal for connection of

2. Terminal for connection of elec-

light (if connected)

trical cable

9. Strain relief connector for

3. Cable grommet (x6)

cables to modular contacts

4. Control panel cable

(x2)

5. Modular contacts for connection 10. Strain relief connector for

of control panel, sensor etc.

electrical cable

6. Sensor cable

11. rotection hose for 10

cables 5. un the cables for the control panel and the temperature

sensor through the cable grommets (3). Connect the control

panel cable (4) to one of the four S4 5 contacts (positions

6-9) (see Figure 11) according to the wiring diagram (see the

Connection/wiring diagram section, page 9 fig.19).

6. Connect the humidity- and temperature sensors cable (6) to

one of the four S4 5 contacts (positions 6-9) (5) according

to the wiring diagram (see the Connection/wiring diagram

section, page 9 fig. 19).

7. Connect the light cable (if relevant) (7), see Figure 11, to the terminal ( ) according to the wiring diagram Figure 19.
8. Close the cover and tighten the screws (see Figure 10). 9. Hang the heater on the bracket (see Figure 12).

7
12. Install the sensor on the wall see Fig 15 and 16. The thermistor wire may also be passed through the wall see Fig 17 and 1 . Seal any holes in the wall behind the sensor. The thermistor wire may be extended outside the sauna using low voltage wire (2-lead).

Figure 12: Hang the heater up.
10. Fit the spacers between heater and wall (to prevent the heater from being lifted off) (see Figure 13).

Combi Elite

Fig 13: Fit spacers
11. Fit the cover for the water reservoir, herb grille and fragrance holder/air humidifier (see Figure 14).

Fig 16: Installing the humidity- and temperature sensor – Combi Elite. The cable inside the sauna must be heat resistant.

Fig 14: Fitting the cover for the water reservoir, herb grille and fragrance holder/air humidifier

Fig 18: Wiring through the wall – Combi Elite.
8QXVXDOYROWDJHVQXPEHUVRISKDVHV Contact Tyl Customer Service before connecting to voltages or numbers of phases that are not listed in the wiring diagram Figure 19.
([WHUQDO212))VZLWFKRSWLRQ The external ON/OFF switch can be positioned anywhere outside the sauna, not to exceed 75 feet from the heater, to avoid voltage loss in the cable. oltage loss affects the ED indicator for heater status (if built-in and connected to the switch). For further information, see instructions supplied with the control panel.

9 &211(&7,21:,5,1’,$5$0

TA Model
Sense Combi-U 7 Sense Combi-U

20 1 hase

Amperage Output Wire Si e

Amps

kW

AW

26

5,3

10

30

6,3

240 1 hase

Amperage Output Wire Si e

Amps

kW

AW

30

7,0

35

,3

1RWH: Heating elments do not change for voltage changes. The heater output will changed based on the voltage applied to heater.

1234 5 6789

11

40 41 B B
120 V~

16 15 14 10

12 13

3 x 14 AWG RJ10 4P4C RJ10 4P4C

RJ10 4P4C ***
RJ10 4P4C

max 75 feet – Combi Elite
*** max 300 feet – Combi Pure

Figure 19: Wiring diagram
2. Ext switch (External switch Optional) 3. N/A 4. N/A 5. N/A 6. Sensor (humidity- and temperature) – Combi Elite. 7. N/A
. N/A 9. Controls panels (Elite).

5,3-8,3 kW 208/240 V~
G

14
14 AWG Max. 6 Amp.

10. Heater 11. Terminal for connection of electrical cable 12. Control panel (connect to positions 6-9) 13. Humidity- and temperature sensor – Combi Elite
(connect to positions 6-9) 14. ight/terminal for connection of light 15. Door contact (option) 16. External switch (option)

1 Pin

1:A 2:B 3:12V 4:GND

A B

2

11

12

Fig 20a: Connecting the humidity- and temperature sensor Combi Elite
1. Modular plug ( 10, see Fig 19) 2. Humidity- and temperature sensor

12 3 4

A

R

B

G

11

W

12

B

Fig 20b: Connecting the humidity- and temperature sensor Combi Elite
ed, reen, W White, lack

10 ‘HVFULSWLRQRIFDEOLQJPRGXODUFRQWDFWV

Pos 1. Pos 2. Pos 3. Pos 4. Pos 5.

NTC

Ext sw Door sw Bim/NTC Addon (option)

Pin 1:

Pin 1:

Pin 1:

Pin 1: Bim

Pin 2: NTC Pin 2: LED Pin 2: LED Pin 2: NTC

Pin 3: NTC Pin 3: SW Pin 3: SW Pin 3: NTC

Pin 4:

Pin 4: 12 V Pin 4: 12 V Pin 4: Bim

1 2 34

5

10

Pos 6-9.

4x RS485

6

7

8

9

Pin 1: A

Pin 2: B

Pin 3: 12 V

Pin 4: GND

Pin: 1 2 3 4

Figure 21: Modular contacts, description (Pos 1-4 and 6-9: RJ10, Pos 5: RJ45)

2. Ext switch (External switch Optional) 3. N/A 4. N/A 5. N/A 6. Sensor (humidity- and temperature) – Combi Elite. 7. N/A
. N/A 9. Controls panels (Elite). 10. Modular plug ( 10)11. Modular contact ( 10)

Pin: 4 3 2 1
11

NOTE! Crimp pliers are needed if changing modular cabling, e.g. shortening wires.
6(/),163(&7,212)7+(,167$//$7,21 To check the installation: 1. Turn power on at the Circuit reaker ox. 2. Check that the control panel lights up. 3. Start the heater (see User uide). 4. Check that all three tubular elements start to heat up (go
red).
lease keep these instructions . In the event of problems, please contact the retailer where you purchased the e uipment.
This publication many not be reproduced, in part or in whole, without the written permission of Tyl . Tyl reserves the right to make changes to materials, construction and design.

11 ‘,0(16,216
17,0″ 7,3″

14,8″

24,4″

1,6″

(11″) 19,3″

12
86(58,'(
(1(5$/,1)250$7,21

‘HIDXOWVHWWLQJV Using the control panel for the first time:
See instructions supplied with the control panel.

Congratulations on your new sauna heater Follow this user guide to get the most from your purchase. Wet and dry saunas are forms of bathing which originate way back in history. A hot sauna is best enjoyed at temperatures between 145-190 F.
35,257286(

3ULRUWRHDFKXVH Check the following Check that:
there are no foreign objects in the sauna cabin, on or in the heater. the door and any windows to the sauna cabin are closed. that the sauna door opens outwards with a little pressure.

7KH¿UVWWLPHRXXVHWKHKHDWHU Fill the stone compartment
NB: Always use dolerite stones (Manufacure’s Stones)! “Ordinary” stones may damage the heater. Do not use ceramic stones. Ceramic stones may damage the heater. The heater guarantee does not cover damage caused by ceramic stones.
Fill the stone compartment around the heating elements from the bottom to the top, to approx. 2″ above the top front edge. Do not press the stones into place. Capacity: Approx. 35 lb of stones.
lace the stones loosely to allow optimum air circulation. The tubular heating elements must not be s uee ed together or against the side.

1% DANGER! Fragrant essences and similar products may ignite, if poured directly onto the stones.
NOTE! Do not use the sauna cabin for any purpose other than taking saunas.
7XUQRQWKHPDLQSRZHUVZLWFK
The main power switch is at the bottom of the heater. Switch it on, if it is not already switched on (see Figure 2).

Sauna stones must: tolerate extreme heat and fluctuations caused by water being poured on them. be cleaned before use. must have an uneven surface, so that the water clings to the stone surface and evaporates e ciently. be between 1-1/2″ to 2″ in si e to allow air circulation in the stone compartment. This will increase the life of the tubular elements.

NB: Never place stones on top of the side air chambers. This way will obstruct air circulation, causing the unit to overheat and the cut-out switch to activate.

1

2

1

Figure 2: Positioning of the main power switch 1. Main power switch

Figure 1: Filling the stone compartment
1. Stone compartment 2. Side chambers
Turn on the heater to remove any new paint odors To remove new paint odor from the heater: Heat the sauna heater for about one hour. The water reservoir does not need to be working. A little smoke may appear.

86(

13 Water reservoir in operation:

7KHFRQWUROSDQHOLQJHQHUDO See instructions supplied with the control panel.
:DWHUUHVHUYRLU The sauna heater works with and without water in the tank. When the water reservoir is in use, max. two out of three heater elements in the stone compartment will be working. The heater switches automatically between the reservoir and stone compartment, depending on which setting has been set on the control panel. See the instructions supplied with the control panel.
Filling the water reservoir:

1. When in use and if the water level drops below the upper level sensor, it will continue to operate as normal but a single filled-in drop symbol will show on the Elite control panel display ( ure control panel shows unlit water drop). Water can be added, and a steady audio signal will sound when the water level reaches full.
2. When in use and if the water level drops below the safety sensor, three pulsing audio signals will sound and two empty drop symbols will show on the Elite control panel display ( ure control panel shows a flashing water drop when the heater is operating). This indicates that there is insu cient water in the reservoir, and the heater element will automatically switch off.

efore starting the heater, fill the water reservoir by carefully pouring tap water through the herb grille, see fig. 3.

2WKHUIXQFWLRQV

)UDJUDQFHKROGHU

DANGER! Never put fragrances in the herb bowl or water reservoir.

DANGER! Fragrant essences etc. may ignite if poured directly onto the stones.

Figure 3: Filling the water reservoir.
Note! Never use salt water – can damage the heater element in the reservoir. It can also cause a build up of foam which causes the level sensor to detect a higher water level than actual, and the heater elements can break.

To create a pleasant fragrance in the sauna, pour a few drops of Tyl Sauna Fragrance into the water in the fragrance holder.
ou can also mix a few drops of the sauna fragrance with water in a sauna bucket and pour the water on fully heated stones. Use a sauna ladle for pouring water on the hot stones.
our max. 1-2 ladles of water at a time, and then wait until the stones have regained su cient heat before pouring fresh water on the stones again.
Tyl Sauna Fragrance comes in different variants and fragrances.

1. An empty reservoir is shown by two empty drop symbols on the Elite control panel display ( ure control panel shows a flashing drop symbol when the heater is operating). If the reservoir is empty when activating the main switch, three pulsing audio signals will sound

1

2

2. When the water level reaches the safety sensor, a filled drop symbols will shown on the Elite control panel display ( ure control panel shows an unlit drop symbol). The heater element in the reservoir can be started.

3. When the water level reaches the upper level sensor, two filled-in drop symbols will show on the Elite control panel display ( ure control panel shows unlit water drop). A continuous audio signal will also sound for approx.: 2 secs, indicating that the water level in the tank is full (in case you do not check the control panel display during filling).
Note! Do not add more water after the audio signal to avoid the water boiling over and out of the reservoir.

Figure 4: Other functions 1. Herb bowl 2. Fragrance holder/air humidifier
+HUEERZO A fragrant, refreshing herbal sauna can be created with fresh or dried herbs or spices. Enjoy pleasant herbal fragrances in a steamy tropical climate. To create a fragrant sauna using fresh or dried herbs, put the herbs in the herb bowl (see Figure 4).
TIP! Try dierent combinations, such as birch, lavender, mint, spices, tea bags and other exciting fragrances.

14 $LUKXPLGL¿HU
WARNING! Do not confuse the instructions for the air humidifier with those for the water reservoir.
DANGER! Do not pour water into the fragrance holder once it has been heated up, as this can cause boiling water to splash on the sauna occupants. Do not stand or sit in front of the heater while water is being poured into the fragrance holder, as hot water can spray out suddenly.
To maintain a comfortable basic level of humidity in the sauna, fill the built-in air humidifier (see Fig. 4) with water before switching on the sauna.
Tip: Pour a few drops of diluted sauna fragrance into the built-in air humidifier.

2
1
3

(;7(51$/212))6:,7&+237,21
External ON/OFF switch can be installed anywhere outside the sauna. The switch is momentary pulse or constant activation. The heater circuit automatically recognises which is used. Heater status and faults on the door contact can be seen if the switch has a built-in ED. See instructions supplied with the control panel.

Figure 5: Emptying the water reservoir.
1. Water reservoir hose. 2. emove plug 3. ower hose into a suitable container
6ZLWFKRPDLQSRZHUVZLWFK
CAUTION! The heater’s memory function will be cancelled if disconnected from the mains for more than 7 days. The date and time will have to be reprogrammed.

$)7(586( (PSWWKHUHVHUYRLU

The main power switch is at the bottom of the heater. Switch off here when the heater is not to be used for an extended period (e.g. several weeks).

DANGER! Hot water! Wait until the water has cooled before completing this step.

To prevent the build-up of limescale and higher salt/mineral levels, empty the reservoir after each bath. If this is not done and water is added each time you take a sauna, foam build-up can occur which can cause the level sensor to detect a higher water level than actual, with a risk that the heater element will break. To empty: 1. elease the hose from the hose clip. 2. Hold the hose up and remove the plug. 3. ower the hose into a suitable container and drain off the
remaining water. 4. Hang the hose on the hose clip.
1

Figure 6: Location of main power switch

0$,17(1$1&(
$IWHUHDFKXVH Empty the water reservoir.

$VUHTXLUHG
Descale the water reservoir.
Clean the herb bowl and fragrance holder.
Clean the electrodes using a cloth or similar. See fig. 7.

2QFHDQQXDOO
Check the stone compartment.

15
WARNING! If the stone compartment fills up with gravel and small stones, the tubular element can be damaged as a result of overheating, as air flow will be insucient.

1
Figure 7: Cleaning the electrodes 1. Electrodes
‘HVFDOLQJWKHZDWHUUHVHUYRLU Descale the water reservoir as re uired using Tyl descaling agent. How to descale: 1. emove the herb grille from the herb bowl. 2. Start the steam function (see The section called Use, age
13) and run until the water boils. 3. Switch off the heater, and wait for about 5 minutes. 4. Mix 2 cups of descaling agent and pour into the water inlet. 5. eave the descaling agent to work for 1 hour, empty the res-
ervoir and rinse thoroughly. 6. If necessary, repeat the procedure several times until all lime-
scale has been removed.
&OHDQLQJWKHIUDJUDQFHKROGHUDLUKXPLGL¿HUDQGKHUEERZO Clean the fragrance holder/air humidifier and herb bowl as re-
uired. To clean the fragrance holder/air humidifier and herb bowl:
ift out the fragrance holder/air humidifier and herb bowl and rinse them under running water.

7528%/(6+227,1*
7HPSHUDWXUH6DIHW6ZLWFKHV The heater s temperature protection devices:
PCA – The temperature safety on the CA in the heater is designed to prevent components being damaged by overheating. If the safety switch is triggered, an error code shows on the control panel display. If the overheating switch has activated, the heater cannot be started again until the temperature has dropped down 6 degrees ( F) on the CA.
Water reservoir – The temperature safety switch in the reservoir is designed to protect the heater element from boiling dry. There is a red reset button under the heater which must be pressed in (see Fig. 9). If the cut-out has activated, the button will feel stiff and will click when reset. If the cut- out has not activated and after resetting, the button will feel springy.
Heater – The temperature cut-out in the heater protects the components and woodwork in the sauna from overheating. There is a white reset button on the left side of the heater which must be pressed in (see Fig. 9). If the heater safety switch has activated, the button will feel stiff and will click’ when reset.
Information! When the overheating safety switches activate, always check the cause of the problem. The life of the elements and CA can be adversely eff ected by each overheating. If systems continues to overheat look at the following: entilation defi cient oom volume Internal heater fault Water reservoir not properly cleaned

Figure 8: Cleaning the fragrance holder/air humidifier and herb bowl

&KHFNWKHVWRQHFRPSDUWPHQW

Check the stone compartment at least once annually or as many times per year as the heater is used per week.

2

1

Example: If the unit is used 3 times a week, check the stone compartment 3 times per year.

Figure 9: Resetting the temperature cut-out 1. Temperature cut-out water reservoir

How to check the stone compartment:

2. Temperature cut-out sauna heater

1. emove all stones from the compartment.

2. emove any small stones, gravel and lime-scale from the

compartment. 3. ut whole, undamaged stones back. eplace damaged
stones with new ones as re uired (see Filling the stone com-

7URXEOHVKRRWLQJWKHFRQWUROSDQHO See instructions supplied with the control panel.

partment, page 13).

16 7URXEOHVKRRWLQJWKHVDXQDKHDWHU

Information!
Contact the dealer during the guarantee period in the event of faults. See the instructions for the control panel for details of faults not covered in this user guide.

Table 1: Troubleshooting the sauna heater

Symptom

ossible cause

emedy

Heater is on but does not create steam. Water boils in reservoir.

1. Water level incorrect. Minimum water level for safety sensor
2. Humidity settings on control panel do not correspond to operating status
3. Water reservoir temperature cut-out activated 4. Heater element in reservoir faulty 5. If the sauna structure has deficient ventilation in
conjunction with dry sauna and high sauna temperature (operating with no water in reservoir), the temperature cut-out can activate because of higher radiating temperature in the heater.

1. Fill up reservoir. 2. Set humidity to correspond to reservoir operation –
read control panel manual. 3. eset temperature cut-out. For more information,
see the section on temperature cut-out on page 14. If the steam function does not work after reset, there is a risk of the reservoir being damaged. 4. An authori ed electrician is re uired to find the fault. 5. Check for possible deficient ventilation.

Heater element in heater stone compartment does not warm up.

1. Temperature settings on control panel do not cor- 1. Set temperature to correspond to heater element

respond to operating status

operation in stone compartment.

2. Water reservoir in operation Only two of the

2. See the instructions supplied with the control

three heater elements in the stone compart-

panel.

ment can operate at the same time as the tank, 3. Check and replace/reset the fuses in the main

otherwise excessive current is drawn from the

switchboard.

electricity supply. This is not a fault outside nor- 4. An authorised electrician is re uired to find the

mal operation.

fault.

3. Some of the heater fuses on the main switch-

5. An authorised electrician is re uired to find the

board can have tripped out

fault.

4. esistor coil in the heater element faulty

5. Internal heater C fault

ights in the sauna 1. Is lighting connected to the heater

do not come on

2. Internal heater C fault

when switched on

at the control panel.

1. erify with authori ed electrician who performed installation of heater/lighting.
2. An authori ed electrician is re uired to find the fault.

Heater does not work, control panel does not light up.

1. The main power switch is off

1. Turn heater main power switch.

2. Circuit breaker tripped on main electical panel. 2. Check and replace/reset the fuses in the main

3. oose contact in cabling between heater and

switchboard.

control panel

3. Switch off heater main power switch and connect

4. The specific 12 DC output on one of the C s

each/paired cable to the control panel. Switch on

S4 5 modular jack to the control panel is faulty

heater main power switch again. If this does not

due to short-circuit

help, an authori ed electrician is re uired to find

5. Transformer on C in heater faulty

the fault.

6. Control panel faulty

4. e uires an authori ed electrician to find the fault,

faulty 12 DC output is indicated by ED out next

to the S4 5 output. Note: if the fault is in the

10 cable to the control panel, do not click into

a working vacant S4 5 outlet to avoid causing a

fault in that outlet. 10 cable must be replaced/

contacts fitted in the event of a fault.

5. An authori ed electrician is re uired to find the

fault.

6. An authori ed electrician is re uired to find the

fault.

The fuses or circuit 1. There is a short-circuit at the heater ND. Can

breaker in the build-

be due to a faulty heater element

ing breaker panel 2. ighting connected to and controlled via the

trips as soon as the

heater faulty

heater is turned on. 3. The heater has not been used for a long period,

causing an insulation fault in the heater ele-

ment

4. Heater has had too much water poured on it

5. Other internal heater fault

1,2,3,4,5. Do not use the heater, switch off at main heater main switchboard trip and disconnect heater fuses on the main switchboard. An authori ed electrician is re uired to find the fault.

63$5(3$576/,67 1
10 2

3

4

2 4 5
3 7

17
6

8

5

6 11
1

9

7

12

Figure 11: Spare parts 2

Figure 10: Spare parts 1

1. Combi U Tubular Elements Combi U7 Tubular element
2. Stone compartment 3. Circuit board 4. Terminal block 5. Water tank temperature safety switch 6. Sauna heater temperature safety switch 7. Strain relief connector
. On/Off Switch 9. On/off dial 10. ock uard 11. NTC sensor – Combi Pure 12. Humidity- and temperature sensor – Combi Elite

3001-924 3001-920 n/a 9600 006 9600 0723 9600 0002 3119-607 9600 0554 9600 0040 9600 0132
019-541 9600 0219 9600 0074

1. 9600 0223 Tubular element 2. 9600 0730 Herb bowl 3. 9600 0731 Hose with plug 4. 9600 0732 Filler grille 5. 9600 0733 Wall bracket 6. 9600 0734 Electrodes 7. 9600 021 Water reservoir
52+65(675,&7,212)+$=$5’28668%67$1&(6
Instructions for environmental protection: Do not dispose of this product with the domestic refuse when no longer in use. Take it to a recycling station for electrical and electronic e uipment instead. For further information, see the symbol on the product, manual or packaging.

Figure 12: Symbol

lease keep these instructions . In the event of problems, please contact the retailer where you purchased the e uipment.
This publication many not be reproduced, in part or in whole, without the written permission of Tyl . Tyl reserves the right to make changes to materials, construction and design.

The different materials can be recycled as specified by their labelling.
ou can help protect the environment by recycling or reusing the spent appliances or the materials in them. Take the product to a recycling centre without the sauna stones or the soapstone jacket (if fitted). Contact your local authorities for details of your nearest recycling centre.

1 +($7(5:,5,1’,$5$0

WATER TANK

GND

Electrodes

BACK MIDDLE FRONT

High Limit Control Heater

31 42

NTC (Sensor) Ext Switch Door Switch Sec/NTC Add On

High Limit Control Water tank

Circuit board

GND M H

H3 H2 H1 H.Tank Light Aux 0
Sec/NTC

X17 X18

X1

X2

X3 X4 X5 X6

X7 X8 X9 X10 X11 X12 X13 X14 X15 X16

Type kW Sense 5.3 Combi-U 7 7.0
Sense 6.3 Combi-U 8 8.3

208 V~ Amp AWG 26 10

30 8

Use only 194° F copper wire Don´t forget to earth (ground)!

240 V~

Amp AWG

30 8

35 8

Switch

6

f

a

b

c

d

e

P1 P2 P3

1

2

3

1

2

3

4

5

GND GND

12345G

40 41 B B

L1

L2 GND

208-240V, 1-ph

120 V~ N

120 Volt Light input

(Separate from

Heater Power)

AWG 14 Max 6 Amp.

Output to light

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

TYLO User Manuals

Related Manuals