Honeywell NDM-100-A Series Dual Monitor Module Instructions

June 9, 2024
Honeywell

Honeywell logo NDM-100-A Series Dual Monitor Module
Instructions Honeywell NDM-100-A Series Dual Monitor
ModuleMonitor Modules
NMM-100(A), NMM-100P(A), NZM-100(A),
and NDM-100(A) for FireWarden Series

Intelligent Addressable Devices

General

Four different monitor modules are available for Notifier’s FireWarden Series intelligent control panels for a variety of applications. Monitor modules supervise a circuit of  dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (NZM-100(A)).
NMM-100(A) is a standard-sized module (typically mounts to a 4″ [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices.
NMM-100P(A) is a miniature monitor module a mere 1.3″ (3.302 cm) H x 2.75″ (6.985 cm) W x 0.65″ (1.651 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the NMM-100P(A) to be mounted in a single-gang box behind the device it monitors.
NZM-100(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit.
NDM-100(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems.
LiteSpeed™ is a communication protocol that greatly increases the speed of communication between analog intelligent devices.
Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on
single points. The net effect is response speed greater than five times that of other communication protocols.
NMM-100(A) Monitor Module

  • Built-in type identification automatically identifies this device as a monitor module to the control panel.
  • Powered directly by two-wire SLC loop. No additional power required.
  • High noise (EMF/RFI) immunity.
  • SEMS screws with clamping plates for ease of wiring.
  • Direct-dial entry of address: 01 – 99 on FireWarden-1002, 01 – 50 on FireWarden-50.
  • LED flashes during normal operation and latches on steady to indicate alarm.

The NMM-100(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches.
It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator.

NMM-100(A) APPLICATIONS

Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normallyopen dry-contact alarm activation devices. May also
be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit.

NMM-100(A) OPERATION

Each NMM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/
normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).

NMM-100(A) SPECIFICATIONS

Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 375 µA (LED flashing), 1 communication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5″ (11.43 cm) high x 4″ (10.16 cm) wide x 1.25″ (3.175 cm) deep. Mounts to a 4″ (10.16 cm) square x 2.125″ (5.398 cm) deep box.

NMM-100P(A) Mini Monitor Module

  • Built-in type identification automatically identifies this device as a monitor module to the panel.
  • Powered directly by two-wire SLC loop. No additional power required.
  • High noise (EMF/RFI) immunity.
  • Tinned, stripped leads for ease of wiring.
  • Direct-dial entry of address: 01 – 99 on FireWarden-100-2, 01 – 50 on FireWarden-50.

Honeywell NDM-100-A Series Dual Monitor Module -
diagram

The NMM-100P(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed  without rigid mounting. The NMM-100P(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches.
It provides a twowire initiating device circuit for normally-open-contact fire alarm and security devices. NMM-100P(A)
NMM-100P(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry- contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the circuit.
NMM-100P(A) OPERATION
Each NMM-100P(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC).
NMM-100P(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Shorted).
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 450 µA.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3″ (3.302 cm) high x 2.75″ (6.985 cm) wide x 0.65″ (1.651 cm) deep.
Wire length: 6″ (15.24 cm) minimum.
NZM-100(A) Interface Module
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry entry of address:, 01 – 99 on FireWarden100-2, 01 – 50 on FireWarden-50.
• LED flashes during normal operation.
• LED latches steady to indicate alarm on command from control panel.
The NZM-100(A) Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All  two-wire detectors being monitored must be UL compatible with the module.
NZM-100(A) APPLICATIONS
Use the NZM-100(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms).
Install ELR across terminals 8 and 9 for Style D application.
NZM-100(A) OPERATION
Each NZM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/
normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
NZM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 Ohms.
Average operating current: 270 µA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K Ohms.
External supply voltage (between Terminals T10 and T11):

  • DC voltage: 24 volts power limited.
  • Ripple voltage: 0.1 Vrms maximum.
  • Current: 90 mA per module maximum.

Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5″ (11.43 cm) high x 4″ (10.16 cm) wide x 1.25″ (3.175 cm) deep. Mounts to a 4″ (10.16 cm) square x 2.125″ (5.398 cm) deep box.
NDM-100(A) Dual Monitor Module
The NDM-100(A) Dual Monitor Module is intended for use in intelligent, two- wire systems. It provides two independent twowire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panelcontrolled LED.
NOTE: The NDM-100(A) provides two Style B (Class B) IDC circuits  ONLY.
Style D (Class A) IDC circuits are NOT supported in any application.
NDM-100(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 µA (LED flashing).
Maximum IDC wiring resistance: 1,500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 µA
EOL resistance: 47K Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5″ (11.43 cm) high x 4″ (10.16 cm) wide x
1.25″ (3.175 cm) deep. Mounts to a 4″ (10.16 cm) square x
2.125″ (5.398 cm) deep box.
NDM-100(A) AUTOMATIC ADDRESSING
The NDM-100(A) automatically assigns itself to two addressable points, starting with the original address. For example, if the NDM-100(A) is set to address “26”, then it will
automatically assign itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the NDM-100(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. !

Installation

NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4″ (10.16 cm) square, 2.125″ (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only.
The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL: S635.
  • ULC: S635.
  • FM Approved.

CAUTION:
Avoid duplicating addresses on the system.

  • CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM100); 7300-0028:0237 (NDM-100).
  • MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); 227-03-E Vol. 3 (NDM-100).

Product Line Information
NOTE: “A ” suffix indicates ULC-listed model.
NMM-100(A): Monitor module.
NMM-100P(A): Monitor module, miniature.
NZM-100(A): Monitor module, two-wire detectors.
NDM-100(A): Monitor module, dual, two independent Class B circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 52304.

Honeywell logoNotifier® and FireWarden® are registered trademarks and LiteSpeed™ and
FireWatch™ are trademarks of Honeywell International Inc.
©2015 by Honeywell International Inc. All rights reserved.
Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier.
Phone: 203-484-7161, FAX: 203-484-7118.
www.notifier.com
DN-6999:E • 07/30/2015