Majestic BE36 Woodburning Fireplace Instruction Manual

June 9, 2024
Majestic

Majestic BE36 Woodburning Fireplace

Majestic-BE36-Woodburning-Fireplace-PRODUCT

Product Information

The wood burning fireplace comes in two models: BE36 and BE42. It requires the use of SL300 Series Chimney and needs to have a 2-inch clearance to combustibles and building insulation from the chimney. The installation and service of this appliance should be performed by qualified personnel. Hearth & Home Technologies recommend HHT Factory Trained or NFI certified professionals. The fireplace is designed for use with solid wood fuel only; other fuels may overfire and generate poisonous gases like carbon monoxide

Product Usage Instructions

  1. Read the entire installation manual before proceeding with the installation.
  2. Ensure that the installation is carried out by a qualified professional.
  3. Do not discard the manual as it contains important safety information.
  4. Use only solid wood fuel in the fireplace.
  5. Ensure that the chimney and termination requirements are met.
  6. Construct the chase and frame the fireplace according to the provided instructions.
  7. Install the chimney system as per the instructions.
  8. Finish the fireplace with non-combustible materials and ensure proper clearance to combustibles.
  9. Before usage, check all the components for any damage or defects, and ensure that they are installed correctly.
  10. Keep the area around the fireplace clear of any combustible materials.
  11. Do not leave a fire unattended, and ensure that all fires are fully extinguished before leaving the area.
  12. Regularly inspect and clean the chimney to prevent creosote buildup and other potential fire hazards.
  13. If there is any smell of gas, immediately turn off the gas supply and contact a qualified professional for assistance.

By following these usage instructions, you can safely enjoy the warmth and comfort of your wood-burning fireplace.

INSTALLER : Leave this manual with party responsible for use and operation.
OWNER : Retain this manual for future reference.
This fireplace uses SL300 Series Chimney
2” CLEARANCE TO COMBUSTIBLES AND BUILDING INSULATION FROM CHIMNEY REQUIRED

NOTICE : DO NOT discard this manual

Installation and service of this appliance should be performed by qualified personnel. Hearth & Home Technologies recomends HHT Factory Trained or NFI certified professionals

WARNING : If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death

  • DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
  • DO NOT overfire. Overfiring will void your warranty.
  • Comply with all minimum clearances to combustibles as specified. Failure to comply may cause house fire.

WARNING HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.

  • DO NOT touch glass until it is cooled
  • NEVER allow children to touch glass
  • Keep children away
  • CAREFULLY SUPERVISE children in same room as the fireplace.
  • Alert children and adults to hazards of high temperatures. High temperatures may ignite clothing or other flammable materials.
  • Keep clothing, furniture, draperies and other flammable materials away.

WARNING
For use with solid wood fuel only. Other fuels may overfire and generate poisonous gases (i.e. carbon monoxide).

Safety Alert Key:

  • DANGER! Indicates a hazardous situation that, if not avoided will result in death or serious injury.
  • WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
  • CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
  • NOTICE : Indicates practices that may cause damage to the fireplace or to property.

ATTENTION INSTALLER: Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in htis installation manual.

  • Customer:
  • Lot/Address
  • Model (circle one): BE36 BE42
  • Date Installed:
  • Location of Fireplace: Installer:
  • Dealer/Distributor
  • Phone #
  • Serial #:

WARNING! Risk of Fire or Explosion! Failure to install fireplace acording to these instructions can lead to a fire or explosion.

Fireplace Install

  • Verified that the chase is insulated and sealed. (Pg. 11)
  • Verified clearances to combustibles. (Pg. 10)
  • Fireplace is leveled and secured. (Pg. 12)
  • Protective hearth strips installed per manual requirements. (Pg. 13)
  • Hearth extension size/height decided. (Pg. 28)
  • Outside air kit installed. (Pg 14)

Chimney Section 4 & 5 (Pg. 15)

  • Chimney configuration complies with diagrams.
  • Chimney installed, locked and secured in place with proper clearance.
  • Chimney air kit installed.
  • Firestops installed.
  • Attic insulation shield installed.
  • Roof flashing installed.
  • Termination installed.
  • Shrouds Section 6 (Pg. 25)
  • Shroud is installed properly per instructions.

Finishing Section 7 (Pg. 27)7 (P 27)

  • Combustible materials not installed in non-combustible areas.
  • Verified all clearances meet installation manual requirements.
  • Mantels and wall projections comply with installation manual requirements.
  • Hearth extension installed per manual requirements.

Fireplace Setup Section 8 (Pg. 34)

  • All packaging and protective materials removed.
  • Refractory installed correctly.
  • Grate is properly installed.
  • Firescreen properly installed.
  • Optional doors properly installed.
  • Manual bag and all of its contents are removed from the fireplace and given to the party responsible for use and operation.

Hearth & Home Technologies recommends the following:

  • Photographing the installation and copying this checklist for your file.
  • That this checklist remain visible at all times on the fireplace until the installation is complete.

Comments : Further description of the issues, who is responsible (Installer/Builder/Other Trades, etc.) and corrective action needed:
Comments communicated to party responsible

  • (Builder/Gen. Contractor)
  • (Installer)
  • (Date)

Product Specific & Important Safety Information

Fireplace Certification

This fireplace system has been tested and listed in accor-dance with UL 127 and ULC-S610 standards by Under-writers Laboratories Inc. for installation and operation in the United States and Canada.
This fireplace may be installed in sleeping rooms EX-CEPT in manufactured homes. If installed with a gas log set, provisions for the National Fuel Gas Code must be met.
This fireplace has been tested and listed for use with the optional components specified in this manual. These optional components may be purchased separately and installed at a later date. An outside air kit, gas insert, gas log set or gas log-lighter should be installed at the time of fireplace installation.
WARNING! Risk of Fire! Hearth & Home Technologies disclaims any responsibility for, and the warranty and agency listing will be voided by the following actions.

DO NOT:

  • install or operate damaged fireplace
  • modify fireplace
  • install other than as instructed by Hearth & Home Technologies
  • operate the fireplace without fully assembling all components
  • overfire
  • install unvented gas log set
  • install any component not approved by Hearth & Home Technologies
  • install parts or components not Listed or approved

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified installer, service agency or your dealer.

WARNING : This product and the fu-els used to operate this product (wood and wood pellets), and the products of combustion of such fuels, can expose you to chemicals including carbon black, which is known to the State of California to cause cancer and carbon monoxide, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.

Non-Combustible Materials

  • Materials which will not ignite and burn, composed of any combination of the following:
    • * Steel – Iron
    • Brick – Tile
    • Concrete – Slate
    • Glass – Plasters
  • Materials reported as passing ASTM E 136, Standard

Test Method for Behavior of Metals, in a Vertical Tube Furnace at 750° C

Combustible Materials

  • Materials made of or surfaced with any of the following materials:
    • Wood – Compressed paper
    • Plant fibers – Plastic
    • Plywood/OSB – Sheet rock (drywall)
  • Any material that can ignite and burn; flame proofed or not, plastered or un-plastered

Getting Started

Typical Fireplace SystemMajestic-BE36-Woodburning-Fireplace-FIG-
\(3\)

Design and Installation Considerations

NOTICE : Check building codes prior to installation.

  • Installation MUST comply with local, regional, state and national codes and regulations.

  • Consult insurance carrier, local building inspector, fire officials or authorities having jurisdiction over restrictions, installation inspection and permits.

  • Before installing, determine the following:

    • Where the fireplace is to be installed.

    • The vent system configuration to be used.

    • Gas supply piping.

    • Electrical wiring.

    • Framing and finishing details.
      Note : A raised hearth extension built flush with the fireplace opening or less than 4 in. (102 mm) below the fireplace opening requires the fireplace be installed on a noncombustible surface.

    • Whether optional accessories – devices such as a fan, wall switch or remote control – are desired.

Selecting Fireplace Locations
This fireplace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.2

Locating the fireplace in a basement should be avoided.
Locating near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance. Consideration should be given to these factors before deciding on a location.
NOTICE : In addition to these framing dimensions, also reference the following section:

  • Clearances (Section 3).

NOTICE:

  • Illustrations and photos reflect typical installations and are FOR DESIGN PURPOSES ONLY.
  • Illustrations/diagrams are not drawn to scale.
  • Actual installation/appearance may vary due to individual design preference.
  • Hearth & Home Technologies reserves the right to alter its products.

NOTICE:

  • A minimum 1/2 in. air clearance at the back and sides of the fireplace assembly must be maintained.
  • Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney sectionsMajestic-BE36-Woodburning-Fireplace-FIG- \(4\)

Locating Fireplace & Chimney
Location of the fireplace and chimney will affect performance.

  • Install within the warm airspace enclosed by the building envelope. This helps to produce more draft, especially during lighting and die-down of the fire.
  • Installing the fireplace in a basement is not recommended.
  • Penetrate the highest part of the roof. This minimizes the effects of wind loading.
  • Locate termination cap away from trees, adjacent structures, uneven roof lines and other obstructions.
  • Minimize the use of chimney offsets.
  • Consider the fireplace location relative to floor and ceiling and attic joists.
  • Take into consideration the termination requirements in Sections 4 and 5.
  • Install the outside air kit with the intake facing prevailing winds during the heating season.
  • Ensure adequate outdoor air for all combustion appliances and exhaust equipment.
  • Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the fireplace.
  • Avoid installing the fireplace near doors, walkways or small isolated spaces.
  • Recessed lighting should be a “sealed can” design.
  • Attic hatches weather stripped or sealed.
  • Attic mounted duct work and air handler joints and seams taped or sealed.Majestic-BE36-Woodburning-Fireplace-FIG- \(5\)

Tools and Supplies Needed

Before beginning the installation be sure the following tools and building supplies are available:

  • Reciprocating saw Framing material
  • Pliers Non-combustible sealant
  • Hammer Gloves
  • Phillips screwdriver Framing square
  • Flat blade screwdriver Electric drill and bits
  • Plumb line Safety glasses
  • Level Tape measure

1/2-3/4 in. length, #6 or #8 self-drilling screws Misc. screws and nails

Inspect Fireplace and Components

WARNING! Risk of Fire and/or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep fireplace dry.

  • Remove fireplace and components from packaging and inspect for damage.
  • Vent system components and doors are shipped in separate packages.
  • Report to your dealer any parts damaged in shipment.
  • Read all the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit.

Fireplace System Requirements
The HHT fireplace system requirements consist of the following:

  • Fireplace
    • Refractory (included with fireplace)
    • Firescreen (included with fireplace)
    • Grate (included with fireplace)
    • Hearth Extension (required, sold separately)
  • Outside Air System (optional)
    • Air Inlet Hood
    • Flex
  • Chimney System
    • Attic Insulation Shield (included with fireplace)
    • Chimney air kit (required in Canada, sold separately)
    • Chimney termination cap (required, sold separately)
  • Non-combustible finish material

Framing and Clearances

Appliance Dimensions/WeightMajestic-BE36-Woodburning-Fireplace-FIG-
\(6\)

Clearances

WARNING! Risk of Fire!
You must comply with all minimum air space clearances to combustibles as specified in Figure 3.2. DO NOT pack required air spaces with insulation or other materials.
Framing or finishing material used on the front of, or in front of, the fireplace closer than the minimums listed must be constructed entirely of non- combustible materials (i.e., steel studs, concrete board, etc.). Failure to comply may cause fire.

Minimum Clearances to Combustibles

WITHIN ENCLOSURE AREA

Fireplace to backwall| 1/2 in. (13 mm)
Fireplace to sidewall| 1/2 in. (13 mm)
Top standoffs to header| 0 in. (0 mm)
Door opening to sidewall| 12 in. (305 mm)
MANTEL
Mantel minimum height| 12 in. (305 mm)

above opening

Maximum mantel depth| 12 in. (305 mm)

Majestic-BE36-Woodburning-Fireplace-FIG- \(7\)

Construct the Chase

  • A chase is a vertical boxlike structure built to enclose the fireplace and/or its vent system. Vertical chimneys that run on the outside of a building must be installed inside a chase.

  • In cold climates, Hearth & Home Technologies recommends that the chase be well insulated using batt type insulation between the joists.

  • Construction of the chase may vary with the type of building.

  • These instructions are not substitutes for the requirements of local building codes. Local building codes MUST be checked.

  • Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner. All outer walls need to be insulated.

  • Building codes require false ceiling and ceiling firestops/ attic shields at each floor of the chase or every 10 ft (3048 mm) of clear space to control spread of fire.

  • Walls, ceiling, base plate and cantilever floor at the first level of the chase should be insulated (see Figure 3.3.)

  • Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally,

  • Hearth & Home Technologies recommends that the inside surfaces be drywalled and taped (or the use of an equivalent method) for maximum air tightness.

  • Holes and other openings should be caulked with high temperature caulk or stuffed with unfaced fiberglass insulation

  • WARNING! You must install false ceilings and ceiling firestops at each floor of the chase or every 10 ft (3.05 m) to control spread of fire.
    WARNING! Risk of Fire! DO NOT seal area between fire stop opening and chimney pipe except where they enter the attic or leave the warm air envelope of the home (use 600° F sealant).

  • The chase is constructed using framing materials much the same as the walls in your home. A variety of siding materials may be used including brick, stone, veneer brick, or standard siding materials.

  • In constructing the chase, several factors must be considered

    • Maintain a 2 in. (51 mm) air space around the chimney.
    • The chase top must be constructed of noncombustible material.
    • In cold climates, a firestop spacer and attic insulation shield should be installed in an insulated false ceiling at the 8 ft. (2438 mm) level above the fireplace assembly. This reduces heat loss through the chase.
    • In cold climates, the walls of the chase should be insulated to the level of the false ceiling as shown in Figure 3.3. This will help reduce heat loss from the home around the fireplace.
  • WARNING! Risk of Fire! You must maintain a minimum 2 in. (51 mm) air space clearance to insulation and other materials surrounding the chimney system.

    • Insulation and other materials must be firmly secured to prevent accidental contact with chimney system.
    • The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney.
    • Failure to prevent contact between insulation or other materials and chimney system may cause overheating and fire

Three examples of chase applications are shown in Figure 3.4.

  • Fireplace and chimney enclosed in an exterior chase.
  • Chimney offset through exterior wall and enclosed in chase.
  • Chase constructed on roof

Majestic-BE36-Woodburning-Fireplace-FIG- \(9\)

Frame the Fireplace

NOTICE : Hearth extension design must be determined before installation of fireplace.
If the fireplace is placed on the floor the maximum height of a finished raised hearth is 7 1/2”. If you want a higher raised hearth the fireplace must be placed on a platform.
WARNING! Risk of Fire. A raised hearth extension built flush with the fireplace opening or less than 4 in. (102 mm) below the fireplace opening requires the fireplace be installed on a non-combustible surface.
WARNING! Risk of Fire! Comply with all minimum clear-ances specified.

  • A minimum 1/2 in. (13 mm) air clearance must be maintained at the back and sides of the fireplace assembly.
  • Chimney sections at any level require a 2 in. (51 mm) minimum air space clearance between the framing and chimney section.

WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles. DO NOT pack required air spaces with insulation or other materi-als.
Figure 3.5 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All required clearances to combustibles around the fireplace must be adhered to. See Figure 3.2. Any framing across the top of the fireplace must be above the level of the top standoffs.
The finished cavity depth must be no less than 21 3/8 in. (543 mm) from the finished backwall to the outside of front wall framing.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
NOTE : Before framing up the chase, consider where and how the chimney will run. If there are obstacles that might be in the way, it may be necessary to make the chase larger than shown to allow for offsets to be used. Refer to offset chart on page 16 if needed.

Secure and Level the Fireplace

This fireplace may be placed on either a combustible or noncombustible continuous flat surface. Follow the instruc-tions for framing in Section 3. Slide the fireplace into posi-tion. Be sure to provide the minimum 1/2 in. air clearance at the sides and back of the fireplace.
The fireplace should be positioned so the face of the non-combustible material on the fireplace will be flush with the face of the drywall on the walls.
Level the fireplace and shim as necessary.
WARNING! Risk of Fire! Prevent contact with sagging, loose insulation.

  • DO NOT install against vapor barriers or exposed insulation.
  • Secure insulation and vapor barriers.
  • Provide minimum air space clearances at the sides and back of the fireplace assembly.Majestic-BE36-Woodburning-Fireplace-FIG- \(10\)

Protective Metal Hearth Strips

WARNING! Risk of Fire! Protective metal hearth strips MUST be installed on combustible surfaces. DO NOT cover metal strips with combustible materials. Sparks or embers may ignite flooring.
WARNING! Risk of fire! High temperatures, sparks, embers or other burning material falling from the fireplace may ignite flooring or concealed combustible surfaces.

  • Protective metal hearth strips MUST be installed.
  • Hearth extensions MUST be installed exactly as specified.
  • Locate the two protective metal hearth strips measuring approximately 26 in. x 4 in. (660 mm x 102 mm) included with this fireplace.
  • Slide each metal strip 2 in. (51 mm) under front edge of fireplace.
  • Overlap strips in the middle of fireplace opening by 1 in.(25 mm) minimum.
  • Metal strips must extend beyond the front and sides of the fireplace opening by at least 2 in. (51 mm), Figure 3.6).
  • Protect the front of a platform elevated above the hearth extension with metal strips (not included with fireplace) per Figure 3.6. See Section 7 for hearth extension instructions.

Outside Air Kit (optional)

If you install an outside air kit, Hearth & Home Technologies recommends you utilize the shortest duct run to optimize the performance of the outside air kit and install a P-trap (see Figure 3.10). The outside air inlet hood should be po-sitioned in a manner that will not allow snow, leaves, etc. to block the inlet. In some installations the air duct may need to be run vertically. In such an installation, a 3 ft (914 mm) height difference must be maintained from the top of the uppermost chimney section to the outside air inlet hood.

NOTE : The maximum length of a 4 inch diameter duct is 20 feet. The duct can be extended up to a maximum of 40 feet by using 6 inch duct. A 4 inch to 6 inch adapter will be needed. (Not included).
NOTE : The minimum cross-sectional area of the 4 inch inlet hood is 7.0 square inches.
Refer to Figures 3.8 and 3.9 when placing the outside air inlet hood.
The outside air kit is installed on the left hand side of the fireplace.

  • Cut a 4-1/2 in. (114 mm) hole in outside wall to accommodate air piping.
  • Use 4 in. (102 mm) flex (not supplied) to directly connect outside air to fireplace intake. Insulate the pipe to prevent frost condensation.
  • Seal between the wall and the pipe with silicone to prevent moisture penetration and air leaks.
  • Seal between the outside air inlet hood and the house with silicone to prevent air infiltration.

CAUTION! Risk of Fire or Asphyxiation! DO NOT draw outside combustion air from wall, floor or ceiling cavity, or enclosed spaces such as an attic or garage.

  • DO NOT place outside air inlet hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace.
  • Locate outside air inlet hood to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause combustion air starvationMajestic-BE36-Woodburning-Fireplace-FIG- \(13\)
  • CAUTION! Risk of Cuts/Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharpMajestic-BE36-Woodburning-Fireplace-FIG- \(14\)

Chimney and Termination Requirements

Chimney Requirements
Vertical distances are measured from the base of the fireplace as shown in Figure 4.1

Table 4.1 Chimney Requirements

  • Minimum overall straight height 13 (3.96 m)
  • Minimum height with offset/return 14.5 ft (4.42 m)
  • Maximum height 90 ft (27.43 m)
  • Maximum chimney length between an offset and return 20 ft (6.1 m)
  • Maximum distance between chimney stabilizers 35 ft (10.67 m)
  • Double offset/return minimum height 20 ft (6.1 m)
  • Maximum unsupported chimney length between the offset and return 6 ft (1.83 m)
  • Maximum unsupported chimney height above the fireplace 35 ft (10.67 m)
  • Maximum unsupported chimney above roof 6 ft (1.83 m)

NOTICE : A maximum of two pairs of offsets and returns may be used.
WARNING! Risk of Fire! You must maintain 2 in. (51 mm) air space clearance to insulation and other combustible materials around the chimney system. Failure to do so may cause overheating and fire.
NOTICE : You must provide support for the pipe during construction and check to be sure inadvertent loading has not dislodged the chimney section from the fireplace or at any chimney joint

Table 4.2 Chimney Component Dimensions

Offsets/Returns

  • Use an offset/return to bypass overhead obstructions.

  • An offset and return can be used as a single entity or separated by chimney section(s).
    WARNING! Risk of Fire! DO NOT use offset/returns greater than 30°. Chimney draft will be restricted and could cause overheating and fire. Secure offsets with screws ( not to exceed 1/2” / 13 mm in length) Secure returns with strapping. Straight chimney sections may be secured with screws. Keep chimney sections from separating or twisting.

  • Measure the shift needed to avoid the overhead obstruction. Refer to dimension A in Figure 4.2.

  • Find the appropriate A dimension listed in Table 4.3. The B dimension coinciding with the A dimension measurement in Table 4.3 represents the required vertical clearance needed to complete the offset/return.

  • Read across the chart to find the number of chimney sections/model numbers needed between the offset and return.

Example:

  • Your “A” dimension from Figure 4.2 is 14-1/2 in. (368 mm).
  • Using Table 4.3 the dimension closest to, but not less than 14-1/2 in. (368 mm) is 14-1/2 in. (368 mm) using a 30° offset/return.
  • You determine from the table that you need 34-1/8 in. (867 mm) (Dimension “B”) between the offset and return.
  • The chimney component that best fits your application is one SL324.

Table 4.3 Offset Dimensions

15-degree| 30-degree| ****



SL306

| ****



SL312

| ****



SL318

| ****



SL324

| ****



SL336

| ****



SL348

---|---|---|---|---|---|---|---
A| B| A| B
in.| mm| in.| mm| in.| mm| in.| mm
1 5/8| 41| 13 3/8| 340| 3 5/8| 92| 15 1/2| 394| –| –| –| –| –| –
2 7/8| 73| 17 3/4| 451| 5 1/2| 140| 18 5/8| 473| 1| –| –| –| –| –
4 1/8| 102| 22 3/8| 568| 7 1/4| 184| 21 3/4| 552| 2| –| –| –| –| –
4 1/2| 114| 23 5/8| 600| 8 1/2| 216| 23 3/4| 603| –| 1| –| –| –| –
5 3/4| 146| 28 1/4| 718| 10 1/4| 260| 27| 686| 1| 1| –| –| –| –
6| 152| 29 3/8| 746| 11 1/2| 292| 29| 737| –| –| 1| –| –| –
7 1/4| 184| 34| 864| 13 1/4| 337| 32 1/8| 816| –| 2| –| –| –| –
7 3/4| 197| 36 1/8| 918| 14 1/2| 368| 34 1/8| 867| –| –| –| 1| –| –
8 3/4| 222| 39 3/4| 1010| 16 1/4| 413| 37 3/8| 949| 1| –| –| 1| –| –
10 3/8| 264| 45 5/8| 1159| 19 1/4| 489| 42 1/2| 1080| –| –| 2| –| –| –
10 5/8| 270| 46 3/4| 1187| 20 1/2| 521| 44 5/8| 1133| –| –| –| –| 1| –
11 7/8| 302| 51 3/8| 1305| 22 1/4| 565| 47 3/4| 1213| 1| –| –| –| 1| –
13 1/2| 243| 57 1/4| 1454| 25 1/4| 641| 52 7/8| 1343| –| –| –| 2| –| –
13 3/4| 349| 58 3/8| 1483| 26 1/2| 673| 55| 1397| –| –| –| –| –| 1
15| 381| 63| 1600| 28 1/4| 718| 58 1/8| 1476| 1| –| –| –| –| 1
16 1/2| 419| 68 3/4| 1746| 31 1/4| 794| 63 1/4| 1607| –| 1| –| –| –| 1
18| 457| 74 5/8| 1895| 34 1/4| 870| 68 1/2| 1740| –| –| 1| –| –| 1
19 5/8| 498| 80 3/8| 2042| 37 1/4| 946| 73 3/4| 1873| –| –| –| 1| –| 1
20 5/8| 524| 84 1/8| 2137| 39 1/8| 994| 76 7/8| 1953| 1| –| –| 1| –| 1
22 3/4| 578| 91 7/8| 2334| 43 1/4| 1099| 84 1/8| 2137| –| –| –| –| 1| 1
24| 610| 96 1/2| 2451| 45 1/8| 1146| 87 1/4| 2216| 1| –| –| –| 1| 1
25 7/8| 657| 103 1/2| 2629| 49 1/4| 1251| 94 1/2| 2400| –| –| –| –| –| 2

Proper assembly of air-cooled chimney parts result in an overlap at chimney joints of 1-1/4 in. (32 mm). Effective length is built into this chart

Termination Requirements

  • Install a cap approved and listed for this fireplace system.
  • Locate cap where it will not become plugged by snow or other materials.
  • Locate cap away from trees or other structures.
  • The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m).
  • The distance required between caps is shown below.Majestic-BE36-Woodburning-Fireplace-FIG- \(18\)Majestic-BE36-Woodburning-Fireplace-FIG- \(19\)

Chimney Installation

Typical Chimney System

NOTICE: Chimney performance may vary.

  • Trees, buildings, roof lines and wind conditions affect performance.
  • Chimney height may need adjustment if smoking or overdraft occurs.Majestic-BE36-Woodburning-Fireplace-FIG- \(20\)

Assemble Chimney Sections

Use only those components described in this manual.
Substitute or damaged chimney components could impair safe operation and cause overheating and fire.
Attach either a straight chimney section or an offset to the top of the fireplace (depending on your installation require-ment). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.
The inner flue is placed to the inside of the flue section be-low it. The outer casing is placed outside the outer casing of the chimney section below it. See Figure 5.2.
NOTICE : Chimney sections cannot be disassembled once locked together. Plan ahead!

  • Lock chimney sections and/or offsets/returns together by pushing downward until the top section meets the stop bead on the lower section.

  • Pull on the top section to make sure it is fully engaged and will not separate.

  • You may use #6 or #8 sheet metal screws no longer than 1/2 in. (13 mm) to fasten chimney sections together. Do NOT penetrate inner flue.
    WARNING! Risk of Fire! You MUST use screws to fasten offset/returns to chimney sections to keep the chimney parts from twisting. Failure to do so could cause fire.

  • Fasten offset/returns to chimney sections. Insert the screws (provided) through the predrilled holes. Do NOT penetrate inner flue.

  • Secure chimney returns with hanger straps provided; fasten to studs or joists.

  • Vertical straight runs of chimney must be supported every 35 ft (10.7 m).

WARNING! Risk of Fire! DO NOT install substitute or damaged chimney components.

Install Chimney Air Kit

  • Required in Canada.
  • Follow instructions included with accessory.

Secure Offset/Return

When offsets and returns are joined to straight pipe sec-tions, they must be locked into position with screws. To pre-vent gravity from pulling the chimney sections apart, the returns and the chimney stabilizers have hanger straps for securing these parts to joists or rafters. See Figure 5.3.

Use # 6 or # 8 sheet metal screw, or larger, no longer than 1/2 in. (13 mm).

WARNING! Risk of Fire!

  • Secure offsets with screws (not to exceed 1/2 in./13 mm In length).
  • Secure returns with strapping.
  • Straight chimney sections may be secured with screw (not to exceed 1/2 in./13 mm In length) at the joints.
  • Keep chimney sections from separating or twisting

Install Ceiling Firestops
CAUTION! Risk of Fire! Ceiling firestops must be used whenever the chimney penetrates a ceiling/floor.

  • Chase construction requires ceiling firestops at each floor or every 10 ft. (3.05 m) of clear space.
  • The ceiling firestop slows spread of fire and reduces cold air infiltration
  • Install a ceiling firestop whenever chimney penetrates ceiling/floor.
  • Mark and cut an opening in ceiling as shown in Figure 5.4.
  • Frame the opening with the same size lumber used in the ceiling joists.
  • Nail the ceiling firestop to the bottom of the ceiling joists when there is a room above.
  • Use an attic insulation shield if the ceiling is insulated. The ceiling firestop may then be attached above or below the joists.Majestic-BE36-Woodburning-Fireplace-FIG- \(23\)

WARNING! Risk of Fire! DO NOT seal area between firestop opening and chimney pipe except where they enter the attic or leave the warm air envelope of the home (use 600° F sealant).

Install Attic Insulation Shield

WARNING! Risk of Fire! You MUST install an attic insulation shield when there is any possibility of insulation or other combustible material coming into contact with the chimney.

  • DO NOT pack insulation between the chimney and the attic insulation shield.
  • Failure to keep insulation and other materials away from chimney pipe could cause fire.
  • DO NOT offset chimney inside insulation shield.
  • Combustible material may come into contact with the attic insulation shield as long as the required clearances are maintained to the chimney pipe.

Installation of a ceiling firestop is required:

Note : In Canada a CAS8 must be installed. See instructions provided with kit.

  • Refer to Figures 5.5, 5.6, 5.7.
  • If the attic shield is pre-rolled continue. If it is a flat part, try and roll it up to aid in wrapping it around the chimney.
  • Pre-bend all the tabs in at the top to 45°.
  • Wrap the shield (around the chimney if already installed) until you have an overlap and the three holes on each side match up (large holes on top).
  • Insert three screws into the matching holes to form a tube starting at the bottom.
  • Bend the tabs on the bottom of the tube inward to 90° to maintain chimney air space.
  • Rest the insulation shield on the ceiling firestop below.
  • Tape off any opening around the bottom.

If you wish to make a custom shield or barrier, follow these guidelines:

  • Metal is preferred, although any material stiff enough to hold back the insulation can be used.
  • WARNING! Risk of Fire! Use of cardboard or other materials that can deflect under humidity or other environmental conditions is not recommended.
  • The shield or barrier must be tall enough to extend above the insulation and prevent blown-in insulation from spilling into the cavity and accommodate the amount of insulation as required by the National Building Code.
  • Maintain specified air spaces around chimney.
  • Check instructions and local codes for further details

Double-check the Chimney Assembly

  • Continue assembling the chimney sections up through the ceiling firestops as needed. While doing so, be aware of the height and unsupported chimney length limitations given under Section 5.
  • Check each section by pulling up slightly from the top to ensure proper engagement before installing the succeeding sections. If they have been connected correctly, they will not disengage when tested.

Roof PenetrationMajestic-BE36-Woodburning-Fireplace-FIG-
\(27\)

  • Refer to Figure 5.8.
  • Plumb from roof to center of chimney.
  • Drive a nail up through roof to mark center of pipe.
  • Measure to either side of nail and mark the 14-1/2 in. x 14-1/2 in. (368 mm x 368 mm) opening required.
  • Measure opening on the horizontal; actual length may be larger depending on roof pitch.
  • Cut out and frame opening

Install Flashing

  • Assemble chimney so it passes through the framed opening.

  • Slip the flashing over the chimney.
    NOTICE : Roofing shingles must be below the flashing plate on the lower side of a sloped roof and over the flashing plate on the sides and top.

  • Nail the flashing to the roof. Keep gaps between the flashing plate and the roof to a minimum.

  • Caulk the flashing plate and roof junction as well as the vertical seam on the flashing. All nail heads must be caulked with a roofing sealant.

  • Caulk the overlap seam of any exposed pipe sections that are located above the roof line to prevent leaks.

Install Chase/Chase TopMajestic-BE36-Woodburning-Fireplace-FIG-
\(29\)Majestic-BE36-Woodburning-Fireplace-FIG-
\(30\) Majestic-BE36-Woodburning-Fireplace-FIG-
\(31\)Majestic-BE36-Woodburning-Fireplace-FIG-
\(32\) Majestic-BE36-Woodburning-Fireplace-FIG-
\(34\)

  • You MUST use a chase top in a chase installation. Chase tops may be field constructed.

  • Include a turndown and drip edge to prevent water from seeping into the chase.

  • Include a 2 in. (51 mm) soldered, welded or spun collar around pipe opening to keep water out.

  • Provide a 1/8 in. (3 mm) gap around the flue pipe.

  • Slope the chase top downward away from the opening.
    WARNING! Risk of Fire! DO NOT caulk the pipe to the chase top collar.

  • Caulk all seams to prevent leaks

Termination Cap Requirements

  • Install a cap approved and listed for this fireplace system.
  • Locate cap where it will not become plugged by snow or other materials.
  • Locate cap away from trees or other structures.
  • The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m)

Install Termination Cap
Install the chimney sections up through the chase enclosure.

  • Caulk the overlap seam of any exposed pipe sections that are located above the roof line to prevent leaks.
  • Refer to termination cap instructions.
    WARNING! Risk of Fire! The minimum overlap of cap to pipe (as shown in the following illustrations) MUST be met or chimney may separate from cap. Separation allows sparks, heat and embers to escape.
    NOTICE : Paint the termination cap with rust-resistant paint to protect against the effects of corrosion on those\ parts exposed to the weather.

Shrouds

  • WARNING! Risk of Fire! Shrouds must be constructed as specified. Improper construction may overheat chase top.
  • NOTICE : Some regional codes require an agency-Listed shroud. Consult your local building officials.
  • Shrouds may be field constructed where permitted by regional building codes.
  • The shrouds must be constructed from minimum .018 in. (26 ga) thick aluminized steel.
  • Some shrouds require a radiation shield. Use where specified.

Radiation Shield
The radiation shield must be constructed of minimum 26 ga thick sheet metal Majestic-BE36-Woodburning-Fireplace-FIG- \(35\)

Field Constructed Shrouds
The following field-constructed shroud designs have been tested for HHT fireplace systems and termination caps.

Open Top Shroud
TR342/344TV (top vent) caps do not require a radiation shieldMajestic-BE36
-Woodburning-Fireplace-FIG- \(36\)

TR342/344 caps require radiation shield unless installed partially above the shroud. The TR cap must be raised to the minimum dimensions (or greater) above the shroud or install a TR-TVK. Refer to Figure 6.3.Majestic-BE36
-Woodburning-Fireplace-FIG- \(37\)

Mailbox Style Shroud
Radiation shield requiredMajestic-BE36-Woodburning-Fireplace-FIG-
\(38\)

Roofed Style Shroud
Radiation shield requiredMajestic-BE36-Woodburning-Fireplace-FIG-
\(39\)

Finishing

Finishing Material
Refer to Sections 1.B. and Sections 1.C. for combustible/ non-combustible materials. Refer to Figure 7.1 for noncombustible zoneMajestic-BE36
-Woodburning-Fireplace-FIG- \(40\)Majestic-BE36-Woodburning-Fireplace-FIG- \(41\)

WARNING! Risk of Fire! You must maintain clearances.

  • DO NOT cover metal fireplace front with combustible materials.
  • Install combustible materials only to specified clearances on top front and side edges.
  • DO NOT place header or combustible framing below top standoffs.
  • Complete framing and apply drywall over framing.
  • Facing material can butt up to metal face and columns of fireplace.
  • Only non-combustible materials may be used to cover the metal fireplace front.
  • A bead of 300-deg F minimum non-combustible sealant must be used to close off any gaps at the top and sides between the fireplace and drywall to prevent cold air leaks.

Hearth Extension, Building and Finishing

WARNING! Risk of Fire! High temperatures, sparks, embers or other burning material falling from the fireplace may ignite flooring or concealed combustible surfaces.

  • Protective metal hearth strips MUST be installed.
  • Hearth extensions MUST be installed exactly as specified

A hearth extension must be installed with all fireplaces to protect the combustible floor in front of the fireplace from both radiant heat and sparks.

  • You MUST use a hearth extension with this fireplace.
  • Refer to Figure 7.3 for minimum dimensions.
  • This fireplace has been tested and approved for use with a hearth extension insulated to a minimum R value of 1.03.
  • The hearth extension material MUST be covered with tile, stone or other non-combustible material.
  • Manufactured hearth materials will usually have a published R value (resistance to heat) or k value (conductivity of heat). Refer to the formula in Table 7.1 to convert a k value to an R value,
  • Refer to Table 7.2 for hearth extension insulation alternatives.

WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for discoloration, cracking or other material failures of finishing materials due to heat exposure or smoke.

Choose finishing materials carefully.

WARNING! Risk of Fire!

  • Maintain clearances.
  • Framing or finishing material used on the front of the fireplace closer than the minimums listed, must be constructed entirely of non-combustible materials (i.e., steel studs, concrete board, etc.).

WARNING! Risk of Fire!
Hearth extensions are to be installed only as illustrated to prevent high temperatures from occurring on concealed combustible materials.

Hearth Extension Insulation Alternatives, R Value = 1.03



Material

| ****

k per inch thick

| ****

r per inch thick

| Minimum thickness required
Hearth & Home HX3, HX4| 0.49| 2.06| 1/2 in.
USG Micore 300™| 0.49| 2.06| 1/2 in.
USG Durock™ Cement Board| 1.92| 0.52| 2 in.
Cement Mortar| 5.0| 0.20| 5 1/8 in.
Common Brick| 5.0| 0.20| 5 1/8 in.
Ceramic Tile| 12.50| 0.08| 12 1/4 in.


Armstrong™ Privacy Guard Plus

| ****

0.46

| ****

2.18

| ****

1/2 in.

Marble| 14.3-20.0| 0.07-0.05| 14 5/8 in. – 20 3/8 in.

Majestic-BE36-Woodburning-Fireplace-FIG- \(42\)

WARNING! Risk of Fire. A raised hearth extension built flush with the fireplace opening or less than 4 in. (102 mm) below the fireplace opening requires the fireplace be installed on a non-combustible surface.

Hearth Extension 4” or more Below Fireplace OpeningMajestic-BE36
-Woodburning-Fireplace-FIG- \(43\)

Vinyl Flooring

Vinyl Flooring is sensitive to heat. A 48-inch minimum depth hearth extension is recommended when using
vinyl flooring up to the wall. See Figure 7.4.
Notice: Clearances that do not meet the minimum guidelines could result in damage or buckling to the vinyl flooring and is done at the installer’s risk.
Hearth and Home Technologies does not recommend adhesive-based vinyl flooring due to thermal expan-sion. Floating-style flooring can be used, but will reach temperatures up to 110°F in a room with ambient temperatures of 70°F. Consult flooring specifications to ensure compatibility.

Hearth Extension Less Than 4” Below Fireplace Opening

  • The hearth framing must be constructed of non-com-bustible materials (such as metal framing or equivalent material) and placed on HX3(s), HX4(s), or equivalent material. See Figures 7.4 and 7.5.
  • When creating the platform, allow for the thickness of the non-combustible finishing materials.
  • Seal gaps between the hearth extension and the front of the fireplace with a bead of non-combustible sealant or grout.Majestic-BE36-Woodburning-Fireplace-FIG- \(44\)

Fireplace Opening and Hearth Extension Flush with the Floor

  • Non-combustible flooring a minimum of 20 in. (762 mm) in front of and 12 in. (305 mm) to each side of the fuel opening is required on the BE36 and BE42.
  • The hearth framing must be constructed of non-combustible materials (such as metal framing or equivalent material) and placed on HX3(s), HX4(s), or equivalent material.
  • When creating the platform, allow for the thickness of the non-combustible finishing materials.
  • Seal gaps between the hearth extension and the front of the fireplace with a bead of non-combustible sealant or grout.

Non-Combustible Sealant Material

After completing the framing and applying the facing materials over the framing, a bead of noncombustible sealant must be used to close off any gaps at the top and sides between the fireplace and hearth.

Mantel and Wall Projections

The combustible mantel may have a maximum depth of 12 in. (305 mm) positioned 12 in. (305mm) above the fire-place opening. Combustible trim pieces that project no more than 1 1/2 in. (38 mm) from the face of the fireplace can be placed no closer than 6 in. (152 mm) from the top of the decorative front. Combustible trim must not cover:

  • the metal surfaces of the fireplace
  • where the non-combustible board is placed over the metal surfaces
  • the space between the metal face of the fireplace and framing members

WARNING! Risk of Fire!

You must seal around the finishing material to fireplace.

WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for discoloration, cracking or other material failures of finishing materials due to heat exposure or smoke.

  • Choose finishing materials carefully.Majestic-BE36-Woodburning-Fireplace-FIG- \(48\)

Sidewalls/Surrounds

  • Locate adjacent combustible sidewalls a minimum of 12 in. (305 mm) from fireplace opening.
  • Mantle leg, surround, stub wall, whether combustible or non-combustible, may be constructed as shown in Figure 7.11.Majestic-BE36-Woodburning-Fireplace-FIG- \(49\)

Fireplace Setup

Gas Log/Lighter Provision
WARNING! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

  • DO NOT install unvented gas logs
  • Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

  • Maximum input is 100,000 BTU/hr.
  • Decorative gas appliance must be certified to ANSI Z21.60/CSA 2.26 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.
  • Must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1 and Natural Gas Installation Code, CAN/CGA-B149.1-M95 or the Propane Installation Code, CAN/CGA-B149.2-M95.
  • A gas log set must incorporate a gas shutoff.
  • Gas Log set requires the damper to be locked fully open.
  • A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s instructions.
  • Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.
  • Seal refractory around pipe with fireplace mortar or a non-combustible sealant.Majestic-BE36-Woodburning-Fireplace-FIG- \(50\)

Wood Burning Inserts

WARNING! Risk of Fire! Improper installation of wood in-serts may cause fireplace or chimney system to overheat.
If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

  • Cooling air openings at the top of the chimney must not be obstructed in any manner.
  • Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Reference Materials

Chimney Components

Catalog # Description
CAK4A Chimney Air Kit
ID4/ID6 Insulated Duct/Outside Air
UD4/UD6 Uninsulated Duct/Outside Air
SL306 Chimney Section – 6 in. (152 mm) long
SL312 Chimney Section – 12 in. (305 mm) long
SL318 Chimney Section – 18 in. (457 mm) long
SL324 Chimney Section – 24 in. (610 mm) long
SL336 Chimney Section – 36 in. (914 mm) long
SL348 Chimney Section – 48 in. (1219 mm) long
CAS8 Attic Shield Kit
SL3 Chimney Stabilizer
SL315 Chimney Offset/Return – 15 deg
SL330 Chimney Offset/Return – 30 deg
FS338 Ceiling Firestop – Straight
FS339 Ceiling Firestop – 15 deg
FS340 Ceiling Firestop – 30 deg
AS8 SL300 Straight Attic Insulation Shield, 24 in. (610 mm)
JB877 Chimney Joint Band
CB876 Chimney Bracket
RF370 Roof Flashing – Flat to 6/12 Pitch
RF371 Roof Flashing – 6/12 to 12/12 Pitch
TR344 Round Termination Cap
TR342-B Round Telescoping Termination Cap
ST375 Square Termination Cap
TS345 Square Termination Cap
TS345P Square Termination Cap – Painted
TCT375 Terra Cotta Termination Cap
TR-TVK TR Top Vent Kit
DTO134 Short Octagon Decorative Cap
DTO146 Tall Octagon Decorative Cap
DTS134 Short Square Decorative Cap
DTS146 Tall Square Decorative Cap
LDS33 Decorative Shroud – 3 ft x 3 ft (.91 m x .91 m)
LDS46 Decorative Shroud – 4 ft x 6 ft (1.22 m x 1.83 m)
LDS-BV Decorative Shroud – 26 in. x 26 in. (660 mm x 660 mm)
  Field Constructed Shrouds (See “Woodburning Termination Cap”)
CT-3A-B Adapter – May be used with the following caps
  CT Series
  DT Series

Majestic-BE36-Woodburning-Fireplace-FIG- \(51\) Majestic-BE36-Woodburning-Fireplace-FIG- \(52\) Majestic-BE36-Woodburning-Fireplace-FIG- \(54\) Majestic-BE36-Woodburning-Fireplace-FIG- \(56\) Majestic-BE36-Woodburning-Fireplace-FIG- \(57\) Majestic-BE36-Woodburning-Fireplace-FIG- \(58\) Majestic-BE36-Woodburning-Fireplace-FIG- \(59\) Majestic-BE36-Woodburning-Fireplace-FIG- \(60\) Majestic-BE36-Woodburning-Fireplace-FIG- \(61\) Majestic-BE36-Woodburning-Fireplace-FIG- \(62\)

DTO134   A B C
  in 34 20 24
  mm 864 508 610
DTO146      
  in 46 22.7 26
  mm 1168 576 660
DTS134   A B C
--- --- --- --- ---
  in 34 21.18 24
  mm 864 538 610
DTS146      
  in 46 21.18 26
  mm 1168 538 660

Optional ComponentsMajestic-BE36-Woodburning-Fireplace-FIG-
\(63\) Majestic-BE36-Woodburning-Fireplace-FIG-
\(64\) Majestic-BE36-Woodburning-Fireplace-FIG-
\(65\) Majestic-BE36-Woodburning-Fireplace-FIG-
\(66\)

Majestic, a brand of Hearth & Home Technologies 7571 215th Street West, Lakeville, MN 55044 www.majesticproducts.com
Majestic Royalton Series
BE36/42
4044-197 Installation Manual
Rev M
01/22

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals